10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
90
Fault 8Y/591 (locking)
Cause:
Error checking safety assembly.
Description:
SAFe pressure switch has not responded
during safety check.
Fig. 71 Fault elimination sequence 8Y/591
7 747 010 720-58.4RS
yes
no
Perform reset!
Perform reset!
yes
no
Is the required gas supply
pressure of > 3.5 inches w.c.
present?
Perform reset!
Eliminate cause!
Check setting of SAFe
pressure switch
(should be 3 inches w.c.)!
Is pressure
switch setting
correct?
Adjust setting
to 3 inches w.c.
Does MV1 (see LED of the gas
valve) open before error
message?
Check gas
valve connector
is in proper contact.
no
Perform reset!
Perform reset!
Does burner start up?
no
Replace SAFe
pressure switch.
Does burner start up?
Perform reset!
no
Replace SAFe!