6
Installing the boiler
Logano plus GB312 - Technical specifications are subject to change without prior notice
25
6.3
Installing the wall exit for a horizon-
tal flue
Please carefully read the following instructions and infor-
mation on the installation of the wall exit and make sure
you observe the safety instructions.
The wall exit must be installed in accordance with the
specified regulations and/or local building code regula-
tions.
Fig. 12 Specified clearances to ANSI Z223.1 for hori-
zontal flues
1
Flue wall exit
2
Air intake wall exit
A
Minimum horizontal distance from air intake of another
appliance = 10 ft, minimum distance from own air intake
for directly vented appliances = 4 ft.
B
Minimum vertical distance from air intake of another appli-
ance = 3 ft, with directly vented appliances the flue outlet
can be positioned level with the appliance's own air intake
(observe minimum horizontal separation of 4 ft).
Fig. 13 Wall penetration
1
Wall penetration
2
Flue pipe
3
End piece of flue pipe (t-piece or 90°-elbow)
4
External cover plate
All instructions issued by the flue system
manufacturer concerned regarding the fitting
of the wall exit must be followed. Use only
those that are required for the flue pipe diam-
eter. The use of a T-piece or a 90°-elbow as
the external terminal for the flue pipe is re-
quired.
12 in.
min.
12 in.
min.
4 ft.
min.
B
A
4 ft.
min.
2
1
3
1
2
3
4
7 747 010 720-13.1RS