10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
76
V
4U
521
Temperature differ-
ence at twin boiler
sensor too great.
Temperature differ-
ence between flow
temperature sen-
sors 1 and 2 too
great (divergence
of > 9 °F/2s; 5 K/
2s).
Check connectors
on boiler sensor and
SAFe for dirt/dam-
age.
Check boiler sensor
resistance against
sensor characteris-
tic/visually check
temperature sensor.
Check boiler sensor
voltage levels
against table (SAFe
documentation).
Clean contacts/
replace connecting
lead if necessary.
If there are discrep-
ancies in the sensor
readings or the
connector is defec-
tive, the tempera-
ture sensor must be
replaced.
Replace SAFe if
there are discrep-
ancies.
V
4U
522
Short circuit between
boiler sensors 1 and
2.
A fault has been
detected in temper-
ature sensor test
mode.
Check sensor lead.
Check connector.
Check sensor read-
ings against sensor
characteristic.
Check temperature
sensor voltage levels
against table (SAFe
documentation).
Replace if dam-
aged.
If dirty, clean or
replace as neces-
sary.
If connector is
loose, reconnect
properly.
Replace tempera-
ture sensor if there
are discrepancies.
Replace SAFe if
there are discrep-
ancies.
V
4Y
523
Circuit break on flow
temperature sensor.
Temperature at flow
temperature sen-
sor.
< 23 °F (< -5 °C)
Check sensor lead.
Check connector.
Check sensor read-
ings against sensor
characteristic.
Check temperature
sensor voltage levels
against table (SAFe
documentation).
Replace if dam-
aged.
If dirty, clean or
replace as neces-
sary.
If connector is
loose, reconnect
properly.
Replace tempera-
ture sensor if there
are discrepancies.
Replace SAFe if
there are discrep-
ancies.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code