background image

1.7 Symbols in this manual

3 x Phases

Active

current

sensor

AirGate

Alternating

current

Analog

modem

Battery

Binary

output

Breaker

contact

Breaker

contact

Breaker

Breaker

Breaker

Capacitor

Coil

Connector -

female

Connector -

male

Contact

Contactor

Controller

simplified

Module

simplified

Current

measuring

Current

measuring

Diode

Ethernet

male

Ethernet

female

Fuel

solenoid

Fuse

Fuse switch

Generator

Generator

schematic

Grounding

GSM

GSM

modem

IG-AVRi

IG-AVRi

TRANS

Jumper

Load

Mains

Mains

Mobile

provider

Passive

current

sensor

Pick - up

Relay coil

Relay coil of

slow-

operating

Resistor

Resistor

adjustable

Resistive

sensor

RPTC

RS 232

male

RS 232

female

Starter

Switch -

manually

operated

Transformer

USB type B

male

USB type B

female

Voltage

measuring

Wifi / WAN /

LAN

6

back to Document

information

InteliLite Global Guide

9

Содержание InteliLite MRS16

Страница 1: ...20 246 012 111 E mail info comap cz www comap cz Global Guide InteliLite MRS16 Controller for single gen set applications SW version 1 2 1 Table of contents 2 1 Document information 6 2 System overview 10 3 Applications overview 17 4 Installation and wiring 18 5 Controller setup 44 6 Communication 118 7 Technical data 145 8 Appendix 147 ...

Страница 2: ...s in this manual 9 2 System overview 10 2 1 General description 10 2 1 1 The key features of InteliLite 10 2 2 True RMS measurement 10 2 3 Configuration And Monitoring 10 2 3 1 Supported configuration and monitoring tools 11 2 3 2 Configuration parts 11 2 4 PC Tools 12 2 4 1 LiteEdit2015 12 2 4 2 WebSupervisor 12 2 4 3 WinScope 13 2 5 Plug in Modules 13 2 5 1 CM Ethernet 13 2 5 2 CM 4G GPS 13 2 5 ...

Страница 3: ...gency stop 33 4 4 9 Analog inputs 33 4 4 10 CAN bus and RS485 wiring 36 4 4 11 USB 39 4 4 12 Example of MRS Wiring 40 4 5 Plug in module installation 41 4 6 Maintenance 42 4 6 1 Backup battery replacement 42 5 Controller setup 44 5 1 Default configuration 44 5 1 1 Binary inputs 44 5 1 2 Binary outputs 44 5 1 3 Analog inputs 44 5 2 Controller configuration and PC tools connection 45 5 2 1 USB 45 5 ...

Страница 4: ...ntal Timers 99 5 4 13 Service timers 100 5 4 14 Analog switches 100 5 4 15 Flowchart 102 5 4 16 Additional running engine indications 103 5 4 17 Voltage phase sequence detection 103 5 4 18 Gen set operation states 103 5 4 19 Sensor curves 105 5 4 20 PLC 107 5 4 21 Geo fencing 113 5 4 22 Tier 4 Final 113 5 4 23 Alternate configuration 116 6 Communication 118 6 1 PC 118 6 1 1 Direct communication 11...

Страница 5: ...nary inputs 448 8 1 4 Logical binary outputs 462 8 1 5 Logical analog inputs 514 8 1 6 PLC 546 8 2 Alarms 559 8 2 1 Alarms level 1 559 8 2 2 Alarms level 2 581 8 2 3 Fail sensor and other types 599 8 3 Modules 601 8 3 1 Plug In modules 602 8 3 2 CAN modules 616 ...

Страница 6: ...rs This manual provides general information how to install and operate InteliLite controllers This manual is dedicated for Operators of gen sets Gen set control panel builders For everybody who is concerned with installation operation and maintenance of the gen set 1 3 Legal notice This End User s Guide Manual as part of the Documentation is an inseparable part of ComAp s Product and may be used e...

Страница 7: ...tor LICENSE AGREEMENT CONDITIONS COMAP CONTROL SYSTEMS SOFTWARE and STANDARD TERMS FOR SALE OF PRODUCTS AND PROVISION OF SERVICES available on the www comap cz Used Open Source Software mBed TLS https www mbed com en development software mbed tls http www apache org licenses LICENSE 2 0 1 4 General warnings 1 4 1 Remote control and programing Controller can be remotely controlled In the event that...

Страница 8: ...used again ensure that the proper configuration and setpoint settings are set in the controller The following instructions are for qualified personnel only To avoid personal injury do not perform any action not specified in related guides for product 1 5 Certifications and standards Certificates and standards EN 61000 6 2 EN 61000 6 4 EN 61010 1 EN 61000 2 1 20 C 16 h for std 40 C 16 h for LT vers...

Страница 9: ...t measuring Diode Ethernet male Ethernet female Fuel solenoid Fuse Fuse switch Generator Generator schematic Grounding GSM GSM modem IG AVRi IG AVRi TRANS Jumper Load Mains Mains Mobile provider Passive current sensor Pick up Relay coil Relay coil of slow operating Resistor Resistor adjustable Resistive sensor RPTC RS 232 male RS 232 female Starter Switch manually operated Transformer USB type B m...

Страница 10: ...Various customizations are possible thanks to its configurability Excellent remote communication capabilities High level of support for EFI engines most world producers High reliability 2 2 True RMS measurement This controller measures AC values based on True RMS principle This principle corresponds exactly to the physical definition of alternating voltage effective values Under normal circumstanc...

Страница 11: ...ctions are required at the same time on the same gen set and also the controller hardware does not have so many input and output terminals One of the main tasks of the configuration is mapping of logical firmware inputs and outputs to the physical hardware inputs and outputs 2 3 2 Configuration parts Mapping of logical binary inputs functions or assigning alarms to physical binary input terminals ...

Страница 12: ...s i e preparing controllers with identical configuration and settings 2 4 PC Tools 2 4 1 LiteEdit2015 Configuration and monitoring tool for InteliLite controllers See more in LiteEdit2015 Reference Guide This tool provides the following functions Direct or internet communication with the controller Offline or online controller configuration Controller firmware upgrade Reading writing adjustment of...

Страница 13: ...cluding web server 10 100 Mbit ethernet interface in RJ45 socket Web interface for monitoring and adjustment of the controller Direct IP and or AirGate connection for remote access from LiteEdit2015 MODBUS TCP and SNMP protocols for integration of the controller into building management systems or other remote monitoring purposes Sending of active emails Simply connection via AirGate 2 5 2 CM 4G G...

Страница 14: ...s 10 TCP IP communication over GPRS 2 5 4 CM RS232 485 Communication module with two communication ports RS232 and RS485 interface MODBUS ECU link support Serial connection to LiteEdit2015 2 5 5 EM BIO8 EFCP Hybrid current input and binary input output extension module One additional AC current CT measuring for Earth Fault Current protection EFCP Wide range of measured current one input for 1A and...

Страница 15: ... thermocouples 2 6 2 Inteli IO8 8 The extension module Inteli IO8 8 offers users more binary inputs and outputs for controllers The unit offers the user the flexibility to configure the unit to have 8 binary inputs 8 binary outputs and 2 analog outputs or 16 binary inputs 0 binary outputs and 2 analog outputs via switches inside the controller Configuration 8 8 8 Binary inputs options pull up or p...

Страница 16: ...tion Maximal distance 200 m from the controller UL certified 2 6 4 I LB Local Bridge Communication bridge for sites with multiple controllers for local or remote monitoring and control Direct RS232 RS485 modem Modbus or USB connection to multiple controllers Communication speed up to 57600 bps including Modbus mode Analog GSM ISDN CDMA modem support 6 back to System overview ...

Страница 17: ...d for single applications 3 1 MRS Manual Remote Start The typical scheme of Manual Remote Start application is shown below The controller controls one breaker a generator breaker Feedback from breaker isn t necessary InteliLite controllers can also work without breaker feedback Image 3 1 MRS application overview 6 back to Applications overview ...

Страница 18: ...iagram 21 4 4 Recommended wiring 22 4 5 Plug in module installation 41 4 6 Maintenance 42 6 back to Table of contents 4 1 Package content The package contains Controller Mounting holders Terminal blocks Note The package does not contain a communication or extension modules The required modules should be ordered separately ...

Страница 19: ...illimeters Note Cutout is in millimeters 4 2 2 Mounting The controller is to be mounted onto the switchboard door Requested cutout size is 187 x 132 mm Use the screw holders delivered with the controller to fix the controller into the door as described on pictures below Recommended torque for holders is 0 15 Nm Panel door mounting Overview of parameter x ...

Страница 20: ...GPS Depends on connector of antenna Note The controller is to be mounted into panel doors as a standalone unit using provided metal holders The requested cut out size is 187x132 mm Use the screw holders delivered with the controller to fix the controller into the door Note Enclosure Type rating with mounting instruction For use on a Flat surface of a type 1 enclosure ...

Страница 21: ...1 T44 BIN2 T30 L2 T37 L2 T45 BIN3 T31 L3 T38 L3 T46 BIN4 T47 BIN5 T48 BIN6 T49 BIN7 Image 4 1 Terminal diagram for InteliLite MRS16 CAN1 ANALOG INPUTS BINARY OUTPUTS POWER SUPPLY D T25 L T15 RPM GND T04 BOUT1 T01 BATT T26 COM T16 RPM IN T05 BOUT2 T02 D T27 H T17 A COM T06 BOUT3 T03 BATT T18 A01 T07 BOUT4 T19 A02 T08 BOUT5 T20 A03 T09 BOUT6 T21 A04 T10 BOUT7 ...

Страница 22: ...ng page 27 Binary inputs 43 49 Binary inputs page 31 CAN bus and RS485 H COM L CAN bus and RS485 wiring page 36 Analog inputs 15 21 Analog inputs page 33 Binary outputs 04 10 Binary Outputs page 32 Power supply D Power supply page 23 USB USB page 39 Note Wiring terminal markings to included tightening torque 0 5 N m 4 5 lb in and wire size 2 mm2 12 26AWG ...

Страница 23: ...tening torque 0 79 nm 7 0 In lb Use only diameter 2 0 0 5 mm 12 26 AWWG conductor rated for 75 C minimum use copper conductors only 4 4 2 Grounding The shortest possible piece of wire should be used for controller grounding Use cable min 2 5 mm2 The negative battery terminal must be properly grounded Switchboard and engine must be grounded at common point Use as short cable as possible to the grou...

Страница 24: ...eps operating It is possible to further support the controller by connecting the external capacitor and separating diode or I LBA module The capacitor size depends on required time It shall be approximately thousands of μF The capacitor size should be 5 000 μF to withstand 150 ms voltage dip under following conditions Voltage before dip is 12 V after 150 ms the voltage recovers to min allowed volt...

Страница 25: ... and modules Example Maximal consumption of binary outputs can be 22 A 2 x 10 A on high current outputs for 10 seconds 2 A on all others binary outputs 4 4 4 Measurement wiring Use 1 5 mm2 cables for voltage connection and 2 5 mm2 for current transformers connection Adjust Connection type page 157 Nominal Voltage Ph N page 158 Nominal Voltage Ph Ph page 159 Nominal Current page 156 PT Ratio page 1...

Страница 26: ...sary to ensure that potential difference between generator current COM terminal and battery terminal is maximally 2V Therefore is strongly recommended to interconnect these two terminals together Split phase application Image 4 3 Split phase application IMPORTANT The second phase of split phase connection is connected to the terminal where is normally connected the third phase ...

Страница 27: ...ent Connection Type setpoint Connection type page 157 3Ph4Wire 3Ph3Wire Split Ph Mono Ph options every type matches to corresponding generator connection type Note For fusing of voltage measurement input use T1A or T2A fuse The generator protections are evaluated from different voltages based on Connection type page 157 setting 3Ph 4W Ph Ph voltage Ph N voltage 3Ph 3W Ph Ph voltage Split Ph Ph N v...

Страница 28: ...InteliLite Global Guide 28 ConnectionType 3 Phase 4 Wires Image 4 5 3 phase application with neutral ConnectionType 3 Phase 3 Wires Image 4 6 3 phase application without neutral ...

Страница 29: ...onType Split Phase Image 4 7 Split phase application IMPORTANT The second phase of split phase connection is connected to the terminal where is normaly connected the third phase ConnectionType Mono Phase Image 4 8 Mono phase application ...

Страница 30: ...proper function use a shielded cable Be aware of interference signal from Speed governor when one speed pick up is used If engine will not start Check ground connection from pick up to controllers eventually disconnect ground connection to one of them Use galvanically separate RPM input using separation transformer RPM ISO 1 1 Note In some cases the controller will measure a RPM value even though ...

Страница 31: ...liLite Global Guide 31 4 4 6 Binary inputs Use minimally 1 mm2 cables for wiring of Binary inputs Note The name and function or alarm type for each binary input have to be assigned during the configuration ...

Страница 32: ...ANT Use suppression diodes on all relays and other inductive loads Note Every single low current binary output can provide up to 0 5 A of steady current Note Binary output 1 terminal 4 and binary output 2 terminal 5 are high current outputs 10A for 10s 5A for long term IMPORTANT When operating temperature is higher than 60 C it is strongly recommended to limit output current of high current binary...

Страница 33: ...cy stop IMPORTANT Suppression diodes are not indicated but required 4 4 9 Analog inputs The analog inputs are designed for resistive automotive type sensors like VDO or DATCON The sensors are connected either by one wire the second pole is the sensor body or by two wires In the case of grounded sensors connect the AI COM terminal to the engine body as near to the sensors as possible In the case of...

Страница 34: ...e name sensor characteristic and alarm types for each analog input have to be assigned during configuration Analog inputs with voltage current sensors On each analog input there is a possibility to connect voltage or current output sensor instead of resistive one Recommended wiring connection for these measurements and recommended curves are bellow Voltage sensors Sensor s output range V R1 Ω R2 Ω...

Страница 35: ...0 12 14 16 18 20 22 Ω 99 117 137 155 175 196 219 242 266 291 318 346 V 24 26 28 30 32 34 36 38 40 42 44 46 Ω 375 406 439 473 510 549 589 633 679 729 781 838 V 48 50 52 54 56 58 60 62 64 66 68 70 Ω 873 963 1033 1110 1193 1283 1383 1492 1612 1748 1896 2065 Note This is a conversion of voltage from voltage sensor to appropriate resistance value Use resistance values in LiteEdit2015 to create your spe...

Страница 36: ...a way that the following rules are observed The maximum length of the CAN bus depends on the communication speed For a speed of 250 kbps which is used on the CAN1 bus extension modules ECU the maximum length is 200 m The bus must be wired in linear form with termination resistors at both ends No nodes are allowed except on the controller terminals Shielded cable1 has to be used shielding has to be...

Страница 37: ... ns m Wire crosscut 0 25 mm2 Attenuation 1MHz 2dB 100 m Note Communication circuits shall be connected to communication circuits of Listed equipment Image 4 14 CAN bus topology Note A termination resistor at the CAN is already implemented on the PCB For connecting close the jumper near the appropriate CAN terminal For shorter distances connection within one building Image 4 15 CAN bus wiring for s...

Страница 38: ...ernal units can be connected on the RS485 line in any order but keeping line arrangement no tails no star is necessary The line has to be terminated by 120 Ohm resistors at both ends For shorter distances connection within one building Image 4 17 RS485 wiring for shorter distances 1Protections recommended Phoenix Contact http www phoenixcontact com PT 5 HF 12DC ST with PT2x2 BE base element or Sal...

Страница 39: ...quired for computer connection Use the shielded USB A B cable Image 4 19 USB connection Controller can by also power by USB only for service purpose like a uploading firmware change of configuration etc IMPORTANT Power supply by USB is only for service purpose Binary inputs and outputs are in logical 0 Also plug in modules are not working 1Recommended protections Phoenix Contact http www phoenixco...

Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...

Страница 41: ... module Plug in module has to be inserted under holders Start with holders market by symbol 1 On the controller are also narrows for better navigation After inserting plug in module under holders 1 press it down to holders market by symbol 2 which lock the module Insert the plug in module under holders marked by symbol 1 Then insert the plug in module under holders marked by symbol 2 ...

Страница 42: ...6 years If replacement of backup batter is needed follow these instructions Connect the controller to a PC and save an archive for backup purposes not necessary but recommended Disconnect all terminals from the controller and remove the controller from the switchboard Remove the back cover and all plug in modules Release the rear cover using a flat screwdriver or another suitable tool The battery ...

Страница 43: ... pressure to lock the snaps into the housing Pay attention that the cover is in correct position and not upside down Put back the plugin modules and back cover Power the controller on adjust date and time and check all setpoints 6 back to Installation and wiring ...

Страница 44: ...arms SD OVERRIDE PAGE 461 BIN6 Control lock keyswitch REMOTE CTRL LOCK PAGE 459 BIN7 Free slot NOT USED PAGE 458 5 1 2 Binary outputs Number Description Function BOUT1 Starter motor control STARTER PAGE 510 BOUT2 Fuel solenoid valve FUEL SOLENOID PAGE 493 BOUT3 Indication of breaker state GCB CLOSE OPEN PAGE 495 BOUT4 Activation of any devices before start PRESTART PAGE 506 BOUT5 Gen set can be co...

Страница 45: ...tion of various PC tools to the controller If you require detailed information on each PC tool please use the included Help in those PC tools or download their Reference Guides 5 2 1 USB You may connect to the controller using the USB port In this case standard USB A to B cable should be used Connection using LiteEdit2015 Image 5 1 First screen of LiteEdit2015 select connect to controller Image 5 ...

Страница 46: ...ontroller using RS232 direct connection serial port or USB to RS232 converter may be used The following settings need to be checked in the controller COM1 Mode page 300 Direct Controller Address page 161 has to be set to the same value as in the PC tool Connection using LiteEdit2015 Image 5 4 First screen of LiteEdit2015 select connect to controller ...

Страница 47: ...It is possible to connect to the controller using ethernet port either directly or using ComAp s AirGate service Direct connection When you use direct connection the controller needs to be reachable directly from the PC you use i e one LAN or WAN without any firewalls and other points that may not allow the connection The following settings need to be checked in the controller ...

Страница 48: ...ess page 332 is either set automatically or it can be adjusted to a specific requested value Subnet Mask page 333 is either set automatically or it can be adjusted to a specific requested Gateway IP page 333 can be set here when it is used ComAp TCP Port page 338 number is 23 Make sure that this port is open for communication in your network Connection using LiteEdit2015 Image 5 7 First screen of ...

Страница 49: ...e Image 5 9 WinScope screen AirGate connection You can use ComAp s AirGate service that allows you to connect to any controller via internet no matter what are the restrictions of the local network if the controller can connect to the internet AirGate service will work The following setpoints have to be adjusted ...

Страница 50: ...y or it can be adjusted to a specific requested value Subnet Mask page 333 is either set automatically or it can be adjusted to a specific requested Gateway IP page 333 can be set here when it is used AirGate Connection page 337 has to be set to Enabled AirGate Address page 337 currently there is one AirGate server running at URL airgate comap cz enter this URL into the setpoint Connection using L...

Страница 51: ...InteliLite Global Guide 51 Image 5 11 Second screen of LiteEdit select AirGate Connection using WinScope WinScope doesn t support connection via AirGate ...

Страница 52: ...s Position Picture Description LEFT button Use this button to move left or to change the mode The button can change the mode only if the main screen with the indicator of currently selected mode is displayed Note This button will not change the mode if the controller mode is forced by one of binary inputs listed in the Reference Guide Operating modes chapter RIGHT button Use this button to move ri...

Страница 53: ...rt sequence of the engine STOP button Works in MAN mode only Press this button to initiate the stop sequence of the gen set Repeated pressing of button will cancel current phase of stop sequence like cooling and next phase will continue GCB button Works in MAN and TEST modes only Press this button to open or close the GCB Indicators and others Position Description GENERATOR status indicator There ...

Страница 54: ...ay screens and pages structure Main Screen Symbols Padlock active when LBI ACCESS LOCK is active R active when there is active remote connection to controller Exclamation mark active when there is any alarm in alarmlist Measurement Screens ...

Страница 55: ...InteliLite Global Guide 55 ...

Страница 56: ...InteliLite Global Guide 56 ...

Страница 57: ...InteliLite Global Guide 57 ...

Страница 58: ...InteliLite Global Guide 58 ...

Страница 59: ...InteliLite Global Guide 59 ...

Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...

Страница 61: ...InteliLite Global Guide 61 History Log ...

Страница 62: ...InteliLite Global Guide 62 ...

Страница 63: ...InteliLite Global Guide 63 ...

Страница 64: ...InteliLite Global Guide 64 ...

Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...

Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...

Страница 67: ...InteliLite Global Guide 67 Change password ...

Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...

Страница 69: ...InteliLite Global Guide 69 Log out from controller ...

Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...

Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...

Страница 72: ...InteliLite Global Guide 72 ...

