InteliLite Global Guide
167
Setpoint group
Engine settings
Related FW
1.2.1
Range [units]
0,0 .. 10,0 [bar] / Disabled
Default value
4,5 bar
Alternative config
NO
Step
0,1 bar
Comm object
9681
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Oil pressure limit for starting. The controller will stop cranking (
goes OFF) if the oil
pressure rises above this limit.
Adjust this setpoint to Disabled to disable starting oil pressure condition.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Starting Oil Pressure
Setpoint group
Engine settings
Related FW
1.2.1
Range [units]
Enabled / ChargeFail / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
9683
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Behavior of D+ terminal.
Enabled
The D+ terminal is used for both functions – “running engine” detection and charge fail
detection.
ChargeFail
The D+ terminal is used for charge fail detection only
Disabled
The D+ terminal is not used.
D+ Function
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...