10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
81
(continued from
previous page)
SAFe burner con-
trol unit defective.
Ignition transformer
defective (delayed
or non-existent
spark, "violent" start-
tup).
Replace SAFe.
Replace ignition
transformer.
V
6L
561
5 power-up
sequences (power
supply disconnection
during burner start-
up).
The burner control
unit has switched
off 5 times during
the burner start-up
sequence.
Check the 120V
power supply to the
control unit.
Reset burner con-
trol unit.
Rectify power sup-
ply problem.
B
7A
550
Voltage too low.
The power supply
voltage is too low.
The power supply
voltage must not
drop below 102V.
Ensure adequate
power supply volt-
age.
B
7A
551
Power failure.
There has been a
brief loss of power.
Check power supply
lead for loose con-
tacts.
Check wiring and
proper contact of
power plug on
MC10/SAFe.
Rectify any contact
problems.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Содержание Logano plus GB312