Страница 73: ...S operation 81 5 4 7 Engine cool down and stop 81 5 4 8 Alarm management 82 5 4 9 History log 88 5 4 10 Breaker control 89 5 4 11 Exercise timers 92 5 4 12 Rental Timers 99 5 4 13 Service timers 100 5 4 14 Analog switches 100 5 4 15 Flowchart 102 5 4 16 Additional running engine indications 103 5 4 17 Voltage phase sequence detection 103 5 4 18 Gen set operation states 103 5 4 19 Sensor curves 105...

Страница 74: ...65 counter started Cranking Cranking RPM Starting RPM STARTER PAGE 510 off PRESTART PAGE 506 off Starting D input activated or oil pressure detected or Generator voltage 25 Nominal voltage STARTER PAGE 510 off PRESTART PAGE 506 off Cranking Maximum Cranking Time page 165 1st attempt STARTER PAGE 510 off FUEL SOLENOID PAGE 493 off STOP SOLENOID PAGE 511 on Cranking Fail Pause page 165 timer started...

Страница 75: ...unning Stop RPM 0 Oil pressure not detected Generator vooltage 10V D not active Ready If at least one of engine running indication is detected when Stop Time page 174 elapsed Stop Stop fail Note If all generator parameters are OK and Minimal Stabilization Time page 171 elapsed indicates that GCB is possible to close In AUTO Mode GCB is closed in this moment automatically Note The start up sequence...

Страница 76: ...START PAGE 506 and GLOW PLUGS PAGE 500 are energized for time period given by the setpoints Prestart Time page 166 and Glow Plugs Time page 168 After Prestart Time page 166 and Glow Plugs Time page 168 the output FUEL SOLENOID PAGE 493 is energized and after Fuel Solenoid Lead page 169 the starter of motor is activated by energizing the output STARTER PAGE 510 When one or more of following conditi...

Страница 77: ...InteliLite Global Guide 77 After the idle period has finished the output IDLE NOMINAL PAGE 503 is activated and the start up sequence is finished The Stabilization page 81 phase follows ...

Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...

Страница 79: ...unning engine indications page 103 signals are not evaluated during the start of a gas engine The Pickup must be used in any case The maximum duration that the output STARTER PAGE 510 is energized is determined by the setpoint Maximum Cranking Time page 165 If the engine does not start within this period outputs STARTER PAGE 510 and FUEL SOLENOID PAGE 493 are de energized and a pause with length d...

Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...

Страница 81: ...and the gen set will be cooled down and stopped Note The limits for the generator voltage and frequency are given by setpoints in the Group Generator settings page 194 Note The value of the Minimal Stabilization Time page 171 setpoint has to be lower than the value of Maximal Stabilization Time page 172 setpoint 5 4 5 Connecting to load When the Stabilization page 81 phase is finished the gen set ...

Страница 82: ... Time page 174 If the Stop Time page 174 has elapsed and the engine has still not stopped the STOP SOLENOID PAGE 511 is de energized for 5 s and then energized again for Stop Time page 174 and this repeats until the engine is stopped The output Ignition page 503 is continuously energized until the engine is stopped Stopped gen set evaluation The gen set is considered as stopped when all of followi...

Страница 83: ...o this category This category is not configurable to binary and analog input alarms If an alarm is being evaluated and the appropriate alarm condition is fulfilled the delay of evaluation will start to run The delay is adjustable by a setpoint in the case of built in alarms analog input alarms or is adjusted via configuration window in LiteEdit2015 in the case of binary input alarms If the conditi...

Страница 84: ...actions regarding gen set control Alarm is only displayed in alarmlist History record only HistRecOnl The event is recorded into the history Standard alarm outputs HORN PAGE 502 and ALARM PAGE 476 are not activated Alarm types Level 2 The level 2 level alarm indicates that a critical level of the respective value or parameter has been reached Note It is not possible to start the engine if any red ...

Страница 85: ... negative number In this case the lower limit is set as one half of the RL point of the sensor curve characteristic Image 5 17 Sensor fail detection principle Remote alarm messaging If communication plug in module is connected to the controller the controller can send SMS messages and emails at the moment when a new alarm appears in the Alarmlist page 86 or new event is written in History log page...

Страница 86: ...e omitted User configured alarms An alarm message in the alarmlist begins with a prefix which represents the alarm type e g Wrn Sd BOC Alarm type is selected by user during the configuration of binary or analog input as alarm Then the alarm name follows Name is adjusted by user during the configuration of binary or analog input as alarm ECU alarms The ECU alarms are received from the ECU The alarm...

Страница 87: ... tried without success Parameters Fail NONE Wrong check sum of parameters Happens typically after downloading new firmware or changing of the parameter The controller stays in INIT mode Check all parameters change value of at least one parameter Sd Gen Lx V BOC Gen Lx V where x 1 2 3 SD BOC The generator voltage is out of limits given by Gen V BOC and Gen V Sd setpoints BOC Gen V Unbalance BOC The...

Страница 88: ...int The protection comes if counter reaches zero Wrn Maintenance 2 WRN The period for servicing is set by the Maintenance Timer 2 page 189 setpoint The protection comes if counter reaches zero Wrn Maintenance 3 WRN The period for servicing is set by the Maintenance Timer 3 page 189 setpoint The protection comes if counter reaches zero Charge Alternator Fail WRN Failure of alternator for charging t...

Страница 89: ...tage Vg31 Generator voltage Ph31 Generator Current Ig1 Generator current Ph1 Generator Current Ig2 Generator current Ph2 Generator Current Ig3 Generator current Ph3 Voltage Battery VBat Voltage of battery Analog Input 1 Ain1 Analog input 1 Analog Input 2 Ain2 Analog input 2 Analog Input 3 Ain3 Analog input 3 Analog Input 4 Ain4 Analog input 4 Binary Inputs BIN Controller binary inputs Binary Outpu...

Страница 90: ...control of a contactor Its state represents the breaker position requested by the controller The breaker must react within 5 seconds to a close or open command otherwise an alarm is issued ON coil An output giving a 5 second pulse in the moment the breaker has to be closed The output is intended for control of close coils of circuit breakers OFF coil An output giving a pulse in the moment the brea...

Страница 91: ...ifferent time delays for breaker fail detection see following diagrams When binary output breaker close open is in steady state and breaker feedback is changed the breaker fail is detected immediately no delay Image 5 19 Breaker fail breaker close open in steady position open Image 5 20 Breaker fail breaker close open in steady position close When binary output breaker close open opens there is 5 ...

Страница 92: ...ch as e g periodic tests of the gen set scheduled transfer of the load to the gen set prior to an expected disconnection of the mains etc Related setpoints for timer 1 are Timer 1 Function page 264 Timer 1 Repetition page 265 Timer 1 First Occur Date page 266 Timer 1 First Occur Time page 266 Timer 1 Duration page 266 Timer 1 Repeated page 267 Timer 1 Repeat Day page 270 Timer 1 Day page 269 Timer...

Страница 93: ...ded E g the timer can be adjusted to every 2nd day excluding Saturdays and Sundays Weekly The timer is activated every x th week on selected weekdays The week period x is adjustable E g the timer can be adjusted to every 2nd week on Monday and Friday Monthly The timer is activated every x th month on the selected day The requested day can be selected either as y th day in the month or as y th week...

Страница 94: ...etpoint Than go to Timer 1 Setup and press enter button In Timer 1 Repetition page 265 setpoint select Once mode Than adjust Timer 1 First Occur Date page 266 Timer 1 First Occur Time page 266 and Timer 1 Duration page 266 Note Use left and right buttons to move between timer setpoints Daily mode Set up via LiteEdit2015 To set up timer via LiteEdit2015 go to the setpoint ribbon setpoint group sche...

Страница 95: ...o to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 264 setpoint Than go to Timer 1 Setup and press enter button In Timer 1 Repetition page 265 setpoint select Repeated mode Than adjust Timer 1 First Occur Date page 266 Timer 1 First Occur Time page 266 and Timer 1 Duration page 266 In setpoint Timer 1 Repeated page 267 select Daily and adjust Timer 1 Refresh P...

Страница 96: ...ller go to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 264 setpoint Than go to Timer 1 Setup and press enter button In Timer 1 Repetition page 265 setpoint select Repeated mode Than adjust Timer 1 First Occur Date page 266 Timer 1 First Occur Time page 266 and Timer 1 Duration page 266 In setpoint Timer 1 Repeated page 267 select Weekly and adjust Timer 1 Da...

Страница 97: ...ttings adjust date and time of first occurrence of timer Also adjust the duration of each occurrence of timer Than select the type of monthly repetition and the x th day of repetition Timer 1 Repeat Day In Month page 270 Than select the x th month of repetition Example On image example first start of timer will be 1 1 2016 at 12 00 Duration will be 1 hour Timer will be again activated every 2nd da...

Страница 98: ...t select Repeated mode Than adjust Timer 1 First Occur Date page 266 Timer 1 First Occur Time page 266 and Timer 1 Duration page 266 In setpoint Timer 1 Repeated page 267 select Monthly and adjust type of monthly repetition via Timer 1 Repeat Day page 270 Timer 1 Refresh Period page 268 x th month of repetition and Timer 1 Repeat Day In Month page 270 concrete day in repeated months Second type of...

Страница 99: ...imer will be 1 1 2016 at 12 00 Duration will be 1 hour Timer will be again activated every 4th hour for 1 hour Set up via controller interface In controller go to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 264 setpoint Than go to Timer 1 Setup and press enter button In Timer 1 Repetition page 265 setpoint select Repeated mode Than adjust Timer 1 First Occur...

Страница 100: ...e Timer 1 page 188 Maintenance Timer 2 page 189 and Maintenance Timer 3 page 189 or as values Maintenance 1 page 421 Maintenance 2 page 422 and Maintenance 3 page 422 When the value of counter reaches 0 the alarm Wrn Maintenance 1 page 574 or Wrn Maintenance 2 page 574 or Wrn Maintenance 3 page 574 is active until the respective counter is readjusted back to nonzero value Unused timer has to be ad...

Страница 101: ...tch 13 On page 240 Analog Switch 13 Off page 241 ANALOG SWITCH 13 PAGE 482 AIN SWITCH 14 PAGE 540 Analog Switch 14 On page 243 Analog Switch 14 Off page 244 ANALOG SWITCH 14 PAGE 483 AIN SWITCH 15 PAGE 540 Analog Switch 15 On page 246 Analog Switch 15 Off page 247 ANALOG SWITCH 15 PAGE 483 AIN SWITCH 16 PAGE 541 Analog Switch 16 On page 249 Analog Switch 16 Off page 250 ANALOG SWITCH 16 PAGE 484 A...

Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...

Страница 103: ...one phase of generator voltage is 25 of nominal voltage These signals are used during start for powering down the starter motor even if still no RPM is measured and also during stop in order to evaluate if the engine is really stopped 5 4 17 Voltage phase sequence detection Controller detects phase sequence voltage terminals This protection is important after controller installation to avoid wrong...

Страница 104: ...page 167 or Generator voltage 25 of Nominal Voltage Ph N page 158 Still engine conditions Engine speed RPM Starting RPM page 166 or Oil pressure Starting Oil Pressure page 167 or Generator voltage 50V any phase Note When the engine was running before and all above conditions are fulfilled additional 2s delay is necessary to confirm still engine When any engine running conditions are appeared on st...

Страница 105: ...roller will continuously try to stop the engine Image 5 32 Engine stops after first Stop Time page 174 Electric state machine BrksOff GCB opened 5 4 19 Sensor curves Background of the sensor calibration To correct measuring error of each analog input pressure temperature level etc calibrating constants should be set Calibration is made by adding the value of setpoint Analog Input 1 Calibration pag...

Страница 106: ... raise alarm fail sensor Curve Min Ohm Max Ohm Units VDO 10 Bar 0 2400ohm 0 2400 Bar VDO40 120 C0 2400ohm 0 2400 C VDOLevel 0 2400ohm 0 2400 General line 1 0 1000 ohm General line 2 0 1000 ohm General line 3 0 1000 ohm General line 4 0 1000 ohm General line 5 0 1000 ohm General line 6 0 1000 ohm General line 7 0 1000 ohm General line 8 0 1000 ohm General line 9 0 1000 ohm General line 10 0 1000 oh...

Страница 107: ...locks PLC block Number of blocks OR AND 16 XOR RS 2 Comparator with hysteresis Comp Hyst 2 Comparator with delay Comp Time 2 Timer 1 Delay 2 Force history record Force Hist 2 Force protection Force Prot 2 Working with the editor If the currently opened archive does not contain any PLC program then an empty drawing is created automatically when you select the PLC Editor The procedure of creation of...

Страница 108: ...for more information about blocks Working with sheets Drag the sheet edges to re size the sheet according to your needs Image 5 34 Adjusting PLC sheet Adding PLC blocks Adding PLC block is simple and intuitive Follow the procedure below to add PLC block Select required block from the list of available PLC blocks at the left and drag it into the sheet Double click on the block and adjust properties...

Страница 109: ...press delete button Also delete selection function can by used Note To see context help for selected PLC block just press F1 button Define inputs and outputs Image 5 36 Blank sheet of PLC editor Inputs Sheet inputs are located at the left side of a sheet Follow the procedure below to add or edit an input ...

Страница 110: ... If you create an analog input you can select a source from following categories Ana Values this category contains all analog values available in the controller as analog inputs electrical values values from ECU etc All Setpoints this category contains all setpoints of the controller except the dedicated PLC setpoints Names resolutions and dimensions of these setpoints can not be modified PLC Setp...

Страница 111: ...tput has to be connected to this output to enable configuration of output Image 5 38 PLC outputs IMPORTANT It is necessary to click on Connect button after selecting the output Otherwise PLC output is not connected to output Creating wires Wires can be create between PLC inputs and PLC blocks and between PLC blocks and PLC outputs IMPORTANT Keep the order of starting and finishing connection point...

Страница 112: ...nection only between the outputs and inputs with the same type of value binary or analog Binary values are marker by black pointer analog values are marked with green pointer Note To delete wire just click on it and press delete button Also delete selection function can by used PLC logic execution rules The PLC program is executed every 100ms The blocks are executed in order according to block num...

Страница 113: ...nd based on the evaluation takes an action sends sms stops engine make history record etc Function is enabled by setpoint Geo Fencing page 285 or by logical binary input GEO FENCING ENABLED PAGE 456 Using LiteEdit2015 it is possible to set two concentric geo circles within which the unit is allowed to be located Each geo circle is defined as circular geographic area with centre common for both geo...

Страница 114: ...ment screen is automatically shown once any of selected lamps gets active or change status Deactivating of the lamp will not trigger showing the screen The screen is then shown until operator switch it to another one Alarmlist screen has lower priority so even new alarm appears After treatment screen is still displayed To avoid displaying blank screen inactive lamps are represented by dotted icons...

Страница 115: ...nd inverse colored active lamp icon in required frequency Lamp name Active icon Inactive icon Notes Amber warning lamp Note This value can light or blink on both frequencies Red stop lamp Note This value can light or blink on both frequencies Engine wait to start lamp DPF SCR lamp command Note DPF Diesel Particulate Filter SCR Selective Catalytic Reduction This lamp also activates alarm After Trea...

Страница 116: ...generation inhibition This lamp also activates alarm After Treatment page 576 Analog values Supported analog values DPF Ash Load page 407 DPF Soot Load page 407 DEF Level page 407 available on main measurement screen see description of setpoint Main Screen page 164 Control of After Treatment regeneration function User can force or inhibit regeneration process by activating appropriate binary input...

Страница 117: ...cy Select 2 page 298 ECU Speed Adjustment 2 page 298 Nominal RPM 3 page 296 Nominal Frequency 3 page 295 Nominal Voltage Ph N 3 page 296 Nominal Voltage Ph Ph 3 page 296 Nominal Current 3 page 295 Connection type 3 page 295 ECU Frequency Select 3 page 299 ECU Speed Adjustment 3 page 299 Configuration sets can be changed via logical binary inputs CONFIGURATION 2 PAGE 450 and CONFIGURATION 3 PAGE 45...

Страница 118: ...a RS232 connection The module is plugged into the slot located on the rear side of the controller To find more information about installation of the modules see Plug in module installation on page 41 RS232 interface uses COM1 Mode page 300 port of the controller Use a cross wired serial communication cable with DB9 female connectors and signals Rx Tx GND Note Also USB RS232 convertor can be used I...

Страница 119: ...r To find more information about installation of the modules see Plug in module installation on page 41 This connection type is used for communication with the controller from LiteEdit2015 or any other PC tool This connection can be used regardless of AirGate is switched on or off Only three remote clients can be connected at the same time via AirGate only two remote clients at the same time To co...

Страница 120: ...ddress Mode page 332 to FIXED In that case all setpoints of IP settings IP Address page 332 Subnet Mask page 333 Gateway IP page 333 DNS IP Address 1 page 334 have to be adjusted manually If this method is used several basic rules should be kept to avoid conflicts with the remaining network infrastructure The static IP used in the controller must be selected in accordance with the local network in...

Страница 121: ...d to create multiple port forwarding rules in the same local network AirGate This connection type is intended for remote connection from LiteEdit2015 or any other ComAp PC tool over the Internet in situations where obtaining fixed public IP address is not possible Only two remote clients can be connected at the same time This connection type is active if AirGate connection is enabled Setpoint AirG...

Страница 122: ...setting of setpoints Wrn Message page 329 BOC Message page 329 Sd Messages page 330 Note Firstly setpoint Telephone Number 1 page 322 has to be adjusted Message structure Gen set Name AL Alarm 1 Alarm 2 Alarm x Note Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active SMS commands To control the gen set equipped with InteliLite controller and CM GPRS or CM 4G GP...

Страница 123: ...e will be started and GCB will close Then GCB will open the engine will stop and it will go into AUTO mode again The controller will send back the SMS controller will respond to SMS after every command has been finished not sooner InteliLite Test OK OK OK OK OK OK The value OK or ERROR means if the command has been performed succesfuly or not Emails Event Email The InteliLite controller equipped w...

Страница 124: ...ts Wrn Message page 329 BOC Message page 329 Sd Messages page 330 Note Firstly setpoints Email Address 1 page 326 and SMTP Sender Address page 320 for CM GPRS or SMTP Sender Address page 331 for CM Ethernet have to be adjusted Note Summer Time Mode page 263 and Time Zone page 328 have to be adjusted for correct time in emails Message structure Controller Name XXX Serial number XXX SW branch XXX SW...

Страница 125: ... list Alarm 1 Alarm 2 Alarm 3 History events 0 dd mm yyyy hh mm ss 0 Event 1 1 dd mm yyyy hh mm ss 0 Event 2 2 dd mm yyyy hh mm ss 0 Event 3 Note Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active ...

Страница 126: ...e browser to display the main controller web page like http 192 168 1 254 You will be asked for the controller access code prior to entering the web pages IMPORTANT Do not use the browser navigation buttons as Back Forward or Reload Use the links and the reload button located in the toolbar instead Note Only two remote clients can be connected to the Web Server at one moment If you close your web ...

Страница 127: ... SCADA link in the toolbar to display the scada page The scada page is also the main page which is displayed by default if you just put the CM Ethernet address into the browser after entering the right access code Image 6 8 Web Server Scada screen ...

Страница 128: ...toolbar to display the measurement page Then click to the required group name in the left box to display values of the group in the right box Note The measurement page is automatically refreshed every 60 seconds this time cannot be changed Image 6 9 Web Server measurement screen ...

Страница 129: ...o display setpoints of the group in the right box Click to the required setpoint name or value to change the value If the respective setpoint is protected by password which is indicated by a lock icon by the setpoint name you have to click on the Controller password icon located in the toolbar and then enter valid password Image 6 10 Web Server Setpoints screen ...

Страница 130: ...play the history page Use the control buttons to move within the history file Note The history page is automatically refreshed every 60 seconds If a new record appears in the controller the web page will not show it immediately as e g LiteEdit2015 Image 6 11 Web Server History screen ...

Страница 131: ...ODBUS TCP 133 6 back to Communication 6 2 1 SNMP SNMP is an UDP based client server protocol used for providing data and events into a supervisory system building management system The controller plays the role of a SNMP Agent while the supervisory system plays the role of a SNMP Manager CM Ethernet module is required for SNMP function Supported versions SNMP v1 and SNMP v2c The SNMP Agent functio...

Страница 132: ...y send to the Manager groupRdFix contains read only objects that exist in all controller regardless of the firmware version type and configuration groupRdCfg contains read only objects that depend on the firmware version type and configuration groupWrFix contains read write objects that exist in all controller regardless of the firmware version type and configuration groupWrCfg contains read write...

Страница 133: ...tem or for remote monitoring via 3rd party monitoring tools MODBUS RTU can be used on serial interfaces CM RS232 485 module is required The MODBUS RTU server must be activated by switching the setpoint COM1 Mode page 300 or COM2 Mode page 301 into the Modbus position The serial speed for MODBUS RTU communication is to be adjusted by the setpoint COM1 MODBUS Communication Speed page 301 or COM2 MOD...

