Service manual

Lambdatronic S 3200 for firewood boiler

Core module version 50.04 - Build 05.20 | Touch control version 60.01 - Build 01.38

Translation of the original German installation instructions for technicians

Read and follow the instructions and safety information!

Technical changes, typographical errors and omissions reserved!

B1420922_en | Edition 27/10/2022

Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com

Содержание Lambdatronic S 3200

Страница 1: ... 60 01 Build 01 38 Translation of the original German installation instructions for technicians Read and follow the instructions and safety information Technical changes typographical errors and omissions reserved B1420922_en Edition 27 10 2022 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 2: ...nected units 32 3 1 3 System check 32 3 2 General information about the settings wizard 33 3 3 Switching on for the first time 34 3 4 Starting the setting wizard 35 4 Parameters overview 37 4 1 Heating 37 4 1 1 Heating Status 37 4 1 2 Heating Temperatures 38 4 1 3 Heating Times 39 4 1 4 Heating Service 39 4 1 5 Heating Heating up program 40 Heating up programs 41 Configure program 8 41 Heating cir...

Страница 3: ...y 80 4 15 Touchscreen 81 4 15 1 Touchscreen Display settings 81 Display settings General 81 Display settings Basic display 82 Display settings Date Time 82 Display settings Software update Service 82 4 15 2 Touchscreen Display operating rights 83 Froling Connect 83 4 15 3 Touchscreen Display allocation 84 5 FAQ 85 5 1 Activation options of pump outlets 85 5 2 Pump stall protection 86 5 3 Boiler op...

Страница 4: ...ried out on electrical components Always have work carried out by a qualified electrician Observe the applicable standards and regulations Work must not be carried out on electrical components by unauthorised persons WARNING When touching hot surfaces Severe burns are possible on hot surfaces and the flue gas pipe When work is carried out on the boiler Shut down the boiler according to procedure O...

Страница 5: ...L N AUF ZU N AUF ZU KM 26 PWM 0 10V Pumpe 1 KM 25 Kesselfühler KM 24 Rücklauffühler KM 23 Vorlauffühler 1 KM 22 Vorlauffühler 2 KM 21 Raumfühler 1 KM 20 Raumfühler 2 KM 19 Außenfühler KM 18 Fühler 1 KM 17 Fühler 2 KM 16 Türkontaktschalter KM 15 Abgasfühler KM 14 Kesselfreigabe KM 13 Lambdasonde KM 12 Durchflussmesser End jumper Mains fuse Core module Connection Name Note KM 01 BUS Connection with ...

Страница 6: ...em number 69400 KM 14 Boiler release Connection cable1 2 x 0 75 mm2 Caution The connection must be a floating connection Boiler enable contact 24 V supply See Analogue module page 25 KM 15 Flue gas temperature sensor Only use connection cable of the component 24 V supply See Analogue module page 25 KM 16 Door switch Connection cable1 2 x 0 75 mm2 KM 17 Sensor 2 Connection cable1 2 x 0 75 mm2 KM 18...

Страница 7: ...ax 2 5A KM 33 Heating circuit pump 1 KM 34 Heating circuit pump 0 or burner relay Connection cable1 3 x 1 5 mm2 max 2A KM 35 Operating signal Connection cable1 2 x 0 75 mm2 See Operating signal page 14 KM 36 Optional module Ignition expansion connection 1 YMM as per ÖVE K41 5 or H05VV F as per DIN VDE 0881 5 Fuses F2 6 3 AT Pump 1 induced draught fan Power connection and wiring 2 Core module and c...

Страница 8: ...2 Power connection and wiring Core module and connection options 8 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 9: ...luded with the materials supplied for the boiler and is usually mounted on an outer wall that is not directly exposed to the sun It continuously measures the ambient temperature and forms part of the weather compensated heating circuit control KM 19 Außenfühler In the delivered state the outside temperature sensor is read in by the core module KM 19 outside temperature sensor connection Alternativ...

Страница 10: ... deactivated only frost protection Automatic mode Heating and setback phases according to the set times Setback mode Ignores the heating phases and continuously controls the room temperature to the temperature set in setback mode Party switch Ignores the setback phases and continuously controls the room temperature to the temperature set in heating mode Handwheel Allows you to adjust the temperatu...

