InteliLite Global Guide
503
LBO: I
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
39
Description
This output is used for switching between idle speed and nominal speed of the engine during the startup
phase, if this feature (input) is available on the particular engine. In the case of some EFI engines, the
idle/nominal switching is performed over the communication bus.
The output Idle/Nominal closes after the timer
elapses. The
starts
to countdown when
reached. The underspeed protection is not evaluated during
fixed 5 seconds period after reaching
. A Start Fail protection occurs if the RPM drop
below 2RPM during idle.
Image 8.176 Idle/Nominal
Note:
Connect binary output Idle/Nominal to speed governor to switch the speed:
opened = Idle
closed = Nominal
(for normally open contact type)
Idle/Nominal
back to Logical binary outputs alphabetically
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
37
Description
This output is dedicated to controlling the ignition at a gas engine. The output is closed together with binary
output
in the moment when the timer
Sd Ventilation Time (page 173)
elapsed and
the gen-set reaches at least 30 RPM during cranking. The timer
Sd Ventilation Time (page 173)
become
active when the gen-set has been stopped for any Sd protection or the controller has been turned on only
before first cranking attempt. The output is opened 500ms after all Additional running engine indication
Additional running engine indications (page 103)
will be inactive. The output is opened when the gen-
set has to be stopped or in pause during repeated starts.
Ignition
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...