Страница 134: ... LSB value Integer16 2 byte signed integer 1 MSB value MSB LSB value LSB Unsigned16 2 byte unsigned integer 1 MSB value MSB LSB value LSB Integer32 4 byte signed integer 2 MSB1 value byte 3 MSB LSB1 value byte 2 MSB2 value byte 1 LSB2 value byte 0 LSB Unsigned32 4 byte unsigned integer 2 MSB1 value byte 3 MSB LSB1 value byte 2 MSB2 value byte 1 LSB2 value byte 0 LSB Binary8 8 bit binary value 1 MS...

Страница 135: ...CD hh LSB1 BCD mm MSB2 BCD ss LSB2 0 Alarm An item of the Alarmlist 27 MSB1 reserved for future use LSB1 reserved for future use MSB2 Alarm level LSB2 Alarm status MSB3 alarm string LSB3 alarm string MSB4 alarm string LSB5 alarm string 1 level 1 yellow 2 level 2 red 3 sensor fail Bit0 alarm is active Bit1 alarm is confirmed String encoding is UTF 8 Error codes exception codes Exception code is ret...

Страница 136: ...4205 4206 2 read Unsigned32 Last application error To be read after the device returns the exception code 04 It contains specific information about the error 4207 4208 2 read write Unsigned32 Writing command argument Reading command return value 4209 1 write Unsigned16 Command code 4010 1 Not implemented 4211 1 write Unsigned16 Password 4212 4213 2 read Unsigned32 Communication status 4214 1 read ...

Страница 137: ...tion 16 3 Write the command code into the register 44210 register address 4209 Use function 6 4 Optional Read the command return value from the registers 44208 44209 register addresses 4207 4208 Use function 3 5 If the command was executed the return value is as listed in the table If the command was accepted but there was an error during execution the return value indicates the reason a 0x0000000...

Страница 138: ... read Data 00F0hex 240dec CRC We read value 240 from register 01053 From table of modbus registers we get dimension of read value and Dec Dec 1 means shift one decimal place to the right So battery voltage is 24 0 V Reading Nominal power Export table of values from LiteEdit Table Values Allowed MODBUS functions 03 04 Register s Com Obj Name Dimension Type Len Dec Min Max Group 01228 9018 Nominal P...

Страница 139: ...t Numbers in Hex 01 03 04 2C 00 01 44 F3 Controller address Modbus function Register address 042Chex 1068dec Number of registers CRC Response Numbers in Hex 01 03 02 00 12 38 49 Controller address Modbus function Length of data 02hex 2 bytes read Data 0012hex 00010010bin CRC Binary inputs is 00010010 It means Binary input 2 and binary input 5 are active Note You can use modbus function 4 insted of...

Страница 140: ...edback Controller I O 00002 Value 8235 Binary Inputs 3 Emergency Stop Controller I O We will read state of MCB Feedback binary input Request Numbers in Hex 01 01 00 01 00 01 AC 0A Controller address Modbus function Register address 0001hex 0001dec Number of registers CRC Response Numbers in Hex 01 01 01 01 90 48 Controller address Modbus function Length of data 01hex 1 byte read Data 01hex active ...

Страница 141: ... List of commands and arguments page 137 Action Command code Argument Return value Engine start 0x01 0x01FE0000 0x000001FF Engine stop 0x01 0x02FD0000 0x000002FE Request 1 2 Numbers in Hex 01 10 10 6F 00 03 06 Controller address Modbus function 10hex 16dec Register address 106Fhex 4207dec Number of registers Data length in bytes Request 2 2 Numbers in Hex 01 FE 00 00 00 01 68 0B Argument Command c...

Страница 142: ...the password is 1234 Request Numbers in Hex 01 06 10 73 04 D2 7C D1 Controller address Modbus function Register address 1073hex 4211dec Password 04D2hex 1234dec CRC Response for success Numbers in Hex 01 06 10 73 00 00 7C D1 Controller address Modbus function Register address 1073hex 4211dec Allways zero CRC Response for bad password Numbers in Hex 01 86 04 43 A3 Controller address Modbus exceptio...

Страница 143: ...1 06 0B C0 00 00 8B D2 Controller address Modbus function Register address 0BC0hex 3008dec Allways zero CRC Writen setpoint nominal power is 100 kW CRC calculation The check field allows the receiver to check the validity of the message The check field value is the Cyclical Redundancy Check CRC based on the polynomial x16 x15 x2 1 CRC is counted from all message bytes preceding the check field Onl...

Страница 144: ...sters Request Numbers in Hex 00 00 00 00 00 06 01 03 04 1D 00 01 transaction identifier usually 0 protocol identifier usually 0 Length of data bytes following Controller address Modbus function Register address 041Dhex 1053dec Number of registers Response Numbers in Hex 00 00 00 00 00 05 01 03 02 00 F0 transaction identifier usually 0 protocol identifier usually 0 Length of data bytes following Co...

Страница 145: ...urement range 5 A Max allowed current 10 A Accuracy 1 5 for full temperature range 1 from 0 C to 50 C Input impedance 0 1 Ω Current measurement Number 7 non isolated Close Open indication 0 2 VDC close contact 6 VDC open contact Binary inputs Number 2 high current output non isolated 5 low current output non isolated Max current 10 A for 10 s 4 A long term 0 5 A Switching to positive supply termin...

Страница 146: ...N 61000 2 1 20 C 16 h for std 40 C 16 h for LT versio n EN 61000 2 2 70 C 16 h EN 61000 2 6 2 25 Hz 1 6 mm 25 10 0 Hz 4 0 g EN 61000 2 27 a 500 m s2 T 6 ms EN 61000 2 30 EN 60529 front panel IP65 back side IP20 6 back to Table of contents InteliLite Global Guide 146 ...

Страница 147: ...InteliLite Global Guide 147 8 Appendix 8 1 Controller objects 148 8 2 Alarms 559 8 3 Modules 601 6 back to Table of contents ...

Страница 148: ...InteliLite Global Guide 148 8 1 Controller objects 8 1 1 Setpoints 149 8 1 2 Values 404 8 1 3 Logical binary inputs 448 8 1 4 Logical binary outputs 462 8 1 5 Logical analog inputs 514 8 1 6 PLC 546 ...

Страница 149: ...an be assigned to the setpoints during the configuration procedure See the chapter Password page 66 in Operator guide for instructions on how to enter and modify a password List of setpoint groups Group Basic settings 155 Group Engine settings 164 Group Generator settings 194 Group General Analog Inputs 202 Group Scheduler 262 Group Geo Fencing 283 Group Plug In Modules 287 Group Sensors Spec 288 ...

Страница 150: ... Delay 178 Coolant Temperature Wrn 179 Coolant Temperature Sd 179 Coolant Temperature Delay 179 ECU Coolant Temperature Wrn 180 ECU Coolant Temperature Sd 180 ECU Coolant Temperature Delay 180 Temperature Switch On 181 Temperature Switch Off 182 Coolant Temperature Low Wrn 182 Coolant Temperature Low Delay 183 Fuel Level Wrn 183 Fuel Level Sd 183 Fuel Level Delay 184 ECU Fuel Level Wrn 184 ECU Fue...

Страница 151: ...Switch 9 On 228 Analog Switch 9 Off 229 Analog Protection 10 Wrn 229 Analog Protection 10 Sd 230 Analog Protection 10 Delay 230 Analog Switch 10 On 231 Analog Switch 10 Off 232 Analog Protection 11 Wrn 232 Analog Protection 11 Sd 233 Analog Protection 11 Delay 233 Analog Switch 11 On 234 Analog Switch 11 Off 235 Analog Protection 12 Wrn 235 Analog Protection 12 Sd 236 Analog Protection 12 Delay 23...

Страница 152: ...Alternate Config Connection Type 1 290 Nominal Current 1 291 Nominal Frequency 1 291 Nominal RPM 1 291 Nominal Voltage Ph N 1 292 Nominal Voltage Ph Ph 1 292 Connection type 2 293 Nominal Current 2 293 Nominal Frequency 2 293 Nominal RPM 2 294 Nominal Voltage Ph N 2 294 Nominal Voltage Ph Ph 2 294 Connection type 3 295 Nominal Current 3 295 Nominal Frequency 3 295 Nominal RPM 3 296 Nominal Voltage...

Страница 153: ...7 AirGate Address 337 ComAp TCP Port 338 Extension Modules Earth Fault Current Protection 338 Earth Fault Delay 339 Earth Fault CT Input Range 339 Earth Fault CT Ratio 339 Earth Fault Sd 340 PLC PLC Setpoint 1 340 PLC Setpoint 2 341 PLC Setpoint 3 342 PLC Setpoint 4 343 PLC Setpoint 5 344 PLC Setpoint 6 345 PLC Setpoint 7 346 PLC Setpoint 8 347 PLC Setpoint 9 348 PLC Setpoint 10 349 PLC Setpoint 1...

Страница 154: ...obal Guide 154 PLC Setpoint 55 394 PLC Setpoint 56 395 PLC Setpoint 57 396 PLC Setpoint 58 397 PLC Setpoint 59 398 PLC Setpoint 60 399 PLC Setpoint 61 400 PLC Setpoint 62 401 PLC Setpoint 63 402 PLC Setpoint 64 403 ...

Страница 155: ...n menu Gen Set Name 6 back to List of setpoints Subgroup Power settings Setpoint group Basic settings Related FW 1 2 1 Range units 1 5 000 kW Default value 200 kW Alternative config Yes Step 1 kW Comm object 9977 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type page 157 Description Nominal power of the gen set for detected split pha...

Страница 156: ...h Leg D or 3Ph4Wire Nominal Power 6 back to List of setpoints Subgroup Current settings Setpoint group Basic settings Related FW 1 2 1 Range units 1 10 000 A Default value 350 A Alternative config YES Step 1 A Comm object 8275 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type page 157 Description It is current limit for generator IDM...

Страница 157: ...o Phase SplitPhase 3Ph3Wire High Leg D 3Ph4Wire Autodetect Default value 3Ph4Wire Alternative config YES Step Comm object 11628 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Mono Phase Single phase voltage measurement L1 N 1x CT Current Transformer Split Phase Double Delta connection Split Phase Two phase voltage measurement L1 L2 with 180 phase shift 2x...

Страница 158: ...k this setpoint against editing you also have to lock setpoint Connection Type 1 page 290 and Connection type 2 page 293 6 back to List of setpoints Setpoint group Basic settings Related FW 1 2 1 Range units 80 20 000 V Default value 231 V Alternative config YES Step 1 V Comm object 8277 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection t...

Страница 159: ...nits 0 1 500 0 V V Default value 1 0 V V Alternative config NO Step 0 1 V V Comm object 9579 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Generator voltage potential transformers ratio If no PTs are used adjust the setpoint to 1 PT Ratio 6 back to List of setpoints Subgroup Frequency settings Setpoint group Basic settings Related FW 1 2 1 Range units 45...

Страница 160: ...W terminal should be used to prevent possible overcranking which can occur if at least 25 of nominal generator voltage is not present immediately after exceeding firing speed Gear Teeth 6 back to List of setpoints Setpoint group Basic settings Related FW 1 2 1 Range units 100 4 000 RPM Default value 1 500 RPM Alternative config YES Step 1 RPM Comm object 8253 Related applications AMF MRS Config le...

Страница 161: ...e from LiteEdit2015 Controller mode 6 back to List of setpoints Setpoint group Basic settings Related FW 1 2 1 Range units 1 32 Default value 1 Alternative config NO Step 1 Comm object 24537 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Controller identification number It is possible to set controller address different from the default value 1 so that mo...

Страница 162: ...matically in specific cases when fault reset button is pressed Example Controller is in AUTO mode and there is red inactive unconfirmed alarm and fault reset button is pressed controller will start automatically Reset To Manual 6 back to List of setpoints Setpoint group Basic settings Related FW 1 2 1 Range units Disabled 1 255 min Default value Disabled Alternative config NO Step 1 min Comm objec...

Страница 163: ... Horn timeout has elapsed Horn Timeout 6 back to List of setpoints Setpoint group Basic settings Related FW 1 2 1 Range units Disabled 1 360 min Default value Disabled Alternative config NO Step 1 min Comm object 8548 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description The controller is switched to Zero Power Mode when there is no user interaction with the con...

Страница 164: ...up Starting Setpoint group Engine settings Related FW 1 2 1 Range units Diesel Gas Default value Diesel Alternative config NO Step Comm object 9100 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Determines behavior of the Binary output FUEL SOLENOID PAGE 493 Diesel Output closes before binary output STARTER PAGE 510 Lead of output is adjusted via setpoint...

Страница 165: ...dvanced Setpoint visibility Always Description Maximum time limit of cranking time IMPORTANT There is a protection against broken pinion on starter In case that there are no RPM after 5 seconds of starting cranking is interrupted and cranking fail pause follows Maximum Cranking Time 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 5 60 s Default value 8 s Alt...

Страница 166: ...ant to leave the output PRESTART PAGE 506 open Image 8 1 Prestart Time Prestart Time 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 5 50 Default value 25 Alternative config NO Step 1 of Nominal RPM page 160 Comm object 8254 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint defines the firing speed level ...

Страница 167: ... disable starting oil pressure condition IMPORTANT Value from analog input has higher priority than value from ECU Starting Oil Pressure 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units Enabled ChargeFail Disabled Default value Disabled Alternative config NO Step Comm object 9683 Related applications AMF MRS Config level Standard Setpoint visibility Always De...

Страница 168: ...1 Range units 0 Prestart Time page 166 s Default value 0 s Alternative config NO Step 1 s Comm object 14412 Related applications AMF MRS Config level Standard Setpoint visibility Always Description This setpoint defines the time before starting when logical binary output GLOW PLUGS PAGE 500 will be close Glow Plugs Time 6 back to List of setpoints ...

Страница 169: ...RT PAGE 506 goes to logical zero when Fuel Solenoid Lead goes to logical one Fuel Solenoid Lead 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 600 s Default value 12 s Alternative config NO Step 1 s Comm object 9097 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Idle Time delay starts when RPM exceeds Starting RP...

Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...

Страница 171: ...Related applications AMF MRS Config level Standard Setpoint visibility Always Description When the gen set has been started and the idle timer has elapsed the controller will wait for a period adjusted by this setpoint before closing GCB even if the generator voltage and frequency are already in limits Image 8 7 Minimal Stabilization Time Minimal Stabilization Time 6 back to List of setpoints ...

Страница 172: ...rwise an appropriate shutdown alarm generator voltage and or frequency is issued Image 8 8 Maximal Stabilization Time Maximal Stabilization Time 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 0 300 0 s Default value 5 0 s Alternative config YES Step 0 1 s Comm object 10023 Related applications AMF MRS Config level Advanced Setpoint visibility Always Descr...

Страница 173: ... group Engine settings Related FW 1 2 1 Range units Idle Nominal Default value Nominal Alternative config NO Step Comm object 10046 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Selects the function of the binary output IDLE NOMINAL PAGE 503 during engine cooling state Idle Cooling is executed at Idle speed and generator protections are switched off Nomi...

Страница 174: ...stop Cooling Time 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 600 s Default value 60 s Alternative config NO Step 1 s Comm object 9815 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Under normal conditions the engine must certainly stop within this period after the FUEL SOLENOID PAGE 493 has been de energized ...

Страница 175: ...mp Binary output Cooling pump is closed when the engine starts and opens AfterCool time delayed after gen set stops After Cooling Time 6 back to List of setpoints Subgroup Engine Protections Setpoint group Engine settings Related FW 1 2 1 Range units 50 150 Default value 115 Alternative config NO Step 1 of Nominal RPM page 160 Comm object 8263 Related applications AMF MRS Config level Standard Set...

Страница 176: ... Note This function is available only for GAS engines Fuel Solenoid page 164 GAS Also Gear Teeth page 160 has to be set to FGen RPM Overspeed Overshot 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 255 s Default value 5 s Alternative config NO Step 1 s Comm object 14108 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by ...

Страница 177: ...r curve Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 12779 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical analog input OIL PRESSURE PAGE 546 is configured Description Shutdown threshold level for OIL PRESSURE PAGE 546 Oil Pressure Sd 6 back to List of s...

Страница 178: ... the range is defined by ECU sensor curve Default value the value is defined by ECU sensor curve Alternative config NO Step the step is defined by ECU sensor curve Comm object 14425 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if ECU is configured Description Shutdown threshold level for Oil pressure which is send from ECU ECU Oil Pressure Sd 6 back to List o...

Страница 179: ... Default value the value is defined by analog sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 12780 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical analog input COOLANT TEMP PAGE 543 is configured Description Shutdown or BOC threshold level for COOLANT TEMP PAGE 543 Coolant Temperature Sd 6 back to Li...

Страница 180: ...is defined by ECU sensor curve Default value the value is defined by ECU sensor curve Alternative config NO Step the step is defined by ECU sensor curve Comm object 14428 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if ECU is configured Description Shutdown or BOC threshold level for Coolant temperature which is send from ECU ECU Coolant Temperature Sd 6 back...

Страница 181: ...is defined by sensor curve analog or ECU Comm object 8688 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output TEMPERATURE SWITCH PAGE 513 is configured Description Threshold level for switching the binary output TEMPERATURE SWITCH PAGE 513 on Note Value from analog input has higher priority than ECU Image 8 11 Temperature Switch Temperat...

Страница 182: ...ry output TEMPERATURE SWITCH PAGE 513 off Note Value from analog input has higher priority than ECU Image 8 12 Temperature Switch Temperature Switch Off 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternative config YES Step the step is defined by analog...

Страница 183: ... step is defined by analog sensor curve Comm object 12897 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical analog input FUEL LEVEL PAGE 544 is configured Description Warning or history threshold level for FUEL LEVEL PAGE 544 Fuel Level Wrn 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units the range is defined b...

Страница 184: ... sensor curve Alternative config NO Step the step is defined by ECU sensor curve Comm object 14432 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if ECU is configured Description Warning threshold level for Fuel level which is send from ECU ECU Fuel Level Wrn 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units the range is de...

Страница 185: ...ted applications AMF MRS Config level Advanced Setpoint visibility Visible only if the logical analog input FUEL LEVEL PAGE 544 is or ECU is configured Description Define a capacity of gen set fuel tank Fuel Tank Volume 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units Disabled 1 50 h Default value 25 h Alternative config NO Step 1 h Comm object 12373 Related ...

Страница 186: ...ue 20 Alternative config NO Step 1 Comm object 10100 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if the logical binary output FUEL PUMP PAGE 493 is configured and logical binary input FUEL PUMP ON OFF PAGE 454 isn t configured Description Threshold level for switching the binary output FUEL PUMP PAGE 493 on Image 8 13 Fuel Pump On IMPORTANT When binary input...

Страница 187: ...UMP ON OFF PAGE 454 isn t configured Description Threshold level for switching the binary output FUEL PUMP PAGE 493 off Image 8 14 Fuel Pump Off IMPORTANT When binary input FUEL PUMP ON OFF PAGE 454 is configured then binary output FUEL PUMP PAGE 493 is control by this binary input Setpoints Fuel Pump On page 186 and Fuel Pump Off page 187 are not evaluated Note Value from analog input has higher ...

Страница 188: ...but this alarm becomes immediately inactive and it will be possible to delete this message by the Fault reset button If the fault is deleted the controller will initiate the transfer again Transfer Wrn Delay 6 back to List of setpoints Subgroup Maintenance Setpoint group Engine settings Related FW 1 2 1 Range units 0 9 999 h Disabled Default value 1 000 h Alternative config NO Step 1 h Comm object...

Страница 189: ...Default value 1 000 h Alternative config NO Step 1 h Comm object 10530 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Maintenance timer 3 counts down when engine is running If reaches zero an alarm appears When the value 10000 is set than the Maintenance function is disabled and counter does not count Counter value disappear from controllers statistics Ma...

Страница 190: ...lternative config NO Step 0 1 V Comm object 9587 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Warning threshold for high battery voltage Battery Voltage 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 600 s Default value 5 s Alternative config NO Step 1 s Comm object 8383 Related applications AMF MRS Config leve...

Страница 191: ...F MRS Config level Advanced Setpoint visibility Visible only if the logical binary output POWER SWITCH PAGE 506 is configured Description Threshold level for switching the binary output POWER SWITCH PAGE 506 on Image 8 15 Power Switch Level On Level Off Image 8 16 Power Switch Level On Level Off 6 back to List of setpoints ...

Страница 192: ...659 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if the logical binary output POWER SWITCH PAGE 506 is configured Description Threshold level for switching the binary output POWER SWITCH PAGE 506 on Image 8 17 Power Switch Level On Level Off Image 8 18 Power Switch Level On Level Off Power Switch Off 6 back to List of setpoints ...

Страница 193: ...proprietary frame Note To lock this setpoint against editing you also have to lock setpoint ECU Frequency Select 1 page 297 and ECU Frequency Select 2 page 298 ECU Frequency Select 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 100 Default value 50 Alternative config NO Step 1 Comm object 9948 Related applications AMF MRS Config level Advanced Setpoint vi...

Страница 194: ...ck to List of setpoints Setpoint group Generator settings Related FW 1 2 1 Range units 0 200 Default value 120 Alternative config NO Step 1 of Nominal Power page 156 Comm object 9685 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold level for generator overload in of Nominal power protection This is only warning Overload Wrn 6 back to List of setpo...

