InteliLite Global Guide
591
Related applications
AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator < Frequency BOC (page 201)
Generator <> Frequency BOC Delay (page 202)
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Generator Voltage Unbalance Ph-Ph
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the unbalance of the phase to phase voltage, i.e. the
difference between highest and lowest phase to phase voltage at any given time.
The following setpoints are related to it:
Voltage Unbalance BOC (page 200)
adjusts the maximum allowed difference
between the highest and lowest phase voltage at any given time.
Voltage Unbalance BOC Delay (page 200)
adjusts the alarm delay.
Sd Generator Voltage Unbalance Ph-Ph
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Generator Voltage Unbalance Ph-N
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the unbalance of the phase voltage, i.e. the difference
between highest and lowest phase voltage at any given time. The following
setpoints are related to it:
Voltage Unbalance BOC (page 200)
adjusts the maximum allowed difference
between the highest and lowest phase voltage at any given time.
Voltage Unbalance BOC Delay (page 200)
adjusts the alarm delay.
Sd Generator Voltage Unbalance Ph-N
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Oil Pressure
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that the oil pressure is lover than the pressure set in
setpoint.
Sd Oil Pressure
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...