RM2000 Series Installation and Configuration Guide
38
RM2000 Series Configuration
5
Scale the input channel and input device as follows:
a
Type the minimum and maximum voltage level supported by the
input channel in the top and bottom fields of
Raw voltage values (on
unit input)
, respectively.
For example, to set up the input channel for pipe-to-soil readings, type
–5
in the top text box and
5
in the bottom text box.
b
Type the minimum and maximum voltage level supported by the
input device in the top and bottom fields of
Engineering Units (on
transducer)
, respectively.
For example, to set up the input channel for pipe-to-soil readings, type
–5
in the top text box and
5
in the bottom text box.
6
If you want to apply an optional response filter to the input channel, click
the
Response Filter Time
button and select a time option.
7
If you want the unit to transmit an alarm packet when a low alarm
condition occurs, click
Transmit Low Alarm
and then type a value in the
Low Alarm
field.
The unit transmits an alarm packet when the input channel reading is
lower than the value entered in the
Low Alarm
field.
8
If you want the unit to continue transmitting low alarms until the alarm
condition is removed in the field, click
Repeat Low Alarm
and then type a
value in the
Repeat delay in minutes
field.
9
If you want the unit to transmit an alarm packet when a high alarm
condition occurs, click
Transmit High Alarm
and then type a value in the
High Alarm
field.
The unit transmits an alarm packet when the input channel reading is
higher than the value entered in the
High Alarm
field.
10
If you want to include deadband in low and/or high alarms, type a value
in the low and/or high alarm
Deadband
fields.
Valid entries are any positive scaled value that does not cause the alarm
point to be lower than the minimum scale value or higher than the
maximum scale value in
Engineering Units (on transducer)
. Entering zero
disables deadband.
11
If you want to apply a persistence filter to low and/or high alarms, type a
value in the Persistence field. Valid entries are any number from 1 to 65535.
Entering zero (0) disables persistence.
Содержание RM2000 Series
Страница 1: ...RM2000 Series Installation and Configuration Guide...
Страница 2: ......
Страница 8: ...RM2000 Series Installation and Configuration Guide iv...
Страница 20: ...RM2000 Series Installation and Configuration Guide 12 Getting Started...
Страница 36: ...RM2000 Series Installation and Configuration Guide 28 RM2020 Installation...
Страница 54: ...RM2000 Series Installation and Configuration Guide 46 RM2000 Series Configuration...
Страница 62: ...RM2000 Series Installation and Configuration Guide 54 Battery Replacement...
Страница 64: ...RM2000 Series Installation and Configuration Guide 56 Regulatory Notices...
Страница 76: ...RM2000 Series Installation and Configuration Guide 68 Glossary...
Страница 80: ...RM2000 Series Installation and Configuration Guide 72 Index...
Страница 81: ......