Страница 195: ...rs when generator current reaches this preset threshold Note When there is no control of breakers the type of protection is Sd not BOC Short Circuit BOC 6 back to List of setpoints Setpoint group Generator settings Related FW 1 2 1 Range units 0 00 10 00 s Default value 0 04 s Alternative config YES Step 0 01 s Comm object 9991 Related applications AMF MRS Config level Advanced Setpoint visibility...

Страница 196: ...n time is not constant but depends on generator over current level according to the following formula Reaction time Overcurrent IDMT Delay Nominal Current I Nominal Current gen Note Reaction time is limited to 3600 s 60 minutes IDMT protection is not active for Reaction time values longer than 60 minutes Igen is maximal value of all measured phases of generator current Table 8 1 EXAMPLE of Reactio...

Страница 197: ...symmetry unbalance Protection is BOC Breaker Open and genset Cooldown Note When there is no control of breakers the type of protection is Sd not BOC Current Unbalance BOC 6 back to List of setpoints Setpoint group Generator settings Related FW 1 2 1 Range units 0 0 600 0 s Default value 5 0 s Alternative config NO Step 0 1 s Comm object 8285 Related applications AMF MRS Config level Advanced Setpo...

Страница 198: ...ed according to Ph N nominal voltage Nominal Voltage Ph N page 158 Generator Voltage Sd 6 back to List of setpoints Setpoint group Generator settings Related FW 1 2 1 Range units Generator Voltage Wrn page 199 Generator Voltage Sd page 198 Default value 110 Alternative config NO Step 1 of Nominal Voltage Ph N page 158 or Nominal Voltage Ph Ph page 159 Comm object 9686 Related applications AMF MRS ...

Страница 199: ...N page 158 Note When there is no control of breakers the type of protection is Sd not BOC Generator Voltage BOC 6 back to List of setpoints Setpoint group Generator settings Related FW 1 2 1 Range units Generator Voltage BOC page 199 Generator Voltage Wrn page 198 Default value 70 Alternative config NO Step 1 of Nominal Voltage Ph N page 158 or Nominal Voltage Ph Ph page 159 Comm object 9687 Relat...

Страница 200: ...0 Alternative config NO Step 1 of Nominal Voltage Ph Ph page 159 Comm object 8288 Related applications AMF MRS Config level Advanced Setpoint visibility Conditioned by the setpoint Connection type page 157 Description Threshold for generator voltage unbalance alarm Note When there is no control of breakers the type of protection is Sd not BOC Voltage Unbalance BOC 6 back to List of setpoints Setpo...

Страница 201: ...uency Wrn page 202 Generator Frequency BOC page 201 Default value 110 0 Alternative config NO Step 0 1 of Nominal Frequency page 159 Comm object 9688 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold for generator phase L1 overfrequency Generator Frequency Wrn 6 back to List of setpoints Setpoint group Generator settings Related FW 1 2 1 Range unit...

Страница 202: ... 1 s Comm object 8297 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for Generator Frequency BOC page 201 and Generator Frequency BOC page 201 protection Generator Frequency BOC Delay 6 back to List of setpoints Group General Analog Inputs General Analog Input 1 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined b...

Страница 203: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 01 PAGE 516 Analog Protection 1 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9261 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 204: ...efined by analog sensor curve Comm object 11407 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 1 PAGE 476 is configured Description Threshold level for switching the binary output ANALOG SWITCH 1 PAGE 476 on The value is measured from AIN SWITCH 01 PAGE 536 analog input Image 8 20 General analog input 1 switch Analog S...

Страница 205: ... the binary output ANALOG SWITCH 1 PAGE 476 off The value is measured from AIN SWITCH 01 PAGE 536 analog input Image 8 21 General analog input 1 switch Analog Switch 1 Off 6 back to List of setpoints General Analog Input 2 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternati...

Страница 206: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 02 PAGE 517 Analog Protection 2 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9264 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 207: ...defined by analog sensor curve Comm object 11408 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 2 PAGE 477 is configured Description Threshold level for switching the binary output AIN SWITCH 02 PAGE 536 on The value is measured from AIN SWITCH 02 PAGE 536 analog input Image 8 22 General analog input 2 switch Analog Sw...

Страница 208: ...g the binary output AIN SWITCH 02 PAGE 536 off The value is measured from AIN SWITCH 02 PAGE 536 analog input Image 8 23 General analog input 2 switch Analog Switch 2 Off 6 back to List of setpoints General Analog Input 3 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 209: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 03 PAGE 518 Analog Protection 3 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9267 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 210: ...defined by analog sensor curve Comm object 11409 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 3 PAGE 477 is configured Description Threshold level for switching the binary output AIN SWITCH 03 PAGE 536 on The value is measured from AIN SWITCH 03 PAGE 536 analog input Image 8 24 General analog input 3 switch Analog Sw...

Страница 211: ...g the binary output AIN SWITCH 03 PAGE 536 off The value is measured from AIN SWITCH 03 PAGE 536 analog input Image 8 25 General analog input 3 switch Analog Switch 3 Off 6 back to List of setpoints General Analog Input 4 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 212: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 04 PAGE 519 Analog Protection 4 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9270 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 213: ...defined by analog sensor curve Comm object 14385 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 04 PAGE 537 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 26 General analog input 4 switch Analog Sw...

Страница 214: ...g the binary output AIN SWITCH 04 PAGE 537 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 27 General analog input 4 switch Analog Switch 4 Off 6 back to List of setpoints General Analog Input 5 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 215: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 05 PAGE 520 Analog Protection 5 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9273 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 216: ...defined by analog sensor curve Comm object 14963 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 05 PAGE 537 on The value is measured from AIN SWITCH 05 PAGE 537 analog input Image 8 28 General analog input 4 switch Analog Sw...

Страница 217: ...g the binary output AIN SWITCH 05 PAGE 537 off The value is measured from AIN SWITCH 05 PAGE 537 analog input Image 8 29 General analog input 4 switch Analog Switch 5 Off 6 back to List of setpoints General Analog Input 6 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 218: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 06 PAGE 521 Analog Protection 6 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9276 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 219: ...defined by analog sensor curve Comm object 14964 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 06 PAGE 537 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 30 General analog input 4 switch Analog Sw...

Страница 220: ...g the binary output AIN SWITCH 06 PAGE 537 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 31 General analog input 4 switch Analog Switch 6 Off 6 back to List of setpoints General Analog Input 7 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 221: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 07 PAGE 522 Analog Protection 7 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9279 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 222: ...defined by analog sensor curve Comm object 14965 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 07 PAGE 538 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 32 General analog input 4 switch Analog Sw...

Страница 223: ...g the binary output AIN SWITCH 07 PAGE 538 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 33 General analog input 4 switch Analog Switch 7 Off 6 back to List of setpoints General Analog Input 8 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 224: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 08 PAGE 523 Analog Protection 8 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9282 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 225: ...defined by analog sensor curve Comm object 14966 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 08 PAGE 538 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 34 General analog input 4 switch Analog Sw...

Страница 226: ...g the binary output AIN SWITCH 08 PAGE 538 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 35 General analog input 4 switch Analog Switch 8 Off 6 back to List of setpoints General Analog Input 9 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 227: ...ations AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 09 PAGE 524 Analog Protection 9 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9285 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 228: ...defined by analog sensor curve Comm object 14967 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 09 PAGE 538 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 36 General analog input 4 switch Analog Sw...

Страница 229: ... the binary output AIN SWITCH 09 PAGE 538 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 37 General analog input 4 switch Analog Switch 9 Off 6 back to List of setpoints General Analog Input 10 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 230: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 10 PAGE 525 Analog Protection 10 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9288 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 231: ...efined by analog sensor curve Comm object 14968 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 10 PAGE 539 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 38 General analog input 4 switch Analog Swi...

Страница 232: ...the binary output AIN SWITCH 10 PAGE 539 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 39 General analog input 4 switch Analog Switch 10 Off 6 back to List of setpoints General Analog Input 11 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 233: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 11 PAGE 526 Analog Protection 11 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9291 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 234: ...efined by analog sensor curve Comm object 14969 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 11 PAGE 539 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 40 General analog input 4 switch Analog Swi...

Страница 235: ...the binary output AIN SWITCH 11 PAGE 539 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 41 General analog input 4 switch Analog Switch 11 Off 6 back to List of setpoints General Analog Input 12 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 236: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 12 PAGE 527 Analog Protection 12 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9294 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 237: ...efined by analog sensor curve Comm object 14970 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 12 PAGE 539 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 42 General analog input 4 switch Analog Swi...

Страница 238: ...the binary output AIN SWITCH 12 PAGE 539 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 43 General analog input 4 switch Analog Switch 12 Off 6 back to List of setpoints General Analog Input 13 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 239: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 13 PAGE 528 Analog Protection 13 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9297 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 240: ...efined by analog sensor curve Comm object 14971 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 13 PAGE 540 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 44 General analog input 4 switch Analog Swi...

Страница 241: ...the binary output AIN SWITCH 13 PAGE 540 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 45 General analog input 4 switch Analog Switch 13 Off 6 back to List of setpoints General Analog Input 14 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 242: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 14 PAGE 529 Analog Protection 14 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9300 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 243: ...efined by analog sensor curve Comm object 14972 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 14 PAGE 540 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 46 General analog input 4 switch Analog Swi...

Страница 244: ...the binary output AIN SWITCH 14 PAGE 540 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 47 General analog input 4 switch Analog Switch 14 Off 6 back to List of setpoints General Analog Input 15 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 245: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 15 PAGE 530 Analog Protection 15 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9303 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 246: ...efined by analog sensor curve Comm object 14973 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 15 PAGE 540 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 48 General analog input 4 switch Analog Swi...

Страница 247: ...the binary output AIN SWITCH 15 PAGE 540 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 49 General analog input 4 switch Analog Switch 15 Off 6 back to List of setpoints General Analog Input 16 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 248: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 16 PAGE 531 Analog Protection 16 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9306 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 249: ...efined by analog sensor curve Comm object 14974 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 16 PAGE 541 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 50 General analog input 4 switch Analog Swi...

Страница 250: ...the binary output AIN SWITCH 16 PAGE 541 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 51 General analog input 4 switch Analog Switch 16 Off 6 back to List of setpoints General Analog Input 17 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 251: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 17 PAGE 532 Analog Protection 17 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9309 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 252: ...efined by analog sensor curve Comm object 14975 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 17 PAGE 541 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 52 General analog input 4 switch Analog Swi...

Страница 253: ...the binary output AIN SWITCH 17 PAGE 541 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 53 General analog input 4 switch Analog Switch 17 Off 6 back to List of setpoints General Analog Input 18 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 254: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 18 PAGE 533 Analog Protection 18 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9312 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 255: ...efined by analog sensor curve Comm object 14976 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 18 PAGE 541 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 54 General analog input 4 switch Analog Swi...

Страница 256: ...the binary output AIN SWITCH 18 PAGE 541 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 55 General analog input 4 switch Analog Switch 18 Off 6 back to List of setpoints General Analog Input 19 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 257: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 19 PAGE 534 Analog Protection 19 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9315 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 258: ...efined by analog sensor curve Comm object 14977 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 19 PAGE 542 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 56 General analog input 4 switch Analog Swi...

Страница 259: ...the binary output AIN SWITCH 19 PAGE 542 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 57 General analog input 4 switch Analog Switch 19 Off 6 back to List of setpoints General Analog Input 20 Setpoint group General Analog Inputs Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value the value is defined by analog sensor curve Alternativ...

Страница 260: ...tions AMF MRS Config level Standard Setpoint visibility Always Description Shutdown or BOC threshold level for AIN PROT 20 PAGE 535 Analog Protection 20 Sd 6 back to List of setpoints Setpoint group General Analog Inputs Related FW 1 2 1 Range units 0 900 s Default value 0 s Alternative config NO Step 1 s Comm object 9318 Related applications AMF MRS Config level Standard Setpoint visibility Alway...

Страница 261: ...efined by analog sensor curve Comm object 14978 Related applications AMF MRS Config level Standard Setpoint visibility Visible only if the logical binary output ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 20 PAGE 542 on The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 58 General analog input 4 switch Analog Swi...

Страница 262: ...put ANALOG SWITCH 4 PAGE 478 is configured Description Threshold level for switching the binary output AIN SWITCH 20 PAGE 542 off The value is measured from AIN SWITCH 04 PAGE 537 analog input Image 8 59 General analog input 4 switch Analog Switch 20 Off 6 back to List of setpoints Group Scheduler Subgroup Time Date Setpoint group Scheduler Related FW 1 2 1 Range units HH MM SS Default value 0 0 0...

Страница 263: ...isibility Always Description Time interval for periodic history records Time Stamp Period 6 back to List of setpoints Setpoint group Scheduler Related FW 1 2 1 Range units Disabled Winter Summer Winter S Summer S Default value Disabled Alternative config NO Step Comm object 8727 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Behavior of switching between ...

Страница 264: ... Timer 1 has higher priority over Timer 2 So if Timer 1 Function page 264 is configured for OFF mode and Timer 2 Function page 271 is over the same time configured for AUTO mode controller will work in OFF mode Controller activates timer whenever it is powered up even in period where timer should be already running Disable The Timer 1 is disabled No Func There is no any other function only binary ...

Страница 265: ...ge 270 Timer 1 Repeat Day In Month page 270 Timer 1 Repeat Week In Month page 271 Timer 1 Refresh Period page 268 Timer 1 Weekends page 269 Timer Setup 6 back to List of setpoints Setpoint group Scheduler Related FW 1 2 1 Range units Off Once Repeated Default value Off Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the...

Страница 266: ...ts HH MM Default value 00 00 Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 1 Function page 264 Description Time of first occurrence of Timer 1 Function page 264 Timer 1 First Occur Time 6 back to List of setpoints Setpoint group Scheduler Related FW 1 2 1 Range units HH MM Default value 00 00 Altern...

Страница 267: ...ned by the setpoint Timer 1 Function page 264 Description Repeated interval of Timer 1 Function page 264 Daily Timer 1 Function page 264 is repeated every day Weekly Timer 1 Function page 264 is repeated every week in chosen days Monthly Timer 1 Function page 264 is repeated in chosen day every month or in chosen days of chosen week of month Short Period Timer 1 Function page 264 is repeated in ad...

Страница 268: ... you set this setpoint to 2 then every second week from first occurrence of Timer 1 Function page 264 the Timer 1 Function page 264 will be activated in selected days adjusted by Timer 1 Day page 269 Monthly Range units 1 12 month This setpoint adjust that every X month the timer will be activated Example If you have monthly repetition and you set this setpoint to 2 then every second month from fi...

Страница 269: ...ge 264 counter isn t running on the weekends and Timer 1 Function page 264 isn t active If the activation of timer is counted on the weekend than timer will be activated after weekend Another activation of timer is counted from original date of first occurrence date Timer 1 Weekends 6 back to List of setpoints Setpoint group Scheduler Related FW 1 2 1 Range units Monday Tuesday Wednesday Thursday ...

Страница 270: ... Monday Tuesday Wednesday Thursday Friday Saturday Sunday Default value All OFF Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 1 Function page 264 Description Use this setpoint to select the day of week when timer will be activated Note More day can be selected Timer will be activated on the day whic...

Страница 271: ...ose out of 5 following Timer functions Binary output EXERCISE TIMER 2 PAGE 492 is always activated when Timer is active regardless of chosen timer function Timer functions require controller running in AUTO mode Timer 1 has higher priority over Timer 2 So if Timer 1 Function page 264 is configured for OFF mode and Timer 2 Function page 271 is over the same time configured for AUTO mode controller ...

Страница 272: ...77 Timer 2 Repeat Day In Month page 277 Timer 2 Repeat Week In Month page 278 Timer 2 Refresh Period page 275 Timer 2 Weekends page 276 Timer Setup 6 back to List of setpoints Setpoint group Scheduler Related FW 1 2 1 Range units Off Once Repeated Default value Off Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the set...

Страница 273: ...nits HH MM Default value 00 00 Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 2 Function page 271 Description Time of first occurrence of Timer 2 Function page 271 Timer 2 Start Time 6 back to List of setpoints Setpoint group Scheduler Related FW 1 2 1 Range units HH MM Default value 00 00 Alternativ...

Страница 274: ...ed by the setpoint Timer 2 Function page 271 Description Repeated interval of Timer 2 Function page 271 Daily Timer 2 Function page 271 is repeated every day Weekly Timer 2 Function page 271 is repeated every week in chosen days Monthly Timer 2 Function page 271 is repeated in chosen day every month or in chosen days of chosen week of month Short Period Timer 2 Function page 271 is repeated in adj...

Страница 275: ... you set this setpoint to 2 then every second week from first occurrence of Timer 2 Function page 271 the Timer 2 Function page 271 will be activated in selected days adjusted by Timer 2 Day page 276 Monthly Range units 1 12 month This setpoint adjust that every X month the timer will be activated Example If you have monthly repetition and you set this setpoint to 2 then every second month from fi...

Страница 276: ...ge 271 counter isn t running on the weekends and Timer 2 Function page 271 isn t active If the activation of timer is counted on the weekend than timer will be activated after weekend Another activation of timer is counted from original date of first occurrence date Timer 2 Weekends 6 back to List of setpoints Setpoint group Scheduler Related FW 1 2 1 Range units Monday Tuesday Wednesday Thursday ...

Страница 277: ... Monday Tuesday Wednesday Thursday Friday Saturday Sunday Default value All OFF Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 2 Function page 271 Description Use this setpoint to select the day of week when timer will be activated Note More day can be selected Timer will be activated on the day whic...

Страница 278: ...AMF MRS Config level Advanced Setpoint visibility Always Description Another engine start is not allowed when this timer elapsed This timer is based on engine running hours The alarm Rental Timer 1 Elapsed page 566 will be recorded in alarm list and the binary output AL RENTAL TIMER 1 PAGE 474 will close IMPORTANT To reset Rental Timer 1 page 278 we have to set up Rental Timer 1 page 278 again It ...

Страница 279: ...un counter will start increment when the engine is continue running after the Rental Timer 1 page 278 elapsed Note There is no priority between Rental Timer 1 and Rental Timer 2 The sooner timer will activated the Rental Timer BOC page 282 protection 6 back to List of setpoints ...

Страница 280: ...1 Range units DD MM YYYY Default value 01 01 2015 Alternative config NO Step 1 day Comm object 14367 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Another engine start is not allowed when this timer elapsed This timer is based on date At the midnight of the last day the alarm Rental Timer 2 Elapsed page 566 will be recorded in alarm list and the binary o...

Страница 281: ...ine will be cooled and stopped when the Rental Timer BOC page 282 time elapsed Image 8 62 Rental Timer 2 The Running Hours Overrun counter will start increment when the engine is continue running after the Rental Timer 2 page 280 elapsed Note There is no priority between Rental Timer 1 and Rental Timer 2 The sooner timer will activated the Rental Timer BOC page 282 protection 6 back to List of set...

Страница 282: ... are adjusted by this setpoint Image 8 63 Rental Timer 2 Wrn Rental Timer 2 Wrn 6 back to List of setpoints Setpoint group Scheduler Related FW 1 2 1 Range units Disabled 1 210 h Default value 24 h Alternative config NO Step 1 h Comm object 14334 Related applications AMF MRS Config level Advanced Setpoint visibility Conditioned by the setpoints Rental Timer 1 page 278 and Rental Timer 2 page 280 D...

Страница 283: ...s setpoint will be adjusted automatically from actual coordinates from GPS signal Home Latitude 6 back to List of setpoints Setpoint group CM 4G GPS Related FW 1 2 1 Range units 180 0000 180 0000 Default value 0 0000 Alternative config NO Step 0 0001 Comm object 14607 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoi...

Страница 284: ...its 0 0 99 9 km Default value 0 0 km Alternative config NO Step 0 1 km Comm object 14608 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Radius for circle area 2 When the gen set leaves this area Fence 2 Protection page 287 is activated after Fence 2 Delay page 285 Note The center of this circle area is defined by Home positio...

Страница 285: ...ed Enabled LBI Enable Default value Disabled Alternative config NO Step Comm object 11681 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint enables or disables geo fencing function Disabled Fence 1 Protection page 286 and Fence 2 Protection page 287 are disabled Enabled Fence 1 Protection page 286 and Fence 2 Prote...

Страница 286: ...d displayed on the LCD screen but not used for protection History record is made if position is out of Fence Radius 1 page 284 Wrn Position of gen set is used for warning protection only Protection is activated when position of the gen set is out of Fence Radius 1 page 284 Sd Position of gen set is used for shutdown protection Protection is activated when position of the gen set is out of Fence Ra...

Страница 287: ... protection only Protection is activated when position of the gen set is out of Fence Radius 2 page 284 Sd Position of gen set is used for shutdown protection Protection is activated when position of the gen set is out of Fence Radius 2 page 284 BOC Position of gen set is used for BOC Breaker Open and Cooling protection Protection is activated when position of the gen set is out of Fence Radius 2 ...

Страница 288: ... Sensors Spec Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value 0 number of decimal is given by sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 8431 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Calibrating constant to adjust the measured value of controller analog inputs...

