9
Heating system servicing
Logano plus GB312 - Technical specifications are subject to change without prior notice
60
Conducting a flue gas test
The
button is used by the heating engineer for the
flue gas test.
The control system runs the heating at a raised flow tem-
perature for 30 minutes. During the flue gas test, the dec-
imal point on the status display lights up.
V
Press and hold the
button until the decimal point
on the status display lights up (at least 2 seconds).
V
Conduct the flue gas test.
V
Cancel the flue gas test and press the
button
again.
Fig. 55 Starting the flue gas test
Opening the Service menu on the RC35
V
Simultaneously
press
the + +
buttons
to
open the
SERVICE MENU
.
V
Turn the rotary selector
counter-clockwise to
select
Diagnosis
(indicated by
).
V
Press the
button to open the
SERVICE/DIAG-
NOSIS
menu.
V
Turn the rotary selector
counter-clockwise to
select
Monitor reading
(indicated by
).
V
Press the
button to open the
DIAGNOSIS/
MONITOR READING
menu.
V
Turn the rotary selector
counter-clockwise to
select
Boiler/Burner
(indicated by
).
7 747 010 720-39.1RS
90
130
100
120
110
Eco
140
Aut
90
110
130
150
170
190
Aut
A PC running the Buderus Logamatic ECO-
Soft 4000/EMS software together with a ser-
vice key can also be used as a monitoring de-
vice. Please contact Buderus for more
detailed information.
SERVICE MENU
quick operation
B
settings
diagnosis
servicing
SERVICE|DIAGNOSIS
function test
monitor reading
diagnosis
servicing
B
DIAGNOSIS|MON.READING
Boiler/Burner
domestic hot water
heating circuit 1
bus users
B