Страница 11: ... 1 N PE L LV N Netz PE L AO P1 PWM 0 10V Connect the power supply for the high efficiency pump to output Pump 1 of the core module Connect the PWM cable of the high efficiency pump to the corresponding PWM 0 10V port Make sure that the cables are configured correctly polarity in accordance with the connection diagram of the pump Set control of the pump in the relevant menu to Field pump PWM or Fie...

Страница 12: ...ol signal AC pump without control signal pulse package control On older pumps without a control signal that are not highly efficient the speed control is implemented via a pulse package control Please note that the minimum speed may need to be adjusted on some pumps default setting 30 FRKEM29 Pumpe 1 N PE L LV N Netz PE L AO P1 Connect pump to output Pump 1 of the core module In the relevant menu ...

Страница 13: ... Netz PE L AO P1 HKP0 N PE L1 Phase L for switching the valve and connecting neutral conductor N to output Pump 1 with the RC element Phase L for continuous supply switches the valve back to the initial position at output HCP0 connect terminal L1 Power connection and wiring 2 Core module and connection options Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 13 ...

Страница 14: ...ontact can used to switch the phase At above 5 Ampere the pump must be isolated with a relay HKP 0 N PE L1 Wire the floating output contact as an enabling signal to control the standby boiler 2 1 8 Operating signal On the core module connection position KM 35 it is possible to issue a floating operating signal The status is displayed under the Standby relay output in the Manual Digital outputs men...

Страница 15: ...Connecting the bus cable page 28 Caution CAN L and CAN H must not be connected to UBUS HE 02 BUS HE 03 Flow temperature sensor 1 Connection cable1 2 x 0 75 mm2 HE 04 Flow temperature sensor 2 HE 05 Room temperature sensor 1 Connection cable1 2 x 0 75 mm2 shielded from 25 m cable length HE 06 Room temperature sensor 2 HE 07 Sensor 1 Connection cable1 2 x 0 75 mm2 Connection of the outside temperatu...

Страница 16: ...ss 0 to 7 A hydraulic module is included in the delivery as standard address 0 A further seven modules addresses 1 to 7 can be retrofitted You must ensure that the module address is assigned correctly See Setting the module address page 29 Hydraulic module up to version FRHYU21 FRHYU21 N N L L HY 14 Pumpe _ 1 HY 13 Netz HY 05 AO P1 HY 07 Fühler _ 1 HY 08 Fühler _ 2 HY 09 Fühler _ 3 HY 10 Fühler _ ...

Страница 17: ... Fühler _ 1 HY 08 Fühler _ 2 HY 09 Fühler _ 3 HY 10 Fühler _ 4 HY 11 Fühler _ 5 HY 06 AO P2 HY 12 Fühler _ 6 HY 01 HY 02 Bus HY 15 Pumpe _ 2 L N L L Hydraulic module Mains fuse Module address End jumper Connection Name Note HY 01 BUS Patch cable CAT 5 RJ45 SFTP 1 1 configuration HY 02 BUS HY 03 BUS Connection with cable LIYCY paired 2x2x0 5 See Connecting the bus cable page 28 Caution CAN L and CA...

Страница 18: ... additional wired control line the speed control is implemented via the additional connection for the PDM or 0 10V signal up to hydraulic module version FRHYU21 up to hydraulic module version FRHYU22 FRHYU21 N Pumpe 1 Netz PE L N PE L AO P1 PWM 0 10V FRHYU22 PWM 0 10V N AO P1 Pumpe 1 Netz PE L N PE L L Hydraulic module FRHYU21 Connect the power supply for the high efficiency pump to output Pump 1 ...

Страница 19: ...ut control signal AC pump without control signal pulse package control On older pumps without a control signal that are not highly efficient the speed control is implemented via a pulse package control Please note that the minimum speed may need to be adjusted on some pumps default setting 30 up to hydraulic module version FRHYU21 up to hydraulic module version FRHYU22 FRHYU21 N Pumpe 1 Netz PE L ...

Страница 20: ...rsion FRHYU22 FRHYU22 N AO P1 Pumpe 1 Netz PE L N PE L L L N L N PE 22 12 24 14 21 11 A2 A1 230 VAC power supply Hydraulic module FRHYU22 Connect the pump relay to output Pump 1 or Pump 2 and use the relay output for phase L Install and connect two pole cable 2 x 0 75 mm2 from connection AO P1 or AO P2 to the pump and connect terminal with terminal IN of the pump Install and connect two pole cable...