Страница 289: ...djusted via LiteEdit2015 in configuration of analog input 2 Analog Input 2 Calibration 6 back to List of setpoints Subgroup Analog Input 3 Setpoint group Sensors Spec Related FW 1 2 1 Range units the range is defined by analog sensor curve Default value 0 number of decimal is given by sensor curve Alternative config NO Step the step is defined by analog sensor curve Comm object 8467 Related applic...

Страница 290: ... LiteEdit2015 in configuration of analog input 4 Analog Input 4 Calibration 6 back to List of setpoints Group Alternate Config Subgroup Basic settings Setpoint group Basic settings Related FW 1 2 1 Range units Monophase Splitphase 3Ph3Wire High Leg D 3Ph4Wire Autodetect Default value 3Ph4Wire Alternative config YES Step Comm object 12058 Related applications AMF MRS Config level Standard Setpoint ...

Страница 291: ... applications AMF MRS Config level Standard Setpoint visibility Always Description When logical binary input CONFIGURATION 2 PAGE 450 isn t active then setpoint Nominal Frequency page 159 has the same value as setpoint Nominal Frequency 1 Setpoint Nominal Frequency page 159 can be changed from both places from Basic settings setpoint group and from Alternate Config setpoint group Nominal Frequency...

Страница 292: ...tings setpoint group and from Alternate Config setpoint group Nominal Voltage Ph N 1 6 back to List of setpoints Setpoint group Basic settings Related FW 1 2 1 Range units 80 40 000 V Default value 400 V Alternative config YES Step 1 V Comm object 12055 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection Type 1 page 290 Description When log...

Страница 293: ...nfig level Standard Setpoint visibility Conditioned by the setpoint Connection type 2 page 293 Description When logical binary input CONFIGURATION 2 PAGE 450 is active then setpoint Nominal Current page 156 has the same value as setpoint Nominal Current 2 Setpoint Nominal Current page 156 can be changed from both places from Basic settings setpoint group and from Alternate Config setpoint group No...

Страница 294: ...nection type 2 page 293 Description When logical binary input CONFIGURATION 2 PAGE 450 is active then setpoint Nominal Voltage Ph N page 158 has the same value as setpoint Nominal Voltage Ph N 2 Setpoint Nominal Voltage Ph N page 158 can be changed from both places from Basic settings setpoint group and from Alternate Config setpoint group Nominal Voltage Ph N 2 6 back to List of setpoints Setpoin...

Страница 295: ...nfig level Standard Setpoint visibility Conditioned by the setpoint Connection type 2 page 293 Description When logical binary input CONFIGURATION 3 PAGE 450 is active then setpoint Nominal Current page 156 has the same value as setpoint Nominal Current 3 Setpoint Nominal Current page 156 can be changed from both places from Basic settings setpoint group and from Alternate Config setpoint group No...

Страница 296: ...nection type 2 page 293 Description When logical binary input CONFIGURATION 3 PAGE 450 is active then setpoint Nominal Voltage Ph N page 158 has the same value as setpoint Nominal Voltage Ph N 3 Setpoint Nominal Voltage Ph N page 158 can be changed from both places from Basic settings setpoint group and from Alternate Config setpoint group Nominal Voltage Ph N 3 6 back to List of setpoints Setpoin...

Страница 297: ...both places from Basic settings setpoint group and from Alternate Config setpoint group ECU Frequency Select 1 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 100 Default value 50 Alternative config NO Step 1 Comm object 14337 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if ECU is configured Description When logical b...

Страница 298: ...from Basic settings setpoint group and from Alternate Config setpoint group ECU Frequency Select 2 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 100 Default value 50 Alternative config NO Step 1 Comm object 14338 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if ECU is configured Description When logical binary input ...

Страница 299: ... from Basic settings setpoint group and from Alternate Config setpoint group ECU Frequency Select 3 6 back to List of setpoints Setpoint group Engine settings Related FW 1 2 1 Range units 0 100 Default value 50 Alternative config NO Step 1 Comm object 15199 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if ECU is configured Description When logical binary input...

Страница 300: ...ODBUS protocol COM1 Mode 6 back to List of setpoints Setpoint group CM RS232 485 Related FW 1 2 1 Range units 9600 19200 38400 57600 115200 bps Default value 57600 bps Alternative config NO Step Comm object 24341 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint COM1 Mode page 300 Description If the direct mode i...

Страница 301: ...d applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Communication protocol switch for the COM2 channel Direct LiteEdit2015 communication protocol via serial cable MODBUS MODBUS protocol COM2 Mode 6 back to List of setpoints Setpoint group CM RS232 485 Related FW 1 2 1 Range units 9600 19200 38400 57600 115200 bps Default value 57600 bps...

Страница 302: ...oint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units Email SMS SMS Only Default value Email SMS Alternative config NO Step Comm object 24315 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint adjust the communication mode of module Email SMS Controller is connected to the Internet and is able to send e mails as...

Страница 303: ...ations AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Mode page 314 Description User name for the GPRS 4G Access Point if authentication is required But mostly it is not required and should be left blank APN User Name 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units 0 15 characters Default ...

Страница 304: ... This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 1 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units 0 63 characters Default value Alternative config NO Step Comm object 24297 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint ...

Страница 305: ... This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 3 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units 0 63 characters Default value Alternative config NO Step Comm object 24144 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint ...

Страница 306: ... selection page 71 more information This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email SMS Language 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units 0 31 characters Default value Alternative config NO Step Comm object 24313 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed co...

Страница 307: ... NO Step Comm object 24311 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Mode page 314 Description This setpoint is used for entering the domain name e g smtp yourprovider com or IP address e g 74 125 39 109 or number of port with colon like a first mark of the SMTP server Ask your internet provider or IT man...

Страница 308: ...Address 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units GMT 12 00 GMT 13 00 hours Default value GMT 1 00 hour Alternative config NO Step Comm object 24366 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint is used to select the time zone where the controller is l...

Страница 309: ...ue ON Alternative config NO Step Comm object 8482 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint enables or disables Wrn Messages This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Wrn Message 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units...

Страница 310: ...nt group CM GPRS CM 4G GPS Related FW 1 2 1 Range units 0 31 characters Default value Alternative config NO Step Comm object 24296 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent For GSM numbers use either the national format i e the ...

Страница 311: ... prefix IMPORTANT Telephone number has to be entered without spaces Telephone Number 2 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units 0 31 characters Default value Alternative config NO Step Comm object 24143 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this setpoint eithe...

Страница 312: ...e full international format beginning with a character followed by the country prefix IMPORTANT Telephone number has to be entered without spaces Telephone Number 4 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units Valid IP address Default value Alternative config NO Step Comm object 24314 Related applications AMF MRS Config level Standard Setpoint visibilit...

Страница 313: ...rver address is adjusted by the setpoint AirGate Address page 337 IMPORTANT When this setpoint is changed the controller has to be restarted to apply changes AirGate Connection 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units Default value airgate comap cz Alternative config NO Step Comm object 24364 Related applications AMF MRS Config level Sta...

Страница 314: ...ns IMPORTANT If AirGate is used this setpoint has to be adjusted to 23 Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules ComAp TCP Port 6 back to List of setpoints Group CM 4G GPS Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units Email SMS SMS Only Default value Email SMS Alternative config NO Step Comm object 24315 Related applications AMF MRS Config level Sta...

Страница 315: ...ations AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Mode page 314 Description User name for the GPRS 4G Access Point if authentication is required But mostly it is not required and should be left blank APN User Name 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units 0 15 characters Default ...

Страница 316: ... This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 1 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units 0 63 characters Default value Alternative config NO Step Comm object 24297 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint ...

Страница 317: ... This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 3 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units 0 63 characters Default value Alternative config NO Step Comm object 24144 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint ...

Страница 318: ... selection page 71 more information This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email SMS Language 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units 0 31 characters Default value Alternative config NO Step Comm object 24313 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed co...

Страница 319: ... NO Step Comm object 24311 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Mode page 314 Description This setpoint is used for entering the domain name e g smtp yourprovider com or IP address e g 74 125 39 109 or number of port with colon like a first mark of the SMTP server Ask your internet provider or IT man...

Страница 320: ...Address 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units GMT 12 00 GMT 13 00 hours Default value GMT 1 00 hour Alternative config NO Step Comm object 24366 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint is used to select the time zone where the controller is l...

Страница 321: ...ue ON Alternative config NO Step Comm object 8482 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint enables or disables Wrn Messages This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Wrn Message 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units...

Страница 322: ...nt group CM GPRS CM 4G GPS Related FW 1 2 1 Range units 0 31 characters Default value Alternative config NO Step Comm object 24296 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent For GSM numbers use either the national format i e the ...

Страница 323: ... prefix IMPORTANT Telephone number has to be entered without spaces Telephone Number 2 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units 0 31 characters Default value Alternative config NO Step Comm object 24143 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this setpoint eithe...

Страница 324: ...ut spaces Telephone Number 4 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS Related FW 1 2 1 Range units DISABLED ENABLED Default value ENABLED Alternative config NO Step Comm object 24273 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Mode page 314 Description This setpoint enable or disable Air...

Страница 325: ...Ethernet Related FW 1 2 1 Range units 0 65 535 Default value 23 Alternative config NO Step Comm object 24374 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Mode page 314 CM GPRS module Description This setpoint is used to adjust the port number which is used for Ethernet connection to a PC with any of ComAp PC...

Страница 326: ...send Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 1 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units 0 63 characters Default value Alternative config NO Step Comm object 24297 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the ...

Страница 327: ... This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Email Address 3 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units 0 63 characters Default value Alternative config NO Step Comm object 24144 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint ...

Страница 328: ...GPS CM Ethernet Related FW 1 2 1 Range units GMT 12 00 GMT 13 00 hours Default value GMT 1 00 hour Alternative config NO Step Comm object 24366 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint is used to select the time zone where the controller is located See your computer time zone setting click on the time indi...

Страница 329: ...ue ON Alternative config NO Step Comm object 8482 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint enables or disables Wrn Messages This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules Wrn Message 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units...

Страница 330: ...Step Comm object 24370 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Use this setpoint to enter the username for the SMTP server Leave the setpoint blank if the SMTP server does not require authentication SMTP User Name 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 2 1 Range units 0 15 characters Defaul...

Страница 331: ...e SMTP server at airgate comap cz may be used Ports 25 and 9925 are supported After controller connects to AirGate for the first time or with new public IP address it may not be able to send emails for first 5 10 minutes SMTP Server Address 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 2 1 Range units 0 31 characters Default value Alternative config NO Step Comm object 24367 ...

Страница 332: ...ed settings are visible in the values and the setpoints do not take place Use this option if you connect to the device only via AirGate or if you assure obtaining a static IP address at the DHCP side IP Address Mode 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 2 1 Range units Valid IP address Default value 192 168 1 254 Alternative config NO Step Comm object 24376 Related ap...

Страница 333: ... DHCP server Subnet Mask 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 2 1 Range units Valid IP address Default value 192 168 1 1 Alternative config NO Step Comm object 24373 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint IP Address Mode page 332 Description The setpoint is used to select...

Страница 334: ... is inactive The DNS server IP address is assigned by the DHCP server DNS IP Address 1 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 2 1 Range units Valid IP address Default value 8 8 8 8 Alternative config NO Step Comm object 24331 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description The setpoint is used to s...

Страница 335: ...ABLED Default value DISABLED Alternative config NO Step Comm object 24336 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enable or disable SNMP v1 Agent SNMP Agent 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 2 1 Range units 0 31 characters Default value public Alternative config NO Step Comm object 243...

Страница 336: ...LED Alternative config NO Step Comm object 24294 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description IP address 1 for receiving SNMP Traps Leave this setpoint blank if SNMP traps should not be send SNMP Traps IP Address 1 6 back to List of setpoints Setpoint group CM Ethernet Related FW 1 2 1 Range units Valid IP address Default v...

Страница 337: ...ct to it from the internet ENABLED This mode enables the AirGate service The AirGate server address is adjusted by the setpoint AirGate Address page 337 Also the standard TCP IP is enabled AirGate Connection 6 back to List of setpoints Setpoint group CM GPRS CM 4G GPS CM Ethernet Related FW 1 2 1 Range units Default value airgate comap cz Alternative config NO Step Comm object 24364 Related applic...

Страница 338: ...overcome a firewall restrictions IMPORTANT If AirGate is used this setpoint has to be adjusted to 23 Note This setpoint is common for CM Ethernet CM GPRS and CM 4G GPS modules ComAp TCP Port 6 back to List of setpoints Group EM BIO8 EFCP Setpoint group EM BIO8 EFCP Related FW 1 2 1 Range units DISABLED ENABLED Default value ENABLED Alternative config NO Step Comm object 11631 Related applications ...

Страница 339: ...oint visibility Only if relevant module is installed Description There are 2 physical inputs for Earth Fault Current Protection page 338 Value of this setpoint has to be set on value of physical input which is presently in use Earth Fault CT Input Range 6 back to List of setpoints Setpoint group EM BIO8 EFCP Related FW 1 2 1 Range units 1 2000 1 1or5 A Default value 500 1 1or5 A Alternative config...

Страница 340: ...ed applications AMF MRS Config level Standard Setpoint visibility Only if relevant setpoint is used in PLC Description Adjustable value for input in PLC logic Configuration of setpoint Configuration is made via configuration PC tool LiteEdit2015 Image 8 64 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint R...

Страница 341: ...int Configuration is made via configuration PC tool LiteEdit2015 Image 8 65 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 342: ...int Configuration is made via configuration PC tool LiteEdit2015 Image 8 66 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 343: ...int Configuration is made via configuration PC tool LiteEdit2015 Image 8 67 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 344: ...int Configuration is made via configuration PC tool LiteEdit2015 Image 8 68 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 345: ...int Configuration is made via configuration PC tool LiteEdit2015 Image 8 69 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 346: ...int Configuration is made via configuration PC tool LiteEdit2015 Image 8 70 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 347: ...int Configuration is made via configuration PC tool LiteEdit2015 Image 8 71 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 348: ...int Configuration is made via configuration PC tool LiteEdit2015 Image 8 72 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 349: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 73 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 350: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 74 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 351: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 75 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 352: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 76 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 353: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 77 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 354: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 78 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 355: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 79 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 356: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 80 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 357: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 81 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 358: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 82 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 359: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 83 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 360: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 84 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 361: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 85 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 362: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 86 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 363: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 87 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 364: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 88 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 365: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 89 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 366: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 90 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 367: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 91 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 368: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 92 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 369: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 93 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 370: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 94 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 371: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 95 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 372: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 96 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 373: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 97 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 374: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 98 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 375: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 99 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value ca...

Страница 376: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 100 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 377: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 101 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 378: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 102 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 379: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 103 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 380: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 104 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 381: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 105 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 382: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 106 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 383: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 107 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 384: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 108 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 385: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 109 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 386: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 110 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 387: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 111 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 388: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 112 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 389: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 113 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 390: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 114 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 391: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 115 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 392: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 116 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 393: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 117 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 394: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 118 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 395: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 119 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 396: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 120 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 397: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 121 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 398: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 122 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 399: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 123 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 400: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 124 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 401: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 125 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 402: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 126 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 403: ...nt Configuration is made via configuration PC tool LiteEdit2015 Image 8 127 Screen of configuration from LiteEdit2015 PLC Setpoint name Name of the setpoint 0 32 characters Dimension Dimension of value of the setpoint Resolution Resolution of the value of the setpoint Resolution adjust number of decimal places in low and high limit Low limit The lowest value of setpoint Digit place of this value c...

Страница 404: ...ed on an analog input The configured ECU or extension module does not provide the particular value The communication with the ECU or extension module is interrupted A value containing the invalid flag is displayed as in LiteEdit2015 and on the controller screen If such a value is read out via MODBUS it will contain the data 32768 in the case of signed values and 65535 in the case of unsigned value...

Страница 405: ...6 Load kVAr L1 417 Load kVAr L2 417 Load kVAr L3 417 Load kW 417 Load kW L1 418 Load kW L2 418 Load kW L3 418 Load Power Factor 418 Load Power Factor L1 419 Load Power Factor L2 419 Load Power Factor L3 419 Controler I O Analog Input 1 419 Analog Input 2 419 Analog Input 3 420 Analog Input 4 420 BatteryVoltage 420 Binary Inputs 420 Binary Outputs 420 D 421 Statistics Genset kWArh 421 Genset kWh 42...

Страница 406: ...ID 435 AirGate Status 436 Connection Type 436 Cell Diag Code 436 Cell ErrorRate 438 Cell Signal Lev 438 Cell Status 438 Last Email Result 439 Operator 440 CM 4G GPS GPS part Altitude 434 HomePosDist 434 Latitude 434 Longitude 435 Satellites 435 CM Ethernet AirGate Status 440 AirGate ID 440 Current DNS 441 ETH Interface Status 441 Current Gateway 441 Current IP Address 441 Last Email Result 442 MAC...

Страница 407: ...lues Value group Engine Related FW 1 2 1 Units Comm object 12484 Related applications AMF MRS Description The rate of soot in DPF Diesel particulate filter DPF Soot Load 6 back to List of values Value group Engine Related FW 1 2 1 Units Depends on ECU value Comm object 10153 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type ...

Страница 408: ...ke temperature C oil pressure bar boost pressure bar load oil temperature C etc ECU BIN 3 6 back to List of values Value group Engine Related FW 1 2 1 Units Depends on ECU value Comm object 10156 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h coolant temperature...

Страница 409: ...ke temperature C oil pressure bar boost pressure bar load oil temperature C etc ECU BIN 7 6 back to List of values Value group Engine Related FW 1 2 1 Units Depends on ECU value Comm object 10160 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h coolant temperature...

Страница 410: ...ted FW 1 2 1 Units Comm object 12926 Related applications AMF MRS Description Shows selected frequency of ECU ECU Frequency Select 6 back to List of values Value group Engine Related FW 1 2 1 Units Comm object 10034 Related applications AMF MRS Description Shows binary status 0 or 1 of ECU ECU Yellow Lamp ECU Red Lamp Wait To Start ECU State 6 back to List of values Value group Engine Related FW 1...

Страница 411: ...1 Units RPM Comm object 10006 Related applications AMF MRS Description Requested engine speed Speed Required RPM 6 back to List of values Group Generator Value group Generator Related FW 1 2 1 Units Hz Comm object 8210 Related applications AMF MRS Description Frequency of generator Generator Frequency 6 back to List of values Value group Generator Related FW 1 2 1 Units V Comm object 9628 Related ...

Страница 412: ... back to List of values Value group Generator Related FW 1 2 1 Units V Comm object 8193 Related applications AMF MRS Description Generator voltage on phase 2 Generator Voltage L2 N 6 back to List of values Value group Generator Related FW 1 2 1 Units V Comm object 9630 Related applications AMF MRS Description Generator phase to phase voltage between L3 and L1 phases Generator Voltage L3 L1 6 back ...

Страница 413: ...cations AMF MRS Description Generator nominal power Nominal Power 6 back to List of values Value group Generator Related FW 1 2 1 Units V Comm object 9917 Related applications AMF MRS Description Generator nominal voltage Nominal Voltage 6 back to List of values Value group Generator Related FW 1 2 1 Units A Comm object 14325 Related applications AMF MRS Description Measured value of fault for eva...

Страница 414: ...witch into one decimal power format via LiteEdit2015 PC tool In this case the range of value is decrease 10 times Load A L2 6 back to List of values Value group Load Related FW 1 2 1 Units A Comm object 8200 Related applications AMF MRS Description Load current phase L3 Note This value can be also switch into one decimal power format via LiteEdit2015 PC tool In this case the range of value is decr...

Страница 415: ... is capacitive and R is resistive load power factor 1 Load Characteristic L2 6 back to List of values Value group Load Related FW 1 2 1 Units Comm object 8628 Related applications AMF MRS Description Character of the generator load in the L3 phase L means inductive load C is capacitive and R is resistive load power factor 1 Load Characteristic L3 6 back to List of values Value group Load Related F...

Страница 416: ...t via LiteEdit2015 PC tool In this case the range of value is decrease 10 times Load kVA L2 6 back to List of values Value group Load Related FW 1 2 1 Units kVA Comm object 8532 Related applications AMF MRS Description Load apparent power L3 Note This value can be also switch into one decimal power format via LiteEdit2015 PC tool In this case the range of value is decrease 10 times Load kVA L3 6 b...

Страница 417: ...er format via LiteEdit2015 PC tool In this case the range of value is decrease 10 times Load kVAr L2 6 back to List of values Value group Load Related FW 1 2 1 Units kVAr Comm object 8529 Related applications AMF MRS Description Load reactive power in phase L3 Note This value can be also switch into one decimal power format via LiteEdit2015 PC tool In this case the range of value is decrease 10 ti...

Страница 418: ... in phase L2 Note This value can be also switch into one decimal power format via LiteEdit2015 PC tool In this case the range of value is decrease 10 times Load kW L2 6 back to List of values Value group Load Related FW 1 2 1 Units kW Comm object 8526 Related applications AMF MRS Description Load active power in phase L3 Note This value can be also switch into one decimal power format via LiteEdit...

