InteliLite Global Guide
159
Setpoint group
Basic settings
Related FW
1.2.1
Range [units]
80 .. 40 000 [V]
Default value
400 V
Alternative config
YES
Step
1 V
Comm object
11657
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
.
Description
Nominal system (generator) voltage (phase to phase).
Note:
To lock this setpoint against editing you also have to lock setpoint
and
Nominal Voltage Ph-Ph 2 (page 294)
Nominal Voltage Ph-Ph
Setpoint group
Basic settings
Related FW
1.2.1
Range [units]
0,1 .. 500,0 [V/V]
Default value
1,0 V/V
Alternative config
NO
Step
0,1 V/V
Comm object
9579
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Generator voltage potential transformers ratio. If no PTs are used, adjust the setpoint to 1.
PT Ratio
Subgroup: Frequency settings
Setpoint group
Basic settings
Related FW
1.2.1
Range [units]
45 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
8278
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal system (generator) frequency (usually 50 or 60Hz).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Frequency 1 (page 291)
and
Nominal Frequency 2 (page 293)
.
Nominal Frequency
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...