InteliLite Global Guide
453
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
40
Description
The shutdown procedure will start immediately when this input is activated. Input is inverted (NC = normaly
closed) in default configuration.
Note:
In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured.
To back-up the Emergency Stop function it is recommended to connect separate circuit for
disconnection of Fuel Solenoid and Starter signals.
For more detail see chapter
recommended wiring.
Emergency Stop
back to Logical binary inputs alphabetically
LBI: F
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
191
Description
Binary input has the same function as Fault Reset button
on the InteliLite front panel.
Fault Reset Button
back to Logical binary inputs alphabetically
Related FW
1.2.1
Related applications
AMF, MRS
Comm object
680
Description
When this binary input is activated, the controller send request for force regeneration of DPF (diesel
particulate filter) to ECU.
Note:
ECU with Tier IV support is required for proper functionality.
Force Regeneration
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...