Страница 419: ...Units Comm object 8535 Related applications AMF MRS Description Generator power factor in phase L3 Load Power Factor L3 6 back to List of values Group Controler I O Value group Controler I O Related FW 1 2 1 Units Configurable Comm object 9151 Related applications AMF MRS Description This is the value of the analog input 1 of the controller Analog Input 1 6 back to List of values Value group Contr...

Страница 420: ...he controller Analog Input 4 6 back to List of values Value group Controler I O Related FW 1 2 1 Units V Comm object 8213 Related applications AMF MRS Description Controller supply voltage BatteryVoltage 6 back to List of values Value group Controler I O Related FW 1 2 1 Units Comm object 8235 Related applications AMF MRS Description State of the binary inputs of the controller Binary Inputs 6 bac...

Страница 421: ... case the range of value is decrease 10 times Genset kWArh 6 back to List of values Value group Statistics Related FW 1 2 1 Units kWh Comm object 8205 Related applications AMF MRS Description Counter of gen set active power Note This value can be also switch into one decimal power format via LiteEdit2015 PC tool In this case the range of value is decrease 10 times Genset kWh 6 back to List of valu...

Страница 422: ...189 Maintenance 3 6 back to List of values Value group Statistics Related FW 1 2 1 Units Comm object 11195 Related applications AMF MRS Description Emergency stop alarms counter Num E Stops 6 back to List of values Value group Statistics Related FW 1 2 1 Units Comm object 8207 Related applications AMF MRS Description Engine start commands counter The counter is increased by 1 even if the particula...

Страница 423: ...alue group Statistics Related FW 1 2 1 Units Comm object 11196 Related applications AMF MRS Description Shutdown alarms counter This counter counts all occurrences of a shutdown alarm not only real shutdowns of the gen set i e the counter is increased by 2 if two shutdown alarms appear simultaneously Shutdowns 6 back to List of values Value group Statistics Related FW 1 2 1 Units days Comm object ...

Страница 424: ... Volume page 185 and value from ECU Fuel Rate For correct calculation of this value is necessary to have configured ECU which send Fuel Rate value otherwise this value can t be calculated Time Till Empty 6 back to List of values Value group Statistics Related FW 1 2 1 Units L Comm object 9040 Related applications AMF MRS Description Value containing total amount of consumed fuel by engine The cont...

Страница 425: ... group IL Info Related FW 1 2 1 Units Comm object 12944 Related applications AMF MRS Description The text of this value represents the connection type which is adjusted in setpoint Connection type page 157 Connection Type 6 back to List of values Value group IL Info Related FW 1 2 1 Units Comm object 9244 Related applications AMF MRS Description The value contains actual engine state message which...

Страница 426: ...4202 Related applications AMF MRS Description This value contains a number which can be used for retrieving a lost password Send this number together with the controller serial number to your distributor if you have lost your password Password Decode 6 back to List of values Value group IL Info Related FW 1 2 1 Units Comm object 14447 Related applications AMF MRS Description The name of plug in mo...

Страница 427: ...tain the assignment of texts to the codes Timer Text 6 back to List of values Value group IL Info Related FW 1 2 1 Units HH MM SS Comm object 14147 Related applications AMF MRS Description The value contains the Current process timer value which is shown on the main screen of the controller Timer Value 6 back to List of values Group Log Bout Value group Log Bout Related FW 1 2 1 Units Comm object ...

Страница 428: ...g Bout 4 6 back to List of values Value group Log Bout Related FW 1 2 1 Units Comm object 9147 Related applications AMF MRS Description State of binary outputs Log Bout 5 6 back to List of values Value group Log Bout Related FW 1 2 1 Units Comm object 9148 Related applications AMF MRS Description State of binary outputs Log Bout 6 6 back to List of values Value group Log Bout Related FW 1 2 1 Unit...

Страница 429: ...k to List of values Group CM GPRS Value group CM GPRS CM 4G GPS 4G part Related FW 1 2 1 Units Comm object 24308 Related applications AMF MRS Description Diagnostic code for AirGate connection Helps in troubleshooting Code Description 0 SIM card is not inserted 1 Controller registered waiting for authorization 2 Not possible to register controller blacklisted 3 Not possible to register server has ...

Страница 430: ...lues Value group CM GPRS CM 4G GPS 4G part Related FW 1 2 1 Units Comm object 24288 Related applications AMF MRS Description Diagnostic code for the CM GPRS or CM 4G GPS module Code Description 0 OK No error 1 Not possible to hang up 2 Modul is switched off 3 Module is switched on 4 Module error in initialization 5 Module not possible to set the APN 6 Module not possible to connect to GPRS network...

Страница 431: ... can t detect module speed 24 SIMCom HW reset issued 25 PUK is required 26 Error of SIM card detected 27 ME909s can t set module bps 28 ME909s can t set link configuration 29 ME909s can t do power off 30 ME909s can t do power on 31 ME909s can t do hardware reset 32 ME909s ME909s not started 33 ME909s switch off issued 34 ME909s switch on issued 35 ME909s HW reset issued 36 ME909s can t switch echo...

Страница 432: ... GPRS CM 4G GPS 4G part Related FW 1 2 1 Units Comm object 24302 Related applications AMF MRS Description This value contains information about relative strength of the cellular signal received by the CM GPRS module or by CM 4G GPS module It is a relative value helping to find the best signal and for troubleshooting cases Cell Signal Lev 6 back to List of values Value group CM GPRS CM 4G GPS 4G pa...

Страница 433: ...d 7 Command can t be send 8 HELO command was refused 11 AUTH LOGIN command was refused 12 Wrong user name 13 Wrong password 14 MAIL FROM command was refused 15 RCPT TO command was refused 16 DATA command was refused 17 Sending of email failed 18 SMTP server refused the data of email 19 SMTP server refused the data of email 20 QUIT command was refused 21 Lost of connection 23 Error during closing t...

Страница 434: ...on Actual GPS altitude Altitude 6 back to List of values Value group CM 4G GPS GPS part Related FW 1 2 1 Units km Comm object 11680 Related applications AMF MRS Description Actual distance from home position Home position is adjusted via setpoints Home Latitude page 283 and Home Longitude page 283 or by binary input GEO HOME POSITION PAGE 455 HomePosDist 6 back to List of values Value group CM 4G ...

Страница 435: ...Value group CM 4G GPS GPS part Related FW 1 2 1 Units Comm object 24265 Related applications AMF MRS Description Number of available satellites for GPS location Satellites 6 back to List of values Value group CM GPRS CM 4G GPS 4G part Related FW 1 2 1 Units Comm object 24309 Related applications AMF MRS Description Identification string generated by AirGate server for the purpose of establishing c...

Страница 436: ...other reason 5 Controller registered and authorized AirGate Status 6 back to List of values Value group CM GPRS CM 4G GPS 4G part Related FW 1 2 1 Units Comm object 24146 Related applications AMF MRS Description The type of data connection Connection Type 6 back to List of values Value group CM GPRS CM 4G GPS 4G part Related FW 1 2 1 Units Comm object 24288 Related applications AMF MRS Description...

Страница 437: ...er to complement initialization string 17 Not possible to read GSM signal strength 18 CDMA modem not detected 19 No CDMA network 20 Unsuccessful registration to CDMA network 21 SIMCom ME909s can t read FW version 22 SIMCom GSM signal not found 23 SIMCom can t detect module speed 24 SIMCom HW reset issued 25 PUK is required 26 Error of SIM card detected 27 ME909s can t set module bps 28 ME909s can ...

Страница 438: ...igher quality of signal Cell ErrorRate 6 back to List of values Value group CM GPRS CM 4G GPS 4G part Related FW 1 2 1 Units Comm object 24302 Related applications AMF MRS Description This value contains information about relative strength of the cellular signal received by the CM GPRS module or by CM 4G GPS module It is a relative value helping to find the best signal and for troubleshooting case...

Страница 439: ...d 7 Command can t be send 8 HELO command was refused 11 AUTH LOGIN command was refused 12 Wrong user name 13 Wrong password 14 MAIL FROM command was refused 15 RCPT TO command was refused 16 DATA command was refused 17 Sending of email failed 18 SMTP server refused the data of email 19 SMTP server refused the data of email 20 QUIT command was refused 21 Lost of connection 23 Error during closing t...

Страница 440: ... for AirGate connection Helps in troubleshooting Code Description 0 Ethernet cable is disconected 1 Controller registered waiting for authorization 2 Not possible to register controller blacklisted 3 Not possible to register server has no more capacity 4 Not possible to register other reason 5 Controller registered and authorized AirGate Status 6 back to List of values Value group CM Ethernet Rela...

Страница 441: ...plications AMF MRS Description Current status of ethernet communication ETH Interface Status 6 back to List of values Value group CM Ethernet Related FW 1 2 1 Units Comm object 24182 Related applications AMF MRS Description Current gateway address Current Gateway 6 back to List of values Value group CM Ethernet Related FW 1 2 1 Units Comm object 24184 Related applications AMF MRS Description Curre...

Страница 442: ...ame 13 Wrong password 14 MAIL FROM command was refused 15 RCPT TO command was refused 16 DATA command was refused 17 Sending of email failed 20 QUIT command was refused 25 It is impossible to create data for command DATA 26 It is impossible to read data for command DATA 27 Email address can t be read 30 SMTP server address translation error from DNS server 31 Error reading email content data 24327...

Страница 443: ...Comm object 24554 Related applications AMF MRS Description Shows setup time Time 6 back to List of values Value group Date Time Related FW 1 2 1 Units DD MM YYYY Comm object 24553 Related applications AMF MRS Description Shows setup date Date 6 back to List of values Group Plug In I O Value group Plug In I O Related FW 1 2 1 Units Comm object 14291 Related applications AMF MRS Description Binary i...

Страница 444: ...st of values Value group PLC Related FW 1 2 1 Units Comm object 10505 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc PLC Resource 2 6 back to List of values Value group PLC Related FW 1 2 1 Units Comm object 10506 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc PLC Resource 3 6 back to Li...

Страница 445: ...ource 6 6 back to List of values Value group PLC Related FW 1 2 1 Units Comm object 10510 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc PLC Resource 7 6 back to List of values Value group PLC Related FW 1 2 1 Units Comm object 10511 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc PLC Res...

Страница 446: ... BOUT 3 6 back to List of values Value group PLC Related FW 1 2 1 Units Comm object 10427 Related applications AMF MRS Description State of binary outputs of PLC PLC BOUT 4 6 back to List of values Value group PLC Related FW 1 2 1 Units Comm object 10428 Related applications AMF MRS Description State of binary outputs of PLC PLC BOUT 5 6 back to List of values Value group PLC Related FW 1 2 1 Unit...

Страница 447: ...InteliLite Global Guide 447 Value group PLC Related FW 1 2 1 Units Comm object 10430 Related applications AMF MRS Description State of binary outputs of PLC PLC BOUT 7 6 back to List of values ...

Страница 448: ...nputs for binary values and functions Alphabetical groups of Logical binary inputs LBI A 450 LBI B 450 LBI C 451 LBI E 452 LBI F 453 LBI G 454 LBI H 456 LBI I 456 LBI L 457 LBI N 458 LBI O 458 LBI R 459 LBI S 461 For full list of Logical binary inputs go to the chapter Logical binary inputs alphabetically page 449 ...

Страница 449: ...53 Fault Reset Button 453 Force Regeneration 453 Fuel Level 454 Fuel Pump On Off 454 GCB Button 454 GCB Feedback 455 Geo Home Position 455 Geo Fencing Enabled 456 Horn Reset Button 456 Idle Speed 456 Lang Selection 1 457 Lang Selection 2 457 Lang Selection 3 458 Not Used 458 Oil Pressure 458 Regeneration Inhib 459 Remote AUTO 459 Remote Ctrl Lock 459 Remote MAN 460 Remote OFF 460 Remote Start Stop...

Страница 450: ...configuration sets When this binary input is active setpoints in Alternate Config group are switched to the second set setpoints with number 2 Configuration 2 6 back to Logical binary inputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 860 Description This binary input can switch between configuration sets When this binary input is active setpoints in Alternate Config g...

Страница 451: ...or BOC Breaker Open and Cooling protection Sd Binary input is used for shutdown protection Protection types BIN Protection 1 48 6 back to Logical binary inputs alphabetically LBI C Related FW 1 2 1 Related applications AMF MRS Comm object 625 Description Binary input for COOLANT TEMP PAGE 543 protection Monitoring Binary input is not used for protection or any other function Signal is only monitor...

Страница 452: ... designed to allow the gen set to be controlled externally not by the controller This feature can be useful in case of testing the gen set or in case of some failure which disables the gen set to be controlled by the controller but the gen set itself is operational The controller behaves in the following way Shows the text EmergMan in the engine status on the main screen Stops all functions regard...

Страница 453: ... detail see chapter Emergency stop page 33 recommended wiring Emergency Stop 6 back to Logical binary inputs alphabetically LBI F Related FW 1 2 1 Related applications AMF MRS Comm object 191 Description Binary input has the same function as Fault Reset button on the InteliLite front panel Fault Reset Button 6 back to Logical binary inputs alphabetically Related FW 1 2 1 Related applications AMF M...

Страница 454: ...ns AMF MRS Comm object 694 Description This binary input is used for manual control of binary output FUEL PUMP PAGE 493 Note This binary input is basically designed for ON and OFF switch switch with arrestment in these positions because controller reacts to rising and falling edge of signal in this input IMPORTANT When binary input FUEL PUMP ON OFF PAGE 454 is configured then binary output FUEL PU...

Страница 455: ...not configure the feedback to binary inputs GCB Feedback 6 back to Logical binary inputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 219 Description This binary input can be used to adjust home position of gen set In case that binary input is active setpoints Home Latitude page 283 and Home Longitude page 283 are adjusted automatically from actual coordinates from GPS ...

Страница 456: ... 6 back to Logical binary inputs alphabetically LBI H Related FW 1 2 1 Related applications AMF MRS Comm object 192 Description Binary input has the same function as Horn reset button on the InteliLite front panel Horn Reset Button 6 back to Logical binary inputs alphabetically LBI I Related FW 1 2 1 Related applications AMF MRS Comm object 624 Description This binary input changes cooling speed f...

Страница 457: ...d LANG SELECTION 3 PAGE 458 are active 5 Fifth language Lang Selection 1 6 back to Logical binary inputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 108 Description Use this binary input with binary input LANG SELECTION 1 PAGE 457 and LANG SELECTION 3 PAGE 458 to choose required language of controller The system is based on binary numbers Binary input Binary number Act...

Страница 458: ...are active 5 Fifth language Lang Selection 3 6 back to Logical binary inputs alphabetically LBI N Related FW 1 2 1 Related applications AMF MRS Comm object 184 Description Binary input has no function Use this configuration when binary input is not used Not Used 6 back to Logical binary inputs alphabetically LBI O Related FW 1 2 1 Related applications AMF MRS Comm object 43 Description Binary inpu...

Страница 459: ... there are four modes OFF MAN AUTO TEST when this binary input is closed When opens controller is switched back to previous mode This binary input has the lowest priority from Remote OFF MAN AUTO TEST binary inputs Remote control priority Remote OFF Highest priority Remote TEST Remote MAN Remote AUTO Lowest Priority Remote AUTO 6 back to Logical binary inputs alphabetically Related FW 1 2 1 Relate...

Страница 460: ...s alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 617 Description The controller is switched to the OFF mode there are four modes OFF MAN AUTO TEST when this binary input is closed When opens controller is switched back to previous mode Remote control priority Remote OFF Highest priority Remote TEST Remote MAN Remote AUTO Lowest Priority Remote OFF 6 back to Logical binary...

Страница 461: ...ne is not protected IMPORTANT MISUSE OF THIS INPUT CAN CAUSE DAMAGE TO THE GEN SET Sd Override 6 back to Logical binary inputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 189 Description Binary input has the same function as Start Button on the InteliLite front panel It is evaluated in MAN mode only Start Button 6 back to Logical binary inputs alphabetically Related FW...

Страница 462: ...s for binary values and functions Alphabetical groups of Logical binary outputs LBO A 465 LBO B 486 LBO C 490 LBO E 490 LBO F 493 LBO G 495 LBO H 502 LBO I 503 LBO M 505 LBO N 505 LBO P 506 LBO R 508 LBO S 509 LBO T 513 For full list of Logical binary outputs go to the chapter Logical binary outputs alphabetically page 463 ...

Страница 463: ...Fail 475 AL Underspeed 475 Alarm 476 Analog Switch 1 476 Analog Switch 2 477 Analog Switch 3 477 Analog Switch 4 478 Analog Switch 5 478 Analog Switch 6 479 Analog Switch 7 479 Analog Switch 8 480 Analog Switch 9 480 Analog Switch 10 481 Analog Switch 11 481 Analog Switch 12 482 Analog Switch 13 482 Analog Switch 14 483 Analog Switch 15 483 Analog Switch 16 484 Analog Switch 17 484 Analog Switch 1...

Страница 464: ...InteliLite Global Guide 464 Sd Override 509 Starter 510 Still Log 0 510 Still Log 1 510 Stop Pulse 511 Stop Solenoid 511 Supplying Load 512 Temperature Switch 513 ...

Страница 465: ... 1 Related applications AMF MRS Comm object 1386 Description The output is closed when there is the shutdown or BOC alarm from the analog input 1 of the controller present in the alarmlist or isn t confirmed AL AIN 1 Sd BOC 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1382 Description The output is closed when there is the warning alarm ...

Страница 466: ...lications AMF MRS Comm object 1388 Description The output is closed when there is the shutdown or BOC alarm from the analog input 3 of the controller present in the alarmlist or isn t confirmed AL AIN 3 Sd BOC 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1384 Description The output is closed when there is the warning alarm from the analo...

Страница 467: ...habetically Related FW 1 2 1 Related applications AMF MRS Comm object 1272 Description This output is active when the Battery Charge Fail page 564 alarm is present in the alarmlist or isn t confirmed AL Battery Charge 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1293 Description This output is active when the Wrn Battery Voltage page 567...

Страница 468: ...s active and Fault reset button is pressed AL Common Sd 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 3 Description Output closes when any warning alarm appears The output opens if No warning alarm is active and Fault reset button is pressed AL Common Wrn 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related application...

Страница 469: ...ive if protection type is set to HistRecOnl and threshold level for history record is reach AL CoolantTemp Wrn 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1260 Description This output is active when the Wrn Charging Alternator Fail page 567 alarm is present in the alarmlist or isn t confirm AL D Fail 6 back to Logical binary outputs alp...

Страница 470: ...alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1423 Description The output is closed when there is the shutdown or BOC alarm from the FUEL LEVEL PAGE 544 in the alarmlist or isn t confirmed AL Fuel Level Sd 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1422 Description The output is closed when there is the warni...

Страница 471: ...ted FW 1 2 1 Related applications AMF MRS Comm object 1261 Description This output is active when at least one generator overvoltage alarm is present in alarmlist or isn t confirm AL Gen Voltage 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1265 Description This output is active when at least one generator underfrequency alarm is present ...

Страница 472: ...ive when the Alarm Maintenance 1 is present in the alarmlist It means that counter of maintenance is on zero or the Alarm Maintenance 1 isn t confirm AL Maintenance 1 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1255 Description This output is active when the Alarm Maintenance 2 is present in the alarmlist It means that counter of mainte...

Страница 473: ...s reach AL Oil Press Wrn 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 109 Description This output is active when the BOC Overcurrent IDMT page 598 alarm is present in alarmlist or isn t confirm AL Overcurrent 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1268 Description This ou...

Страница 474: ...e 592 alarm is present in the alarmlist or isn t confirm AL Overspeed 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1370 Description The binary output closes when the Rental Timer 1 page 278 elapsed Image 8 131 Rental Timer 1 AL Rental Timer 1 6 back to Logical binary outputs alphabetically ...

Страница 475: ...larm is present in the alarmlist or isn t confirm AL Start Fail 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 339 Description This output is active when the Wrn Stop Fail page 576 alarm is present in the alarmlist or isn t confirm AL Stop Fail 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Co...

Страница 476: ... confirmation of alarm Alarm 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1400 Description This is an output from the General Analog Input 1 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 1 On page 204 and Analog Switch 1 Off page 205 The value is measured from AIN SWITCH 01 PAGE 536 a...

Страница 477: ...og input Image 8 134 General analog input 2 switch Analog Switch 2 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1402 Description This is an output from the General Analog Input 3 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 3 On page 210 and Analog Switch 3 Off page 211 The value is ...

Страница 478: ...g input Image 8 136 General analog input 4 switch Analog Switch 4 6 Logical binary outputs alphabetically page 463 Related FW 1 2 1 Related applications AMF MRS Comm object 1787 Description This is an output from the General Analog Input 5 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 5 On page 216 and Analog Switch 5 Off page 217 The value is ...

Страница 479: ...g input Image 8 138 General analog input 6 switch Analog Switch 6 6 Logical binary outputs alphabetically page 463 Related FW 1 2 1 Related applications AMF MRS Comm object 1789 Description This is an output from the General Analog Input 7 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 7 On page 222 and Analog Switch 7 Off page 223 The value is ...

