2
Details of the product
Logano plus GB312 - Technical specifications are subject to change without prior notice
14
Fig. 4
Primary circuit flow resistance, GB312 with check valve
x
Flow rate in gal/min (GPM)
y
Primary pressure drop in psi
The boiler is factory-set for:
– Natural gas (gas type A)
0,1
1
10
100
1
10
100
1000
x
y
90-4
120-4
160-5
200-6
240-7
280-8
7 747 010 720-30.1RS
Boiler rating
Gas flow rate
Natural gas (gas type A)
Calorific value 1075 BTU/ft
3
cu ft/hr
90 - 4
324.6
120 - 4
434.4
160 - 5
579.0
200 - 6
720.6
240 - 7
868.8
280 - 8
1013.4
Tab. 3
Gas flow rate (based on gas temperature of 60
°F and air pressure of 30 ins Hg)
Содержание Logano plus GB312