2.10.2 Specifications
Connection ST (B-kit)
¾" NPT
1" NPT
Diameter GAS
1" NPT
1 ¼" NPT
Boiler size (output - no. of heat exchanger
sections)
Unit
90 - 4
120 - 4
160 - 5
200 - 6
240 - 7
280 - 8
Tab. 1
Dimensions and connection sizes
Observe all standards and guidelines appli-
cable to the installation and operation of the
heating system in your country. The informa-
tion on the boiler rating plate is definitive and
it is imperative that it is observed.
Boiler size (output - no. of heat exchanger sec-
tions)
Unit
90 - 4
120 - 4
160 - 5
200 - 6
240 - 7
280 - 8
Natural gas (gas type A)
I-B-R Input
max. load
Btu/hr
328,300
440,500
588,300
732,600
880,700
1,028,800
min. load
Btu/hr
132,200
132,200
176,500
219,800
264,200
308,600
I-B-R gross output 180/80 ° F
max. load
Btu/hr
305,000
409,000
544,000
676,000
810,000
944,000
I-B-R net rating 180/80 ° F
max. load
Btu/hr
265,000
356,000
473,000
588,000
704,000
821,000
Rated heat ouput 122/86 ° F
max. load
Btu/hr
307,100
409,500
545,900
682,400
819,000
955,400
(50/30 ° C)
min. load
Btu/hr
128,100
127,400
171,200
212,300
255,200
298,100
Flue gas mass flow rate 180/80 ° F
max. load
lb/min
4.85
6.53
9.14
11.40
13.88
16.15
Flue gas mass flow rate 122/86 ° F
max. load
lb/min
5.05
7.12
9.29
11.61
14.02
16.65
Flue gas temperature 180/80 ° F
max. load
° F
83
90
127
138
140
134
Flue gas temperature 122/86 ° F
max. load
° F
120
133
129
131
131
135
CO2 content, natural gas
max. load
%
9.1
(GAS A)
min. load
Available flue pressure
in. W.C.
0.4 (100 Pa)
(flue draft + air supply pressure)
Air supply volumetric flow rate
cfm
95
95
130
160
190
220
Blower
G1G 170
Honeywell gas valve
V4730C1071
V4730C1097
V4730C10
63
Gas injector diameter
Natural gas (GAS A) calorific value 1075 BTU/ft3
17.0
Heating water circuit
Boiler water capacity
US gal-
lons
4.2
4.2
5.3
6.3
7.1
7.9
Primary pressure drop
psi
Æ
Fig. 4 (graph)
Maximum flow temperature, heating/hot water
mode
° F
180/180
High temperature cut-out safety limit (manual
reset high limit setting
)
° F
200
Permissible operating pressure
psi
50
Electrical data
Enclosure class
IP 40
Mains power supply
V/Hz
120 V / 60 Hz
Power consumption
max. load
W
84
150
190
230
270
370
min. load
W
40
40
45
50
50
50
Maximum permissible fuse rating
A
10
Appliance dimensions and weight
Transport clearance dimensions, width x depth x
height
Inches
34x25x60
42x25x60
50x25x60
Weight
lbs
455
530
585
665
730
Tab. 2
Specifications
Содержание Logano plus GB312
Страница 121: ...Logano plus GB312 Technical specifications are subject to change without prior notice 121 Notes ...
Страница 122: ...Logano plus GB312 Technical specifications are subject to change without prior notice 122 Notes ...
Страница 123: ...Logano plus GB312 Technical specifications are subject to change without prior notice 123 Notes ...