10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
85
V
CY
573
Flow temperature
< 23 °F (< -5 °C) (cir-
cuit break)
Control unit is
receiving implausi-
ble signals from
flow temperature
sensor.
Check connecting
lead between SAFe
and return sensor.
Check electrical
connection of con-
necting lead to
SAFe.
Check resistance
levels of tempera-
ture sensor against
table
Check voltage at
temperature sensor
terminals on SAFe
against table
Replace connect-
ing lead if neces-
sary
Rectify any contact
problems
Replace tempera-
ture sensor if nec-
essary
If temperature sen-
sor resistances are
correct but volt-
ages incorrect,
replace SAFe
V
CY
574
Flow temperature
>266°F (>130°C)
(short circuit)
Control unit is
receiving implausi-
ble signals from
flow temperature
sensor.
Check connecting
lead between SAFe
and return sensor.
Check electrical
connection of con-
necting lead to
SAFe.
Check resistance
levels of tempera-
ture sensor against
table
Check voltage at
temperature sensor
terminals on SAFe
against table
Replace connect-
ing lead if neces-
sary
Rectify any contact
problems
Replace tempera-
ture sensor if nec-
essary
If temperature sen-
sor resistances are
correct but volt-
ages incorrect,
replace SAFe
V
LP
570
Too many resets via
the interface.
Too many resets
have been received
via the interface
within a certain
period.
Important: this fault
can only be reset
by the button on
the SAFe.
Faults have continu-
ally been simply
reset and not recti-
fied.
There is a fault on
the BC10 causing
continual resets.
There is a malfunc-
tion on the SAFe.
Identify and elimi-
nate the cause of
the problem caus-
ing the resets.
Replace BC10.
Replace SAFe.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Содержание Logano plus GB312
Страница 121: ...Logano plus GB312 Technical specifications are subject to change without prior notice 121 Notes ...
Страница 122: ...Logano plus GB312 Technical specifications are subject to change without prior notice 122 Notes ...
Страница 123: ...Logano plus GB312 Technical specifications are subject to change without prior notice 123 Notes ...