InteliLite Global Guide
87
Events
specification
Protection
type
Description
Analog Input 2 Sd
SD
Value measured on analog input 2 is </> than
setpoint.
Analog Input 3 Wrn
WRN
Value measured on analog input 3 is </> than
setpoint.
Analog Input 3 Sd
SD
Value measured on analog input 3 is </> than
setpoint.
Analog Input 4 Wrn
WRN
Value measured on analog input 4 is </> than
setpoint.
Analog Input 4 Sd
SD
Value measured on analog input 4 is </> than
setpoint.
Wrn Battery Voltage
WRN
Battery voltage is out of limits given by
and
setpoints.
Binary input
Configurable Warning/BOC/Shutdown alarms on the binary inputs.
Sd Battery Flat
SD
If the controller switches off during starting sequence (
output is active) it doesn’t try to start again and activates
this protection (controller assumes bad battery condition).
Sd Start Fail
SD
Gen-set start failed. All crank attempts were tried without success.
Parameters Fail
NONE
Wrong check-sum of parameters. Happens typically after
downloading new firmware or changing of the parameter. The
controller stays in INIT mode. Check all parameters, change value of
at least one parameter.
Sd Gen Lx >V
BOC Gen Lx <V
(where x=1,2,3)
SD
BOC
The generator voltage is out of limits given by Gen <V BOC and Gen
>V Sd setpoints.
BOC Gen V
Unbalance
BOC
The generator voltage is unbalanced more than the value of
setpoint.
BOC Gen >,
<Frequency
BOC
The generator frequency is out of limits given by
and
Generator < Frequency BOC (page 201)
setpoints.
BOC Current
Unbalance
BOC
The generator current is unbalanced more than the value of
setpoint.
BOC Current IDMT
BOC
Generator current exceeds the limit for IDMT protection given by
and
IDMT Overcurrent Delay (page 196)
setpoints.
BOC Overload
BOC
The load is greater than the value given by
setpoint.
Sd Earth Fault
SD
This alarm is activated when Earth Fault value exceeds
limit for at least
period.
Sd Overspeed
SD
The protection comes active if the speed is greater than
setpoint.
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...