7
Recommissioning the heating system
Logano plus GB312 - Technical specifications are subject to change without prior notice
48
7.11 Adjusting and checking CO
2
level at maximum output
V
Read off output on RC35 or using Service Key.
V
Wait until output reaches at least 70%.
V
Insert the sensor through a testing hole in the flue pipe
(
Æ
Fig. 47, page 49) into the centre of the gas flow.
V
Measure the pressure in the flue using a suitable pres-
sure tester (for location of testing point, see Fig. 47,
page 49).
7.11.1 CO
2
content, natural gas type A
If CO
2
content is below 8.5%.
V
Adjust the level to 9.1% CO
2
using the high-output
adjusting screw.
– Turning the screw clockwise reduces the CO
2
level.
– Turning the screw counter-clockwise increases the
CO
2
level.
Fig. 44 Checking the CO
2
setting at maximum output
1
High-output adjusting screw
7.12 Adjusting and checking CO
2
level at minimum output
V
Set to 30%.
V
To do so, press and hold the
button until the dec-
imal point on the status display
lights up
(at least 2
seconds).
This turns on the flue gas test.
V
Simultaneously press and hold the
and
but-
tons for approx. 5 seconds.
At the factory setting, the display shows "
".
V
Press the
button to reduce the boiler output to a
percentage of maximum until the display shows
"
".
V
Read off output on RC35 or using a Service Key.
V
Wait until the output drops to 30%.
Fig. 45 Setting medium output
Boiler rating
Gas orifice diameter for natural gas (gas type
A), calorific value 1075 Btu/ft
3
90-4
17
120-4
17
160-5
17
200-6
17
240-7
17
280-8
17
Tab. 13 Gas injector diameter
7 747 010 720-52.2RS
1
7 747 010 720-42.2RS
90
130
100
120
110
Eco
140
Aut
90
110
130
150
170
190
Aut
Содержание Logano plus GB312
Страница 121: ...Logano plus GB312 Technical specifications are subject to change without prior notice 121 Notes ...
Страница 122: ...Logano plus GB312 Technical specifications are subject to change without prior notice 122 Notes ...
Страница 123: ...Logano plus GB312 Technical specifications are subject to change without prior notice 123 Notes ...