1
General safety instructions and explanation of symbols
Logano plus GB312 - Technical specifications are subject to change without prior notice
4
1
General safety instructions and explanation of symbols
1.1
Safety instructions
If you smell gas
V
Turn off the gas valve (
Æ
page 55).
V
Open windows and doors.
V
Do not operate any electrical switches or equipment
such as telephones, power plugs and doorbells.
V
Extinguish all open flames. Do not smoke. Do not use
lighters of any kind.
V
Warn all occupants of the building, but do not ring
doorbells.
V
If you can actually hear gas escaping, leave the building
immediately. Prevent others from entering and notify
the police and fire department
from outside
the build-
ing.
V
From outside the building,
call gas supplier and
approved heating contractor.
If you smell flue gas
V
Switch "off" the boiler (
Æ
page 55).
V
Open windows and doors.
V
Inform an authorized heating contractor.
Risk of poisoning. An insufficient supply of air can
result in dangerous escape of flue gas.
V
Never close off or reduce the size of air inlet or outlet
vents.
V
The boiler must not be operated until the obstruction
has been removed.
V
Inform the system operator in writing of the problem
and associated danger.
Danger from escaping flue gases.
V
Make sure that the flue pipes and seals are not dam-
aged.
V
Use high temperature silicon as sealing compound.
V
The boiler must not be fitted with a barometric damper
or a thermally controlled flue flap downstream of the
flue socket.
V
Connect only one boiler to each flue system or chimney
flue.
V
Connection of another boiler may cause serious injury
or death.
V
The flue system piping must not feed into another air
extraction duct.
V
Do not route the flue system piping through or inside
another air extraction duct, for example where there is
a masonry or prefabricated chimney flue.
Danger of explosion of flammable gases.
V
Any work on components that carry gas may only be
carried out by an approved heating contractor.
Dangers posed by explosive and easily combusti-
ble materials
V
Do not use or store easily combustible materials
(paper, lace curtains, clothing, thinners, paints, etc.)
near the boiler.
V
Maintain a clearance of 16 inches from the boiler.
Combustion air
V
Keep the combustion air free of corrosive substances
(e.g. halogenated hydrocarbons that contain chlorine
or fluorine compounds). In that way you will prevent
corrosion.
Danger from electric current when the boiler is
open.
V
Before opening the boiler: Disconnect the heating sys-
tem from the electrical power supply by means of the
emergency stop switch or the relevant circuit breaker
on the main fuse board.
V
It is not sufficient just to switch off the control unit.
V
Take measures to ensure the heating system can not
be switched on again unintentionally.
Danger due to short-circuits
To prevent short circuits, only
V
use genuine Buderus wiring replacement parts.
Installation and adjustment
V
Correct and proper installation and adjustment of the
burner and the programmer are the fundamental
requirements for safe and economical operation of the
boiler.
V
The boiler may only be installed by an approved heating
contractor.
V
Do not modify any parts that carry flue gas.
V
Work on gas components may only be carried out by
qualified and authorized personnel.
V
Only qualified electricians are permitted to carry out
electrical work. Installation regulations must be com-
plied with.
V
With
balanced flue appliances:
do not cover or
reduce the size of ventilation openings in doors, win-
dows and walls. If draft-proof windows are fitted,
ensure there is an adequate supply of air to the room
for combustion.
V
Never shut off safety valves.
Water may escape
from the safety valve for the hot water system and pip-
ing when the water is being heated.
Содержание Logano plus GB312
Страница 121: ...Logano plus GB312 Technical specifications are subject to change without prior notice 121 Notes ...
Страница 122: ...Logano plus GB312 Technical specifications are subject to change without prior notice 122 Notes ...
Страница 123: ...Logano plus GB312 Technical specifications are subject to change without prior notice 123 Notes ...