Section 14. Troubleshooting Guide
Possible reason
: Two network devices have the same PakBus
Address.
Remedy
: Change one of the duplicate PakBus Addresses. Make all
addresses unique throughout the network.
Problem
: In P193 network, certain CR200 Series devices don’t transfer data.
Possible reason
: The Master datalogger’s *D15 setting configures
too few max nodes, max neighbors, and max routers.
Remedy
: Change Master *D15 settings for max nodes, max
neighbors, and max routers to larger numbers reflecting the network
size.
*D15 settings allocate memory similar to *A. It is a good idea, when
configuring *D15 settings, to leave ‘room to grow.’ Changing *D15
settings later on could result in loss of data.
14-19
Содержание LoggerNet
Страница 2: ......
Страница 30: ...Preface What s New in LoggerNet 4 xxvi...
Страница 32: ...Section 1 System Requirements 1 2...
Страница 44: ...Section 2 Installation Operation and Backup Procedures 2 12...
Страница 136: ...Section 4 Setting up Datalogger Networks 4 80...
Страница 227: ...Section 7 Creating and Editing Datalogger Programs 7 9...
Страница 298: ...Section 7 Creating and Editing Datalogger Programs 7 80...
Страница 402: ...Section 9 Automating Tasks with Task Master 9 12...
Страница 406: ...Section 9 Automating Tasks with Task Master 9 16...
Страница 450: ...Section 11 Utilities Installed with LoggerNet Admin and LoggerNet Remote 11 22...
Страница 454: ...Section 12 Optional Client Applications Available for LoggerNet 12 4...
Страница 462: ...Section 13 Implementing Advanced Communications Links 13 8...
Страница 482: ...Section 14 Troubleshooting Guide 14 20...
Страница 570: ...Appendix F Calibration and Zeroing F 16...
Страница 578: ...Appendix G Importing Files into Excel G 8...
Страница 579: ......