Страница 21: ...22 N Pumpe 1 Netz PE L N PE L L Hydraulic module FRHYU21 Phase L for switching the valve and connecting neutral conductor N to output Pump 1 or Pump 2 with the RC element Hydraulic module FRHYU22 Phase L for switching the valve and connecting neutral conductor N to output Pump 1 or Pump 2 using the relay output for phase L Connect the phase L for continuous supply switches the valve back to the in...

Страница 22: ...5 Bus FRRLA10 Return mixer module Connection Name Note RL 01 Return mixer Connection cable1 4 x 0 75 mm2 max 0 15A 230V RL 02 Mains Connection cable1 3 x 1 5 mm RL 03 Mains RL 04 Bus Patch cable CAT 5 RJ45 SFTP 1 1 configuration included in delivery RL 05 Bus 1 YMM as per ÖVE K41 5 or H05VV F as per DIN VDE 0881 5 Fuses F1 6 3 AT Return mixer Connection example Firewood Dual fuel boiler Balancing ...

Страница 23: ...dung ZE 05 Verriegelung ZE 06 Kernmodul L N FRZER10 10 AT Ignition expansion Connection Name Note ZE 01 Core module power supply Connection cable1 3 x 1 5 mm ZE 02 Mains Connection cable1 3 x 1 5 mm ZE 03 Reserve S4e Turbo with automatic WOS Connection cable1 3 x 1 5 mm WOS drive ZE 04 Electric ignition Connection cable1 3 x 1 5 mm ZE 05 Lock Connection cable1 2 x 0 75 mm 24V looping through ZE 06...

Страница 24: ...Mains plug Main switch Hydraulic module Core module Lock Use the network cable provided for connecting to the terminal block Ignition expansion Lock 2 Power connection and wiring Expansion modules 24 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 25: ...on AN 04 Bus AN 05 Power supply 24 V power supply of the module connection cable1 2 x 1 0 mm Pellet boiler See 24 V power supply page 26 pellet boiler and dual fuel boiler Pellet module MIN sensor terminal Wood chip boiler Supply via 24 V power supply unit AN 06 Thermocouple Use sensor connection 1 YMM as per ÖVE K41 5 or H05VV F as per DIN VDE 0881 5 Standard configuration Analogue module with ad...

Страница 26: ...ted If the signal falls below 70 0 69 the boiler is activated at a boiler output of 70 until the firewood has burnt down By default 0V 0 and 10V 100 This can be changed using the Invert ext power demand via analogue input parameter To initiate start up via the power demand Automatic mode must be selected and the contact must be closed if a release contact is used Boiler release input available par...

Страница 27: ...though no specific sequence of the module types and addresses is specified A star stub cable is not permitted As the control units are supplied with voltage in addition to transferring data problems caused by voltage drops can occur depending on the number of modules and existing cable lengths A voltage supply unit must be used for every touch room console heating circuit module hydraulic module P...

Страница 28: ...e set on the first and last module When using a bus repeater the two galvanically separated sub networks must be considered separately The jumpers for each network must be set on the first and last module End jumper not set End jumper set If the contacts at the base of the end jumper are not bridged image left it is referred to as not set In this case there is no bus termination If the contacts ar...

Страница 29: ...t included in the delivery The configurations listed are not available in all countries Expansion can include up to eight hydraulic modules address 0 to 7 Important Only set the module address when the device is disconnected from the power supply Included in standard delivery Lambdatronic S 3200 Touch control Address 0 Heating circuit 1 2 Hydraulic module Address 0 Address 1 Hydraulic module Heati...

Страница 30: ...tion line NOTICE The dimensions of the equalization line must be installed by a specialist in accordance with regional regulations Instead of the potential equalisation a Fröling bus repeater can be used in the bus connection line to the next building The potential separation galvanic isolation allows the bus network to be split into two separate sub networks A B C D E F G H I J A B C D E F G H I ...

Страница 31: ...blue N yellow green PE blue brown black PWM not used Wire the power supply to the pump outlet on the board Connect the control cable to the PDM output on the board making sure that the polarity is correct blue wire to earth brown wire to plus Do not use the black wire and insulate if necessary Pump type with 4 pin control cable Power supply 4 pin control cable brown L blue N yellow green PE blue b...

Страница 32: ...onnection of the BUS cable for short circuits Check the specified addresses and terminal jumpers on the individual modules heating circuit modules hydraulic modules displays 3 1 2 Check on the connected units Check that all units that are used are connected correctly Carry out wiring check Check for loose or uninsulated wires in the terminal boxes of the pumps mixing valve and switch valve which c...

