InteliLite Global Guide
450
LBI: A
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
1
Description
When this input is closed, no setpoints can be adjusted from controller’s front panel and gen-set mode (OFF /
MAN / AUTO / TEST) cannot be changed.
Note:
Access Lock does not protect setpoints and mode changing from LiteEdit2015. To avoid
unqualified changes the selected setpoints have to be password protected.
Also the buttons Fault Reset
and Horn Reset
are not blocked at all and buttons Start
and Stop
in MAN mode are not blocked.
Access Lock
back to Logical binary inputs alphabetically
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
859
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the second set (setpoints with number 2).
Configuration 2
back to Logical binary inputs alphabetically
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
860
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the third set (setpoints with number 3).
Configuration 3
back to Logical binary inputs alphabetically
LBI: B
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
623
Description
When binary input is active and his delay
Battery Charge Fail Delay (page 189)
is out of time than alarm
Battery Charge Fail (page 564)
is activated, written into history log and logical binary output
is activated.
Battery Charge
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...