InteliLite Global Guide
556
PLC group
Time functions
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
33
Inputs
Input
Type
Negation
Range
Function
Input
Binary
No
0/1
Input signal to be delayed
Input time
up
Analog
No
-3200,0..3200,0 [s,
m, h]
Delay of the rising edge resp. pulse
length generated by rising edge of the
input
Input time
down
Analog
No
-3200,0..3200,0 [s,
m, h]
Delay of the falling edge resp. pulse
length generated by falling edge of the
input
Input reset
Binary
No
0/1
Resets the output to logical 0. The
output remains in logical 0 until new
rising edge appears on Input (when
Input reset is deactivated already)
Outputs
Output
Type
Negation
Range
Function
Output
Binary
No
0/1
Output signal
Description
This block can work in two modes of operation:
Delay mode - the rising edge at the output is generated with delay of "input time up" when a rising
edge at the input is detected. The falling edge at the output is generated with delay of "input time
down" when a falling edge at the input is detected. If the delayed falling edge at the output came
earlier than the delayed rising edge, then no pulse would be generated at the output.
Pulse mode - a pulse of "input time up" length is generated at the output when a rising edge is
detected, a pulse of "input time down" length is generated at the output when a falling edge is
detected.
Delay
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...