Страница 33: ... boiler specific options ignition filter etc Lambda probe Selection and calibration of the type of sensor used Feed system Selection of the existing discharge system only for boilers with automatic loading Hydraulic system Selection of the hydraulic system hydraulic system 1 2 3 etc Additional components Selection and activation of the existing load and control components heating circuits DHW tank...

Страница 34: ...e production number of the boiler system date and time Then the basic screen of the touch display is shown 1 Selection of the controller language 2 Setting the production number see identification plate 3 Setting the date and time 4 Display of the basic screen 3 Initial start up with settings wizards Switching on for the first time 34 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froel...

Страница 35: ... confirm 3 Tap the icon of the settings wizard 4 Tap the Boiler setting wizard 5 The settings wizard loads 6 Read the information text and continue with YES to start Initial start up with settings wizards 3 Starting the setting wizard Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 35 ...

Страница 36: ...ining the control signal of the respective pump The following options are available depending on the selected menu Pump without control line HE pump without control line Field pump PDM Solar pump PDM Field pump PDM valve Solar pump PDM valve Field pump 0 10 V Solar pump 0 10 V Field pump 0 10 V valve Solar pump 0 10 V valve Switch valve See Activation options of pump outlets page 85 7 Continue to ...

Страница 37: ... mode Heating circuit remains in setback mode until another mode is activated Party Party mode the current or next setback phase is ignored OFF Switched off heating circuit deactivated only frost protection Actual flow temperature Display of the current flow temperature Flow temperature setpoint Display of the calculated flow temperature setpoint Room temperature Prerequisite Heating circuit used ...

Страница 38: ...ing circuit pump switches off in heating mode If the outside air temperature exceeds this value during heating the heating circuit pumps and mixing valve are deactivated External temperature at which heating circuit pump switches off in setback mode If the outside air temperature falls below this value in setback mode the heating circuit pumps and mixing valve are activated Maximum heating circuit...

Страница 39: ...anual Off Mixer runtime Here you can set the mixer runtime of the mixer in use NOTICE To avoid mixer vibration do not set value 150s Switch off heating circuit pump when outfeed setpoint is lower than Prerequisite Heating circuit is operated without remote control If a flow temperature setpoint is calculated below the value set the heating circuit pump switches off and the mixing valve closes Shou...

Страница 40: ...p program that has been set starts After the 30 days the heating circuit that has been selected operates based on the set heating times again The heating times of the selected heating circuit as well as the boiler buffer tank loading times are automatically set to 0 00 24 00 and the outside air temperature heating limit is ignored When using a firewood boiler a corresponding heat supply must be en...

Страница 41: ...p setpoint C 30 The heating up programs listed are non binding recommendations If the heating up program is to be used for floor screed drying you must consult the manufacturer of the floor finish and or the installer Configure program 8 Heating up program Service Configure program 8 Outfeed temperature setpoint on day 1 30 If heating up program 8 is selected the flow temperature setpoint can be p...

Страница 42: ...odule the address of the relevant heating circuit module 1 must be set here sensor 1 on relevant module Using room sensor inputs for room thermostat NOTICE This parameter influences all sensor connections to which an analogue room temperature sensor can be connected NO At the sensor connector of the room sensor a room sensor must be connected to control the room temperature YES At the sensor conne...

Страница 43: ...e time window is active and the loading source boiler or buffer tank indicates the set loading increase and the DHW tank loading is started Load if temperature difference between storage tank and DHW tank is If the top storage tank temperature is above the current DHW tank temperature by this value and the time window is active DHW tank loading starts only for systems with a storage tank Load if t...

Страница 44: ... temperature YES If the DHW tank has already been loaded once on the current day a further DHW tank loading is prevented Legionella heating activated NO A legionella heating of the DHW tank is not carried out YES Once a week the DHW tank is heated to the temperature set under the parameter DHW tank temp setpoint for legionella heating same for all DHW tanks When should the legionella heating be ca...

Страница 45: ...the output is only performed either when a per litre output of the collector pump has been set or an external volume pulse transmitter is used In order to perform the calculation more precisely the use of a collector return sensor is recommended Flow through l h Prerequisite External volume pulse transmitter installed Display of the water quantity currently being pumped through the solar collector...

Страница 46: ... temperature at collector which must be reached in order for the solar control to start Collector pump protection from a collector temp If the measured value of the solar collector sensor exceeds the set value the solar collector must cool down by 20 C within 15 minutes otherwise the solar collector pump stops in order to protect the pump Heat exchanger buffer tank pump start delay Prerequisite Hy...

