InteliLite Global Guide
144
Modbus TCP examples
Reading of Battery voltage
Export table of values from LiteEdit
Table: Values
Allowed MODBUS functions: 03, 04
Register(s)
Com.Obj.
Name
Dimension
Type
Len
Dec
Min
Max
Group
01053
8213
BatteryVoltage
V
Integer
2
1
0
400
Controller
I/O
Request: (Numbers in Hex)
00
00
00
00
00
06
01
03
04
1D
00
01
transaction
identifier
(usually 0)
protocol
identifier
(usually 0)
Length of
data bytes
following
Controller
address
Modbus
function
Register address
041D
hex
=
1053
dec
Number of
registers
Request: (Numbers in Hex)
00
00
00
00
00
06
01
03
04
1D
00
01
transaction
identifier
(usually 0)
protocol
identifier
(usually 0)
Length of
data bytes
following
Controller
address
Modbus
function
Register address
041D
hex
=
1053
dec
Number of
registers
Response: (Numbers in Hex)
00
00
00
00
00
05
01
03
02
00
F0
transaction
identifier
(usually 0)
protocol
identifier
(usually 0)
Length of
data bytes
following
Controller
address
Modbus
function
Length of data
02
hex
= 2 bytes
read
Data
00F0
hex
=
240
dec
We read value 240 from register 01053. From table of modbus registers we get dimension of read value and
"Dec". Dec=1 means shift one decimal place to the right. So battery voltage is
24.0 V
.
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...