Страница 480: ...g input Image 8 140 General analog input 8 switch Analog Switch 8 6 Logical binary outputs alphabetically page 463 Related FW 1 2 1 Related applications AMF MRS Comm object 1791 Description This is an output from the General Analog Input 9 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 9 On page 228 and Analog Switch 9 Off page 229 The value is ...

Страница 481: ...input Image 8 142 General analog input 10 switch Analog Switch 10 6 Logical binary outputs alphabetically page 463 Related FW 1 2 1 Related applications AMF MRS Comm object 1793 Description This is an output from the General Analog Input 11 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 11 On page 234 and Analog Switch 11 Off page 235 The value ...

Страница 482: ...input Image 8 144 General analog input 12 switch Analog Switch 12 6 Logical binary outputs alphabetically page 463 Related FW 1 2 1 Related applications AMF MRS Comm object 1795 Description This is an output from the General Analog Input 13 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 13 On page 240 and Analog Switch 13 Off page 241 The value ...

Страница 483: ...input Image 8 146 General analog input 14 switch Analog Switch 14 6 Logical binary outputs alphabetically page 463 Related FW 1 2 1 Related applications AMF MRS Comm object 1797 Description This is an output from the General Analog Input 15 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 15 On page 246 and Analog Switch 15 Off page 247 The value ...

Страница 484: ...input Image 8 148 General analog input 16 switch Analog Switch 16 6 Logical binary outputs alphabetically page 463 Related FW 1 2 1 Related applications AMF MRS Comm object 1799 Description This is an output from the General Analog Input 17 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 17 On page 252 and Analog Switch 17 Off page 253 The value ...

Страница 485: ...input Image 8 150 General analog input 18 switch Analog Switch 18 6 Logical binary outputs alphabetically page 463 Related FW 1 2 1 Related applications AMF MRS Comm object 1801 Description This is an output from the General Analog Input 19 switch function The behavior of the switch depends on the adjustment of the setpoints Analog Switch 19 On page 258 and Analog Switch 19 Off page 259 The value ...

Страница 486: ... SWITCH 20 PAGE 542 analog input Image 8 152 General analog input 20 switch Analog Switch 20 6 Logical binary outputs alphabetically page 463 LBO B Related FW 1 2 1 Related applications AMF MRS Comm object 1374 Description This output is closed when Binary Input 1 is active and open when Binary Input 1 is inactive When Binary Input 1 is used for BIN protection function then this output is closed w...

Страница 487: ...arm is in Alarmlist Image 8 154 Binary Input 2 Status BIN 2 Status 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1376 Description This output is closed when Binary Input 3 is active and open when Binary Input 3 is inactive When Binary Input 3 is used for BIN protection function then this output is closed when BIN protection alarm is in Al...

Страница 488: ...arm is in Alarmlist Image 8 156 Binary Input 4 Status BIN 4 Status 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1378 Description This output is closed when Binary Input 5 is active and open when Binary Input 5 is inactive When Binary Input 5 is used for BIN protection function then this output is closed when BIN protection alarm is in Al...

Страница 489: ...arm is in Alarmlist Image 8 158 Binary Input 6 Status BIN 6 Status 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1380 Description This output is closed when Binary Input 7 is active and open when Binary Input 7 is inactive When Binary Input 7 is used for BIN protection function then this output is closed when BIN protection alarm is in Al...

Страница 490: ...y outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 74 Description The output closes when gen set is in Cooling state Cooling 6 back to Logical binary outputs alphabetically LBO E Related FW 1 2 1 Related applications AMF MRS Comm object 348 Description This output is active when an ECU is configured but the communication with the ECU is not established or has droppe...

Страница 491: ...h PRESTART PAGE 506 and remains closed for the entire duration that the engine is running It is opened at the moment that the engine comes to a stop i e together with the FUEL SOLENOID PAGE 493 Image 8 161 ECU Power Relay ECU Power Relay 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 350 Description This output is active when the ECU sends...

Страница 492: ...timer 1 This output makes it easy to make periodic tests of the gen set and its activation depends on the setpoints in the Subgroup Timer 1 page 264 subgroup This output is active when Timer 1 is active Note In the event that both Timers are active at the same time Subgroup Timer 1 page 264 has a higher priority than Subgroup Timer 2 page 271 Exercise Timer 1 6 back to Logical binary outputs alpha...

Страница 493: ...sed by binary input FUEL PUMP ON OFF PAGE 454 In this case the binary output FUEL PUMP ON PAGE 186 is closed until the binary input FUEL PUMP ON OFF PAGE 454 is active or until the value of Fuel Pump Off page 187 is reached Note Setpoints Fuel Pump On page 186 and Fuel Pump Off page 187 are invisible until configuration of this LBO Fuel Pump 6 back to Logical binary outputs alphabetically Related ...

Страница 494: ...ore binary output STARTER PAGE 510 The lead time is adjusted by setpoint Fuel Solenoid Lead page 169 Image 8 162 Fuel Solenoid 1 Image 8 163 Fuel Solenoid 2 The output opens when Emergency Stop comes cooled gen set is stopped in pause between repeated starts ...

Страница 495: ... Logical binary outputs alphabetically LBO G Related FW 1 2 1 Related applications AMF MRS Comm object 41 Description The output controls the generator circuit breaker Its state represents the breaker position requested by the controller The breaker must react within 5 seconds to a close or open command otherwise an alarm is issued Note InteliLite controllers can work even without breaker feedback...

Страница 496: ...InteliLite Global Guide 496 Image 8 165 GCB Close command Image 8 166 Repeated GCB Close command Image 8 167 GCB Open command 6 back to Logical binary outputs alphabetically ...

Страница 497: ...utput is intended for control of open coil of generator circuit breaker The output gives a pulse in the moment the breaker has to be opened The pulse lasts until the feedback deactivates but at least for 5 seconds Image 8 168 GCB OFF Coil command GCB OFF Coil 6 back to Logical binary outputs alphabetically ...

Страница 498: ...east 5 second pulse in the moment the breaker has to be closed Image 8 169 GCB ON Coil close command Image 8 170 Repeated GCB ON coil close command GCB ON Coil 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 44 Description The output is intended for control of undervoltage coil of generator circuit breaker The output is active the GCB UV Co...

Страница 499: ...the generator is running The output is deactivated for at least 5 seconds in the moment the breaker has to be switched off Image 8 171 GCB UV Coil close command Image 8 172 GCB UV Coil open command 6 back to Logical binary outputs alphabetically ...

Страница 500: ...er overvoltage under overfrequency and voltage unbalance as well as appropriate delays can be found in the setpoints Group Generator settings page 194 Generator Healthy 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1252 Description This output is dedicated for diesel engine only This output will close for exact time pre set by setpoint Gl...

Страница 501: ... is long as Cranking Fail Pause page 165 Image 8 174 Glow Plugs in Cranking Fail Pause 1 When the Glow Plugs Time page 168 is shorter than Cranking Fail Pause page 165 then the Glow Plugs Time page 168 in Cranking Fail Pause page 165 is long as normal Glow Plugs Time page 168 Image 8 175 Glow Plugs in Cranking Fail Pause 2 6 back to Logical binary outputs alphabetically ...

Страница 502: ...Lamp If ECU stop send HEST LAMP signal binary input will be opened without no matter if alarms in alarmlist are confirmed or not HEST Lamp 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 1 Description The output designed to be used for acoustic indication of a newly appeared alarm The output is activated each time a new alarm has appeared a...

Страница 503: ...nect binary output Idle Nominal to speed governor to switch the speed opened Idle closed Nominal for normally open contact type Idle Nominal 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 37 Description This output is dedicated to controlling the ignition at a gas engine The output is closed together with binary output FUEL SOLENOID PAGE 4...

Страница 504: ...cations AMF MRS Comm object 1257 Description This input is on since start button is pressed till the unit is completely stopped or the engine doesn t start or Sd or E Stop becomes active Note This function is the same as ECU POWER RELAY PAGE 491 Ignition ON stays there from historical reasons Ignition On 6 back to Logical binary outputs alphabetically ...

Страница 505: ...output is active whenever the controller is in AUTO mode Mode AUTO 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 18 Description This output is active whenever the controller is in MAN mode Mode MAN 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 17 Description This output is active...

Страница 506: ...running and is allowed 30 s after start of the engine Image 8 179 Power Switch Note Setpoints Power Switch On page 190 and Power Switch Off page 192 are invisible until configuration of this LBO Power Switch 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 36 Description This output can be used for control of any device which has to be activ...

Страница 507: ... long as Cranking Fail Pause page 165 minus 100ms Image 8 181 Prestart in Cranking Fail Pause 1 When the Prestart Time page 166 is shorter than Cranking Fail Pause page 165 then the Prestart Time page 166 in Cranking Fail Pause page 165 is long as normal Prestart Time page 166 Image 8 182 Prestart in Cranking Fail Pause 2 6 back to Logical binary outputs alphabetically ...

Страница 508: ... limits until delay is count down then output is still closed Ready To Load 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 62 Description The binary output is closed when the engine is stopped and it is possible to start it i e no red alarm is activated or SD OVERRIDE PAGE 461 is active The binary output is switch on when the Ready state o...

Страница 509: ...n The out remains close until engine stop and cooling period elapses Image 8 183 Running Running 6 back to Logical binary outputs alphabetically LBO S Related FW 1 2 1 Related applications AMF MRS Comm object 962 Description The output is closed if SD OVERRIDE PAGE 461 input is active and open if SD OVERRIDE PAGE 461 input is inactive This output is usually used to send information about SD OVERRI...

Страница 510: ...ceeded request to stop comes up D value is higher than 80 Oil pressure value is higher than Starting Oil Pressure page 167 Generator voltage 25 of Nominal Voltage Ph N page 158 or Nominal Voltage Ph Ph page 159 any phase Starter 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 26 Description Logical binary output which is still in logical 0 ...

Страница 511: ...to ECU in case of engine stop request Image 8 185 Stop Pulse Stop Pulse 6 back to Logical binary outputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 23 Description This output is dedicated to control the stop solenoid valve The output closes when an engine stop command is received and remains active until the gen set is stopped Image 8 186 Stop Solenoid 1 Stop Solenoid...

Страница 512: ...F MRS Comm object 1249 Description The binary output depends on measured generator active power Power is compared with generator nominal active power with use of hysteresis and with delay of switch 1 s When the measured active power is equal or bigger than 5 of Nominal Power page 156 for 1 s than the binary output is closed When the measured active power is equal or lower than 3 of Nominal Power p...

Страница 513: ... The behavior of the switch depends on the adjustment of the setpoints Temperature Switch On page 181 and Temperature Switch Off page 182 Image 8 188 Temperature Switch Note Setpoints Temperature Switch On page 181 and Temperature Switch Off page 182 are invisible until configuration of this LBO Temperature Switch 6 back to Logical binary outputs alphabetically ...

Страница 514: ...l analog inputs are Logical analog inputs are inputs for analog values Alphabetical groups of Logical analog inputs LAI A 516 LAI C 543 LAI F 544 LAI N 545 LAI O 546 For full list of Logical analog inputs go to the chapter Logical analog inputs alphabetically page 515 ...

Страница 515: ...17 532 AIN Prot 18 533 AIN Prot 19 534 AIN Prot 20 535 AIN Switch 01 536 AIN Switch 02 536 AIN Switch 03 536 AIN Switch 04 537 AIN Switch 05 537 AIN Switch 06 537 AIN Switch 07 538 AIN Switch 08 538 AIN Switch 09 538 AIN Switch 10 539 AIN Switch 11 539 AIN Switch 12 539 AIN Switch 13 540 AIN Switch 14 540 AIN Switch 15 540 AIN Switch 16 541 AIN Switch 17 541 AIN Switch 18 541 AIN Switch 19 542 AIN...

Страница 516: ...and Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value...

Страница 517: ... Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of...

Страница 518: ... Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of...

Страница 519: ... Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of...

Страница 520: ... Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of...

Страница 521: ... Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of...

Страница 522: ... Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of...

Страница 523: ... Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of...

Страница 524: ... Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of...

Страница 525: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 526: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 527: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 528: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 529: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 530: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 531: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 532: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 533: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 534: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 535: ...d Cooling protection BOC Analog value is used for BOC Breaker Open and Cooling protection Wrn Sd Analog value is used for warning and shutdown protection Sd Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value o...

Страница 536: ...log inputs see Analog inputs on page 33 This analog input controls logical binary output ANALOG SWITCH 2 PAGE 477 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 2 On page 207 and Analog Switch 2 Off page 208 IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Switch 02 6 back to Logical analog in...

Страница 537: ...log inputs see Analog inputs on page 33 This analog input controls logical binary output ANALOG SWITCH 5 PAGE 478 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 5 On page 216 and Analog Switch 5 Off page 217 IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Switch 05 6 back to Logical analog in...

Страница 538: ...log inputs see Analog inputs on page 33 This analog input controls logical binary output ANALOG SWITCH 8 PAGE 480 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 8 On page 225 and Analog Switch 8 Off page 226 IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Switch 08 6 back to Logical analog in...

Страница 539: ...og inputs see Analog inputs on page 33 This analog input controls logical binary output ANALOG SWITCH 11 PAGE 481 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 11 On page 234 and Analog Switch 11 Off page 235 IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Switch 11 6 back to Logical analog ...

Страница 540: ...og inputs see Analog inputs on page 33 This analog input controls logical binary output ANALOG SWITCH 14 PAGE 483 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 14 On page 243 and Analog Switch 14 Off page 244 IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Switch 14 6 back to Logical analog ...

Страница 541: ...og inputs see Analog inputs on page 33 This analog input controls logical binary output ANALOG SWITCH 17 PAGE 484 The behavior of the switch depends on the adjustment of the setpoints Analog Switch 17 On page 252 and Analog Switch 17 Off page 253 IMPORTANT This analog input has no protection Input is designed only to control appropriate logical binary output AIN Switch 17 6 back to Logical analog ...

Страница 542: ...ned only to control appropriate logical binary output AIN Switch 19 6 back to Logical analog inputs alphabetically Related FW 1 2 1 Related applications AMF MRS Comm object 293 Description Logical analog input designed for general value received from analog sensor For more information about wiring of analog inputs see Analog inputs on page 33 This analog input controls logical binary output ANALOG...

Страница 543: ...Analog value is used for shutdown protection Protection types Note This parameter has to be adjusted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of analog input is over adjusted limits Under limit fls Alarm is activated when value of analog input is under adjusted limits If sensor fail is detected then...

Страница 544: ...ted via LiteEdit2015 Under limit Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of analog input is over adjusted limits Under limit fls Alarm is activated when value of analog input is under adjusted limits If sensor fail is detected then the alarm with higher level is activate as well Over limit fls Alarm is activated when value of ...

Страница 545: ...InteliLite Global Guide 545 LAI N Related FW 1 2 1 Related applications AMF MRS Comm object 230 Description Input has no function Not Used 6 back to Logical analog inputs alphabetically ...

Страница 546: ... Alarm is activated when value of analog input is under adjusted limits Over limit Alarm is activated when value of analog input is over adjusted limits Under limit fls Alarm is activated when value of analog input is under adjusted limits If sensor fail is detected then the alarm with higher level is activate as well Over limit fls Alarm is activated when value of analog input is over adjusted li...

Страница 547: ...InteliLite Global Guide 547 Group Comparison of analog inputs 552 Group Time functions 554 Group Other functions 558 For full list of PLC blocks go to the chapter List of PLC blocks page 548 ...

Страница 548: ...roup Basic logical functions OR AND 549 XOR RS 551 Group Comparison of analog inputs Comparator With Hysteresis 552 Comparator With Delay 553 Group Time functions Timer 554 Delay 556 Group Other functions Force History Record 558 Force Protection 558 ...

Страница 549: ...tputs Output Type Negation Range Function Output Binary Yes 0 1 Result of the logical operation Description The block performs logical operation OR AND of 2 8 binary operands The inputs as well as the output can be inverted Input 1 Input 2 Output 0 0 0 0 1 1 1 0 1 1 1 1 Function OR Input 1 Input 2 Output 0 0 0 0 1 0 1 0 0 1 1 1 Function AND There have to be at least 2 inputs every time There may b...

Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...

Страница 551: ... Outputs Output Type Negation Range Function Output Binary Yes 0 1 Result of the logical operation Description The block provides logical function of two values XOR or RS flip flop Both inputs and output can be inverted Input 1 Input 2 Output 0 0 0 0 1 1 1 0 1 1 1 0 Function XOR R S Qn 1 0 0 Qn 0 1 1 1 0 0 1 1 0 Function RS Image 9 2 Configuration of XOR RS block XOR RS 6 back to List of PLC block...

Страница 552: ...ut ON Analog No Same as Input Comparative level for switching on Input OFF Analog No Same as Input Comparative level for switching off Outputs Output Type Negation Range Function Output Binary No 0 1 Comparator output Description The block compares the input value with the comparative levels The behavior depends on whether the ON level is higher than OFF level or vice versa Image 9 3 Different On ...

Страница 553: ...parison of analog inputs Related FW 1 2 1 Related applications AMF MRS Comm object 4 Inputs Input Type Negation Range Function Input 1 Analog No Any Compared value Input 2 Analog No Same as Input 1 Comparative level Delay Analog No 0 0 3000 0 s Comparative delay Outputs Output Type Negation Range Function Output Binary No 0 1 Comparator output Description The block works as an analog switch It com...

Страница 554: ...PLC blocks Group Time functions PLC group Time functions Related FW 1 2 1 Related applications AMF MRS Comm object 14 Inputs Input Type Negation Range Function Run Binary No 0 1 The timer runs only if this input is active or not connected Reload Binary No 0 1 This input reloads the timer to the initial value Reload value Analog No 0 0 3276 7 s Initial value of the timer Outputs Timer ...

Страница 555: ...any other moment using the reload input The timer is held at reload value until the reload input is deactivated The timer output is inverted always when the timer is reloaded Image 9 7 Principle of timer Image 9 8 Configuration of Timer block Note Input reload value can be constant or value from controller Note If you want the output to start at logical 0 tick First down option Otherwise the outpu...

Страница 556: ...appears on Input when Input reset is deactivated already Outputs Output Type Negation Range Function Output Binary No 0 1 Output signal Description This block can work in two modes of operation Delay mode the rising edge at the output is generated with delay of input time up when a rising edge at the input is detected The falling edge at the output is generated with delay of input time down when a...

Страница 557: ...f Delay block Note If Input time up or Input time down value is 0 this input is internally set to zero Note Input time up and Input time down values can be constants or values from controller Note Use Pulse on edge option to choose between delay and pulse mode 6 back to List of PLC blocks ...

Страница 558: ...ivated Image 9 11 Configuration of Force Hist block Note Maximal number of characters for history message is 15 Force History Record 6 back to List of PLC blocks PLC group Other functions Related FW 1 2 1 Related applications AMF MRS Comm object 10 Inputs Input Type Negation Range Function Lvl 1 Binary No 0 1 The input activates yellow level of the configured protection if it is configured Lvl 2 B...

Страница 559: ...Wrn BOC BOC Wrn Sd Sd Note Maximal number of characters for alarmlist message is 15 Note Prefix of protection e g Wrn Sd BOC is added automatically into alarmlist message 6 back to List of PLC blocks 8 2 Alarms 8 2 1 Alarms level 1 559 8 2 2 Alarms level 2 581 8 2 3 Fail sensor and other types 599 What alarms are The controller evaluates two levels of alarms For more information see Alarm manageme...

Страница 560: ...arms level 1 go to List of alarms level 1 page 561 What alarms level 1 are The level 1 alarm indicates that a value or parameter is out of normal limits but has still not reached critical level For more information see Alarm types Level 1 on page 84 ...

Страница 561: ... Wrn Generator L2 Voltage 571 Wrn Generator L2 Voltage 571 Wrn Generator L2L3 Voltage 571 Wrn Generator L2L3 Voltage 571 Wrn Generator L3 Voltage 572 Wrn Generator L3 Voltage 572 Wrn Generator L3L1 Voltage 572 Wrn Generator L3L1 Voltage 573 Wrn Generator Frequency 573 Wrn Generator Frequency 573 Wrn Check DPF Status 573 Wrn Maintenance 1 574 Wrn Maintenance 2 574 Wrn Maintenance 3 574 Wrn Oil Pres...

Страница 562: ...adjusted in setpoint Email Address 2 page 326 and email wasn t send Alarm Email 2 Fail 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Alarm Email 3 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an alarm email to email address which is adjusted in setpoint Email Address 3 page 327 and email wasn t...

Страница 563: ...sted in setpoint Telephone Number 2 page 323 and SMS wasn t send Alarm SMS 2 Fail 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Alarm SMS 3 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an alarm SMS to telephone number which is adjusted in setpoint Telephone Number 3 page 323 and SMS wasn t send...

Страница 564: ...ase Use LiteEdit2015 to enable this function ECU Wait To Start 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Event Email 1 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an event email to email address which is adjusted in setpoint Email Address 1 page 326 and email wasn t send Event Email 1 Fail...

