5.4.16 Additional running engine indications
It is helpful to have information other than speed (RPM), whether the engine is rotating or not, especially if RPM
is measured from the generator frequency instead of magnetic pickup. The generator frequency measurement
can be unreliable at very low speeds and/or may have a delayed reaction to sudden and big changes (i.e. in the
moment that the engine has just started…).
The following conditions are evaluated as additional running engine indication:
Voltage on the D+ input is higher than 80% of battery voltage. Connect this input to the D+ (L) terminal of the
charging alternator and enable the D+ function by the setpoint D+ Function. If D+ terminal is not available,
leave the input unconnected and disable the function.
The pickup is not used and frequency is not detected on the pickup input. Connect the pickup input to the W
terminal of the charging alternator if you do not use pickup and the W terminal is available. If not, leave the
input unconnected.
Oil pressure >
Starting Oil Pressure (page 167)
setpoint. The oil pressure is evaluated from the analog input or
from the ECU if an ECU is configured.
At least one phase of generator voltage is >25% of nominal voltage.
These signals are used during start for powering down the starter motor even if still no RPM is measured and
also during stop in order to evaluate if the engine is really stopped.
5.4.17 Voltage phase sequence detection
Controller detects phase sequence voltage terminals. This protection is important after controller installation to
avoid wrong voltage phase connection. There is fix defined phase sequence in controller L1, L2, L3. When the
phases are connected in different order (e.g. L1,L3,L2 or L2,L1,L3) following alarms are detected:
Generator CCW Rotation (page 578)
5.4.18 Gen-set operation states
Engine state machine
Init
Autotest during controller power on.
Not ready
Gen-set is not ready to start.
Example:
When shutdown alarm is active or unit is in OFF mode.
Prestart
Prestart sequence in process,
output is closed.
Example:
Usually used for preheating or processes executed prior gen-set start.
Cranking
Engine is cranking,
output is closed
Pause
Pause between start attempts.
Starting
Starting speed is reached and the Idle timer is running.
Running
Gen-set is running at nominal speed.
Loaded
Gen-set is running at nominal speed and
is closed.
Stop
Stop.
Example:
Automatic or manual stop command was issued, engine is stopping.
Shutdown
Shut-down alarm activated.
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...