10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
83
V
8Y
590
Pressure switch in
safety assembly has
tripped.
Break in pressure
switch safety
assembly during
burner operation.
Check whether low
gas pressure switch
(available sepa-
rately) is breaking
circuit during opera-
tion.
Check if the air sup-
ply switch or flue
gas pressure switch
opens while the
boiler is operating.
Check whether
SAFe or high gas
pressure switch
(available sepa-
rately) is breaking
circuit during opera-
tion
Section 10.3, page
87 ff
Measure the gas
pressure at 100%
boiler modulation.
Check low gas
pressure switch
(available sepa-
rately) setting.
Check flue/air sup-
ply pipe for block-
ages.
Replace gas valve
V
8Y
591
Error checking safety
assembly.
SAFe pressure
switch has not
tripped.
Check whether gas
supply pressure is
> 3 inches w.c.
Check setting of
SAFe pressure
switch.
Check connector on
gas valve is properly
seated.
Ensure gas supply
pressure is
> 3 inches w.c.
Adjust setting of
SAFe pressure
switch to 3 inches
w.c.
Insert connector
properly.
Replace SAFe
pressure switch
and wiring.
Replace SAFe.
V
9Y
500
501
502
503
Internal SAFe relay
fault.
Internal electronic
fault on SAFe.
Press Reset button
and wait to see if
fault is eliminated.
If fault recurs after
reset, SAFe must
be replaced.
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code