7
Recommissioning the heating system
Logano plus GB312 - Technical specifications are subject to change without prior notice
44
7.4
Checking the air supply/ventilation
and flue pipe connection
V
Check that the air supply/outlet vents comply with the
local regulations and/or gas installation requirements.
V
Check that the flue pipe connection complies with the
applicable regulations (
Æ
Section 6.8, page 28).
V
Check that the flue pressure does not exceed the avail-
able pressure of 0.4 inches W.C. (100 Pa).
7.5
Checking the air inlet diaphragm
V
Check that the air inlet diaphragm on the air inlet
socket is present and in contact with the pipe.
V
Check that the air inlet diaphragm on the air inlet
socket is able to move and is not sticking to the pipe.
Fig. 39 Checking the air inlet diaphragm
1
Air inlet diaphragm
2
Air inlet socket
3
High gas pressure switch (available separately)
4
Low gas pressure switch (available separately)
Danger:
Risk of fatal injury from poisoning.
Insufficient ventilation may cause dangerous
flue gas leaks.
V
Never close off or reduce the size of air in-
let or outlet vents.
V
The boiler must not be operated until the
obstruction has been removed.
V
Inform the system operator in writing of
the problem and associated danger.
7 747 010 720-53.3RS
2
4
3
1