InteliLite Global Guide
280
Setpoint group
Scheduler
Related FW
1.2.1
Range [units]
Disabled / 1..
[h]
Default value
Disabled
Alternative config
NO
Step
1 h
Comm object
14332
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Alarm
comes up after xx running hours from adjusting the
. Hours are adjusted by this setpoint.
Image 8.61 Rental Timer 1 Wrn
Rental Timer 1 Wrn
Setpoint group
Scheduler
Related FW
1.2.1
Range [units]
[DD/MM/YYYY]
Default value
01/01/2015
Alternative config
NO
Step
1 day
Comm object
14367
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Another engine start is not allowed when this timer elapsed. This timer is based on date. At the midnight of
the last day the alarm
Rental Timer 2 Elapsed (page 566)
will be recorded in alarm list and the binary
output
will close.
IMPORTANT: To reset
we have to set up
again. It means go to setpoint group Scheduler and to the setpoint
Then press enter button
, change the value if it is necessary and press enter button
again.
IMPORTANT: To disable
set date to 01/01/2015.
Rental Timer 2
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...