10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
79
V
6C
576
Ionization current
> 0.9 μA during pre-
ventilation.
No flame signal
was detected
within the preventi-
lation phase.
Check ionization
electrode.
Make sure that metal
fibers of propane
burner are not in
contact with with
electrodes.
Check function of
gas valve.
Check ionization
electrode gap.
Replace ionization
electrode.
Replace gas valve.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code