Страница 565: ...usted in setpoint Email Address 4 page 327 and email wasn t send Event Email 4 Fail 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Event SMS 1 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an event SMS to telephone number which is adjusted in setpoint Telephone Number 1 page 322 and SMS wasn t se...

Страница 566: ...o telephone number which is adjusted in setpoint Telephone Number 4 page 324 and SMS wasn t send Event SMS 4 Fail 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Rental Timer 1 Elapsed Alarm evaluated All the time Related applications AMF MRS Description This alarm is activated when Rental Timer 1 page 278 elapses Rental Timer 1 Elapsed 6 back to List of alarms level 1 Alarm ...

Страница 567: ...aluated Engine running only Related applications AMF MRS Description This alarm is issued if the engine is running and the voltage on the D terminal is lower than 80 of the controller supply voltage This alarm works similar to the red battery alarm indicator on a vehicle dashboard The setpoint D Function page 167 has to be in Charge Fail or Enabled position to enable this alarm Wrn Charging Altern...

Страница 568: ... 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Fence 1 Alarm Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates the GPS position of gen set The following setpoint are related to it Geo Fencing page 285 Fence 1 Protection page 286 Fence Radius 1 page 284 Wrn Fence 1 Alarm 6 back to List of alarms level 1 Alarm Type Warning Alarmlis...

Страница 569: ...back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Name of analog input 1 Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that value the general analog protection is out of warning protection limit Wrn AIN Prot 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Name of binary input Alarm evaluated All the time R...

Страница 570: ... to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Generator L1L2 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 1 and 2 The following setpoints are related to it Generator Voltage Wrn page 198 Generator Voltage Delay page 200 Wrn Generator L1L2 Voltage 6 back to List ...

Страница 571: ...s alarm evaluates the generator phase voltage in phase 2 The following setpoints are related to it Generator Voltage Wrn page 199 Generator Voltage Delay page 200 Wrn Generator L2 Voltage 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Generator L2L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator ...

Страница 572: ...rator L3 Voltage 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Generator L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase voltage in phase 3 The following setpoints are related to it Generator Voltage Wrn page 199 Generator Voltage Delay page 200 Wrn Generator L3 Voltage 6 back to List of...

Страница 573: ...oints are related to it Generator Frequency Wrn page 201 Generator Frequency BOC Delay page 202 Wrn Generator Frequency 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Generator Frequency Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator frequency in the phase L1 The following setpoints are related to it Gen...

Страница 574: ... the setpoint will count down while the engine is running and if reaches zero this alarm will be issued It will continue to count down to negative values and the alarm message will remain in the alarm list even if the controller is switched off and on again until the setpoint is re adjusted to a positive value Wrn Maintenance 2 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message ...

Страница 575: ... Warning Alarmlist message Override All Sd Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs when binary input SD OVERRIDE PAGE 461 is activated Wrn Override All Sd 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Wrn Rental Timer 1 Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs xx hours before Rent...

Страница 576: ...PAGE 510 are off Image 9 13 Stop Fail Note Gen set cannot be started until this alarm is inactive and reset Wrn Stop Fail 6 back to List of alarms level 1 Other type Alarm Type Alarm indication Alarmlist message After Treatment Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs when appropriate after treatment lamp is active After Treatment 6 back to List of al...

Страница 577: ...adjusted in setpoint Email Address 1 page 326 and email wasn t send EM A insufficient 6 back to List of alarms level 1 Alarm Type Other Alarmlist message EM A missing or damaged Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that there is a problem with communication with module in slot in first 5 second there was no communication and module is configure...

Страница 578: ...ist message EM B missing or damaged Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that there is a problem with communication with module in slot in first 5 second there was no communication and module is configured in slot EM B missing or damaged 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Generator CCW Rotation Alarm evaluated...

Страница 579: ...t Module slotA false module 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Module slotA unattended Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that two same communication modules are inserted in slots and one of them will be inactive Module slotA unattended 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Module...

Страница 580: ...with communication between controller and module in slot Module slotB comm outage 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Module slotB fake module Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that false module is inserted in slot Module slotB false module 6 back to List of alarms level 1 Alarm Type Other Alarmlist message Mo...

Страница 581: ...evel 1 Alarm Type Warning Alarmlist message Wrn Fuel Transfer Failed Alarm evaluated When FUEL PUMP PAGE 493 is active Related applications AMF MRS Description This alarm will occur when there is no increase of fuel level when FUEL PUMP PAGE 493 is active Wrn Fuel Transfer Failed 6 back to List of alarms level 1 Alarm Type Warning Alarmlist message Transferring Fuel Alarm evaluated When FUEL PUMP ...

Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...

Страница 583: ...nerator Frequency 590 Sd Generator Frequency 590 Sd Generator Voltage Unbalance Ph Ph 591 Sd Generator Voltage Unbalance Ph N 591 Sd Oil Pressure 591 Sd Overload 592 Sd Overspeed 592 Sd RPM Measurement Fail 592 Sd Short Circuit 592 Sd Start Fail 593 Sd Underspeed 593 BOC Coolant Temp 593 BOC Current Unbalance 594 BOC Fence 1 Alarm 594 BOC Fence 2 Alarm 594 BOC Fuel Level 595 BOC AIN Prot 595 BOC B...

Страница 584: ...to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Battery Flat Alarm evaluated During cranking Related applications AMF MRS Description This alarm will be issued if the controller was reset during cranking of the gen set If this situation occurs the controller supposes the starting battery is so exhausted that its voltage drops so low when starter motor is energized that it causes...

Страница 585: ...ications AMF MRS Description This alarm indicates that the value of earth fault current is higher than adjusted limit The following setpoints are related to it Earth Fault Sd page 340 adjusts the maximum allowed earth fault current Earth Fault Delay page 339 adjusts the alarm delay Sd Earth Fault Current 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Fence 1 Alarm Alarm ...

Страница 586: ...ed applications AMF MRS Description This alarm will occur when the GCB FEEDBACK PAGE 455 input does not match the expected position given by the GCB CLOSE OPEN PAGE 495 output It stays active until the mismatch between the output and feedback persists If there was no command issued by the controller and the breaker feedback changes suddenly the position itself the alarm will be issued immediately ...

Страница 587: ...enerator Voltage Sd page 198 Generator Voltage Delay page 200 Sd Generator L1 Voltage 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator L1 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase voltage in phases 1 The following setpoints are related to it Generator Voltage BOC page 199 Gener...

Страница 588: ...lated applications AMF MRS Description This alarm evaluates the generator phase voltage in phase 2 The following setpoints are related to it Generator Voltage Sd page 198 Generator Voltage Delay page 200 Sd Generator L2 Voltage 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator L2 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Descripti...

Страница 589: ... Delay page 200 Sd Generator L2L3 Voltage 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase voltage in phase 3 The following setpoints are related to it Generator Voltage Sd page 198 Generator Voltage Delay page 200 Sd Generator L3 Vo...

Страница 590: ...escription This alarm evaluates the generator phase to phase voltage between phases 3 and 1 The following setpoints are related to it Generator Voltage BOC page 199 Generator Voltage Delay page 200 Sd Generator L3L1 Voltage 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator Frequency Alarm evaluated Generator excited only Related applications AMF MRS Description Th...

Страница 591: ... Unbalance BOC Delay page 200 adjusts the alarm delay Sd Generator Voltage Unbalance Ph Ph 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Generator Voltage Unbalance Ph N Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the unbalance of the phase voltage i e the difference between highest and lowest phase voltage at any...

Страница 592: ...ed has exceeded the limit The behavior of the overspeed alarm is adjusted by the following setpoints Overspeed Sd page 175 adjust the overspeed limit Overspeed Overshot page 176 adjust the additional overspeed limit Overspeed Overshot Period page 176 adjust the time period of additional overspeed limit Sd Overspeed 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd RPM Measu...

Страница 593: ...e number of attempts Sd Start Fail 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Underspeed Alarm evaluated Engine running only Related applications AMF MRS Description This alarm will be issued when the gen set is running and then stops by itself i e the RPM drops under the value of setpoint Starting RPM page 166 The underspeed alarm starts to be evaluated after succes...

Страница 594: ... BOC Current Unbalance 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Fence 1 Alarm Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates the GPS position of gen set The following setpoint are related to it Geo Fencing page 285 Fence 1 Protection page 286 Fence Radius 1 page 284 BOC Fence 1 Alarm 6 back to List of alarms level 2 Alarm Typ...

Страница 595: ...o List of alarms level 2 Alarm Type BOC Alarmlist message BOC Name of binary input Alarm evaluated All the time Related applications AMF MRS Description Binary input also can be adjusted like alarm In this case message in alarmlist contains prefix BOC and binary input name This alarm occurs when appropriate binary input is active BOC BIN Protection 1 48 6 back to List of alarms level 2 Alarm Type ...

Страница 596: ...escription This alarm evaluates the generator phase voltage in phases 2 The following setpoints are related to it Generator Voltage BOC page 199 Generator Voltage Delay page 200 BOC Generator L2 Voltage 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Generator L2L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the...

Страница 597: ...BOC Generator L3L1 Voltage 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Generator Frequency Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator frequency in the phase L1 The following setpoints are related to it Generator Frequency BOC page 201 Generator Frequency BOC Delay page 202 BOC Generator Frequency 6 ba...

Страница 598: ...t depends on how much is the protected value generator current in this case above the limit Nominal Current page 156 The higher is the overcurrent the shorter the reaction time will be All generator phases are evaluated The behaviour of the overcurrent alarm is adjusted by the following setpoints IDMT Overcurrent Delay page 196 defines the reaction time of the protection when the current is twice ...

Страница 599: ...this alarm Short Circuit BOC page 195 adjusts the short current limit Short Circuit BOC Delay page 195 adjusts the delay in fine steps BOC Short Circuit 6 back to List of alarms level 2 8 2 3 Fail sensor and other types Fls AIN Prot 601 Fls Coolant Temp 601 Fls Fuel Level 601 Fls Oil Pressure 601 For full list of Fails sensor and other types of alarms go to List of fail sensor alarms page 600 What...

Страница 600: ...List of fail sensor alarms Fls AIN Prot 601 Fls Coolant Temp 601 Fls Fuel Level 601 Fls Oil Pressure 601 InteliLite Global Guide 600 ...

Страница 601: ...ement value of coolant temperature is out of range or is missing Fls Coolant Temp 6 back to List of fail sensor alarms Alarm Type Fls Alarmlist message Fls Fuel Level Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs when measurement value of fuel level is out of range or is missing Fls Fuel Level 6 List of fail sensor alarms page 600 Alarm Type Fls Alarmlist ...

Страница 602: ...Ethernet The available extension plug in modules for the 3rd generation are EM BIO8 EFCP extension module with 8 binary inputs outputs and with earth fault current protection Note Controller has 2 plug in module slots Communication modules CM RS232 485 602 CM Ethernet 603 CM GPRS 605 CM 4G GPS 609 CM RS232 485 CM RS232 485 is optional plug in card to enable InteliLite the RS232 and RS485 communica...

Страница 603: ...ction with controller via LiteEdit2015 Go the menu Tools Firmware upgrade select the Plug in modules tab and select the appropriate firmware you want to program into the module in LiteEdit2015 Press the OK button to start upgrade of firmware The firmware update process may be performed via any kind of connection including connection via the same module in which the firmware is to be updated The co...

Страница 604: ... network The module can also be connected directly to a PC using cross wired UTP cable Image 9 18 Cross wired cable Module setup All settings related to the module are to be adjusted via the controller setpoints The respective setpoints are located in the setpoint Group CM Ethernet page 326 All actual operational values like actual IP address etc are available in controller values in a specific gr...

Страница 605: ...of firmware The firmware update process may be performed via any kind of connection including connection via the same module in which the firmware is to be updated The connection is reestablished again automatically when the update process is finished CM GPRS CM GPRS plug in module is a GSM GPRS modem which can works in two modes of operation based on the settings in the setpoint Mode page 314 Ima...

Страница 606: ... UserName blank Password blank Make sure SIM card does not require PIN code Use any mobile phone to switch the SIM PIN security off Place the SIM card into slot on CM GPRS card Connect the antenna to Cellular module antenna connector Switch off the controller Insert CM GPRS module into controller Power up the controller Select the mode of CM GPRS module by adjusting setpoint Mode Enter correct APN...

Страница 607: ... of analog modem 11 SIM card is locked Possibly PIN code required PIN needs to be deactivated or unknown status of SIM locking 12 No GSM signal 13 Not possible to read the SIM card parameters 14 GSM modem did not accepted particular initialization command possibly caused by locked SIM card 15 Unknown modem 16 Bad answer to complement initialization string 17 Not possible to read GSM signal strengt...

Страница 608: ...needed to indicate AirGate Diag Diagnostic Code for AirGate connection Code Description 0 Waiting for connection to AirGate Server 1 Controller registered waiting for authorization 2 Not possible to register controller blacklisted 3 Not possible to register server has no more capacity 4 Not possible to register other reason 5 Controller registered and authorized Firmware upgrade Download the newes...

Страница 609: ... SIM card by your mobile operator for successful operation CM 4G GPS module works with WebSupervisor internet based remote monitoring solution AirGate powerful connection technology to make internet access as simple as possible Locate Celluar network based localization service CM 4G GPS module also works like GPS locator Geo fencing function can be used with this module Supported 4G bands are as f...

Страница 610: ... want to use the built in GPS receiver connect also an active GPS antenna to the GPS antenna connector Switch off the controller Insert CM 4G GPS module into controller Power up the controller Select the mode of CM 4G GPS module by adjusting setpoint Mode Enter correct APN Name APN User Name and APN User Password in controller s setpoint group CM 4G GPS which is accessible by PAGE button from any ...

Страница 611: ...ialization of analog modem 11 SIM card is locked Possibly PIN code required PIN needs to be deactivated or unknown status of SIM locking 12 No GSM signal 13 Not possible to read the SIM card parameters 14 GSM modem did not accepted particular initialization command possibly caused by locked SIM card 15 Unknown modem 16 Bad answer to complement initialization string 17 Not possible to read GSM sign...

Страница 612: ...needed to indicate AirGate Diag Diagnostic Code for AirGate connection Code Description 0 Waiting for connection to AirGate Server 1 Controller registered waiting for authorization 2 Not possible to register controller blacklisted 3 Not possible to register server has no more capacity 4 Not possible to register other reason 5 Controller registered and authorized Firmware upgrade Download the newes...

Страница 613: ...CP EM BIO8 EFCP is optional plug in card Through this card controller can accommodate one AC current CT measuring input 1A or 5A input and up to 8 binary inputs or outputs In LiteEdit2015 PC configuration tool it is possible to easily choose if particular I O will be binary input or output Image 9 25 EM BIO8 EFCP interface IMPORTANT Any manipulation with plug in module shall be done with disconnec...

Страница 614: ... 9 26 Overview of EM BIO8 EFCP Image 9 27 EM BIO8 EFCP wiring EM BIO8 EFCP technical data Power supply range 8 36 VDC Power supply Number Up to 8 non isolated Close Open indication 0 2 VDC close contact 6 VDC open contact Binary inputs ...

Страница 615: ...ay page 339 time elapses the Earth Fault Current Protection page 338 Sd Earth Fault Current page 585 alarm and AL EARTH FAULT PAGE 469 output are activated Earth Fault protection is not active when gen set does not run and when the Earth Fault Current Protection page 338 is disabled IMPORTANT Earth fault current measurement is not intended to protect human health but the machines Image 9 28 Earth ...

Страница 616: ...nsion CAN module with 8 binary inputs 8 binary outputs and 2 analog outputs this CAN module can be switched to Inteli IO 16 0 extension CAN module with 16 binary inputs and 2 analog outputs Maximal number of CAN modules is 2 Modules are configured via LiteEdit2015 There are 2 slots for CAN modules Note I LB communication module is not configured via LiteEdit2015 into controller CAN module slot Als...

Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...

Страница 618: ...luded CAN terminating resistor 120 ohm Close jumper P1 to connect terminating resistor to CAN bus open jumper P1 to disconnect terminating resistor RS232 or RS485 termination P2 I LB has included RS232 RS485 terminating resistor 120 ohm Close jumper P2 to connect terminating resistor to RS232 RS485 bus open jumper P2 to disconnect terminating resistor Select RS mode P3 Jumper P3 selecting RS mode ...

Страница 619: ...umper connects bias resistor to the line A P20 or B P21 USB interface enable disable P8 Jumper P8 has to be set to enable USB interface Opened jumper disables USB interface disabled USB doesn t occupies a communication channel on the CAN bus i e there are still 3 free communications channels on the CAN bus USB interface allows only local communication modbus is not implemented in this interface Ju...

Страница 620: ... Unit s power supply is according manual BOOT jumper is set on try again from point 3 10 After successful programming disconnect the power supply from the unit and remove the BOOT jumper 11 Assemble the unit again 12 Module FW is upgraded LED indication LED Description State State RxC No data are received on the CAN line Dark Data are received on the CAN line Blink TxC No data are transmitted on t...

Страница 621: ...modem via standard modem cable full RS232 where the DSR Data Set Ready signal detects modem presence when MODEM HW type selected Three wire RS232 cable TxD RxD GND can be used e g for GSM modems when MODEM SW type is selected Technical data Power supply 8 to 36 V DC Current consumption 100 mA at 24 V Interface to controller CAN2 Interface to modem or PC RS232 RS485 USB Storage temperature 40 C to ...

Страница 622: ...nteli AIN8 Image 9 32 Inteli AIN8 dimensions Note All dimensions are in mm Analog inputs 8 channels can be configured as resistor three wire input current input voltage input All inputs can be configured to any logical function or protection ...

Страница 623: ...e group of signals is deactivated Programming firmware Firmware upgrade process 1 Disconnect all terminals from the unit 2 Separate the top cover of module 3 Put the TEST jumper on a pins 4 Connect the unit with PC via RS232 null modem cable and AT Link conv 5 Connect power supply of the module status LED lights continuously 6 Launch FlashPgr exe PC software version 4 2 or higher 7 In FlashPrg pro...

Страница 624: ... LED indication LED status Description Dark Fw in module does not work correctly Flashing Module does not communicate with controller in case non zero CAN address Lights Power supply is in the range and the communication between Inteli AIN8 and controller works properly Or power supply is in range and zero CAN address is set in case zero CAN address module doesn t communicate with the controller W...

Страница 625: ...InteliLite Global Guide 625 Resistance sensor 2 wires Ranges Pt100 Pt1000 Ni100 Ni1000 0 250 Ω 0 2400 Ω 0 10 kΩ Current sensor active Ranges 20 mA 4 20 mA Current sensor passive Ranges 0 20 mA 4 20 mA ...

Страница 626: ...8 Voltage Range 0 10 V Accuracy 0 25 of actual value 25 mV Current Range 20 mA Accuracy 0 25 of actual value 50 µA Resistive Range 0 10 kΩ Accuracy resistance 0 5 of actual value 2 Ω Analog inputs Inteli IO8 8 Inteli IO8 8 module is an extension module equipped with binary inputs binary outputs and analog outputs Inteli IO8 8 is the name of the module but it is possible to configure the module by ...

Страница 627: ... 9 34 Inteli IO8 8 dimensions Note All dimensions are in mm Inputs and outputs Binary inputs 8 channels can be configured as pull up pull down All 8 inputs are configured to one type together All inputs can be configured to any logical function or protection ...

Страница 628: ...state history record and alarm are issued type of the alarm is set by Protection upon module failure No protection Warning Shutdown This function is designed for short circuit or other failure which causes change of set state of binary output CAN address In Inteli IO8 8 mode CAN address for binary inputs is determined by DIP switch A CAN address for binary output and analog outputs is determined b...

Страница 629: ...orrect Module has power supply no CAN bus connection status LED lights continuously 10 After successful programming disconnect AT Link conv remove TEST jumper and disconnect power supply 11 Connect power supply again status LED should blinking 12 Module FW is upgraded LED indication Binary input Each binary input has LED which indicates input signal LED is shining when input signal is set and LED ...

Страница 630: ...ing The following diagrams show the correct connection of inputs and outputs Binary inputs pull up There are two options of wiring On upper picture you can see case when binary input is connected between BIN2 and COM COM is connected internally to the GND dashed line On lower picture is case of wiring between BIN2 and GND Both ways are correct Binary inputs pull down There are two options of wirin...

Страница 631: ...utputs low side When low side setting of outputs is chosen binary output must be connected to the plus potential of power supply directly Minus potential is connected internally dashed line Analog outputs Limit of analog ground AGND is 100mA IMPORTANT Terminator for analog output has special analog ground AGND which must not be connected to the GND Technical data Power supply 8 to 36 V DC Current ...

Страница 632: ...al value Rmax 500 Ω PWM Level 5 V Frequency adjustable 200 2400 Hz Imax 20 mA Analog outputs Number of channels 8 for Inteli IO8 8 16 for Inteli IO 16 0 Input resistance 4400 Ω Input range 0 to 36 V DC Switching voltage level for open contact indication 0 to 2 V DC Max voltage level for close contact indication 6 to 36 V DC Binary inputs Number of channels 8 for Inteli IO8 8 0 for Inteli IO 16 0 M...