16
Factory default is set as (
1
) 1 Hour. When
the
Off-Set time
is reset in programming
Mode, the time of the Off-Set period will
recalculate.
Off-Set time Report will be sent only once,
and then the Control Panel sends Check-in
Report according to setting of period test
call, unless the Control Panel restarts or
the Off-Set time is reset.
Command 49
Supervision
This option is used to enable system
supervision function. Once enabled,
SUPER 32-DT35A will be able to receive
the check-in signals from Wrist Pendants
(WTR-)
to
indicate
their
proper
functioning.
Function
Selection
Result
(0)
Disable
(1)
4 Days
(2)
5 Days
(3)
6 Days
(4)
7 Days
(5)
8 Days
(6)
9 Days
Factory default is set as (
0
)
Disable
. No
code is sent to Monitoring Centers.
When the supervisory timer expires and no
supervision signal is received from WTR-,
the supervisory alarm reporting will be
made.
The reporting method for supervisory alarm
is the same as the emergency alarm. The
report will be sent based on your reporting
methods without guard time waiting.
Command 53
Voice Prompt Language
This command is used to set voice prompt
language.
0=English,1=Spanish, 2=Russian, 3= Arabic
Factory default is set as (
0
) English.
Command 55
High Temperature Reporting
This command is used to program the
High Temperature Reporting threshold in
degrees Celsius.
When temperature reaches or exceeds
the High Temperature threshold, SUPER
32-DT35A will report High Temperature
Alarm to CMS.
Function
Selection
Result
(000)
0 °C
(001)-(999)
0.1-99.9 °C
Factory Default is set as
(350)
,
35.0°C
.
Command 56
Low Temperature Reporting
This command is used to program the Low
Temperature Reporting threshold in
degrees Celsius.
When temperature reaches or drops
below the Low Temperature threshold,
SUPER 32-DT35A will report Low
Temperature Alarm to CMS.
Function
Selection
Result
(000)
0 °C
(001)-(999)
0.1-99.9 °C
Factory Default is set as
(080)
,
8°C
.
Command 57
CO2 Alarm Reporting
This command is used to program the
CO2 Alarm Reporting threshold.
When CO2 concentration value reaches or
exceeds the Alarm Reporting threshold,
SUPER 32-DT35A will report CO2 Alarm
to CMS.