64
Wet cleaning the heat exchanger
For wet cleaning use a cleaning agent appropriate for the
degree of soiling (soot or scale). The cleaning agent must
be approved for use with aluminium.
V
Screw the cleaning covers back in place.
V
Clean the heat exchanger with water or an Aluminum
approved cleaning agent (see instructions provided by
the manufacturer of the cleaning agent).
Fig. 61 Wet cleaning the heat exchanger
Operations required on the heat exchanger when wet or dry cleaning
V
Use a hose to flush any dirt residues into the bucket.
V
Clean the trap with water.
V
Refit the trap.
Fig. 62 Cleaning the trap
Cleaning the burner
V
Blow-clean the burner rods and manifold from inside
and outside with compressed air.
Fig. 63 Cleaning the burner
1
Burner rods
Warning:
Risk of fatal injury from escaping
flue gases.
V
When refitting the cleaning covers, check
that the seals are not damaged and the
cover is seated correctly.
Protect electrical components from moisture.
7 747 010 720-31.1RS
Warning:
Risk of fatal injury from poisoning.
If the trap is not filled with water, escaping
flue gas can place lives at risk.
V
Fill the trap with approx. 0.3 gallons of wa-
ter.
7 747 010 720 70 1RS
7 747 010 720-72.1RS