Страница 47: ...ge 85 Minimum collector pump speed Adjustment of the minimum speed to the pump type set mode of pump in accordance with pump manufacturer Maximum collector pump speed If you need to limit the maximum speed of the collector pump for systemic reasons you can do so by adjusting this parameter Collector monitoring YES The collector pump is switched on at regular intervals for 10 seconds The time can b...

Страница 48: ... solar heat exchanger and buffer tank is connected Control of storage tank heat exchanger pump Prerequisite Hydraulic system 12 or 13 Definition of control signal for pump type used See Activation options of pump outlets page 85 Pump outlet of DHW tank heat exchanger pump Prerequisite Hydraulic system 12 Pump outlet to which the pump between the solar heat exchanger and DHW tank is connected Contr...

Страница 49: ...ing pumped through the solar collector Todays yield kWh Display of the heat quantity that has been supplied by the solar panel system today Daily yield 1 6 days ago kWh Shows the historical progression of the solar panel system The yields of the last 6 days are available Total yield kWh Display of the heat quantity which has been supplied by the solar panel system since activation of the heat mete...

Страница 50: ... are used to calculate the storage tank charge status Buffer tank middle temperature Prerequisite Middle buffer tank temperature sensor installed Display of the current temperature in the mid area of the buffer tank Buffer tank bottom temperature Display of the current temperature in the lower part of the buffer tank Buffer tank pump control Display of the current speed of the buffer loading pump ...

Страница 51: ...e current temperature in the lower part of the buffer tank buffer tank loading is stopped Storage tank storage tank difference Prerequisite Variant 3 Difference which must be given for loading a storage tank e g in an adjacent building If this difference is not reached the storage tank loading stops Top buffer temp when the start up relief valve switches to bottom buffer If the temperature set is ...

Страница 52: ...nput to which the sensor in the bottom part of the buffer tank is connected Pump output of storage tank pump Pump outlet to which the buffer loading pump is connected Control of storage tank pump Definition of control signal for pump type used See Activation options of pump outlets page 85 Minimum storage tank pump speed Adjustment of the minimum speed to the pump type set mode of pump in accordan...

Страница 53: ... gas setpoint Boiler control variable Display of the signal for the combustion controller ID fan control Display of the current ID fan control ID fan speed Display of the current ID fan speed Primary air Display of the current value of the primary air flap according to controller Position of primary air flap Display of the current position of the primary air flap adjusted for the air settings Resi...

Страница 54: ...is controlled only when the store loading pump is active If the pump stops the mixer closes the total return opens the bypass 4 5 3 Boiler Service System menu Boiler Mixer runtime Prerequisite Return temperature control with mixing valve Setting the runtime of the mixer used for the return temperature control Recommendation To reduce mixer vibration do not set value below 150s Output fire off mess...

Страница 55: ...F Modem installed NO The boiler does not have a modem for data transfer installed YES The boiler has a modem for data transfer installed Memory cycle of data logger If the boiler is equipped with a data logger the most important boiler data is stored on a SD card This parameter specifies at what intervals the recording should be started Which temperature scale should be used Celsius C Displayed te...

Страница 56: ...t for external power demand Defines the input for the external power demand with a specified power of 0 10V address of analogue module and input terminal e g 0 3 Boiler General settings MODBUS settings System menu Boiler MODBUS settings COM 2 is used as a MODBUS interface NO The COM 2 interface sends the most important boiler values every second YES The COM 2 interface can be used to connect a MOD...

Страница 57: ...ay of the current boiler temperature of the secondary boiler Burner relay status Shows the current status of the burner relay 0 Secondary boiler not active 1 Secondary boiler active Standby boiler pump Prerequisite Switch valve installed parameter set to NO Display of the current pump control for the standby boiler Standby boiler switch valve Prerequisite Switch valve installed parameter set to YE...

Страница 58: ...ration when outside air temperature less than Prerequisite Heat pump as standby boiler The heat pump stops working below the set temperature This avoids operation with high energy consumption when the temperature outside is cold Maximum outfeed temperature for heat pump operation Prerequisite Heat pump as standby boiler If a flow temperature higher than the set value is required the main boiler ta...

Страница 59: ... boiler or the secondary boiler switch valve is connected Control of boiler 2 pump Definition of control signal for pump type used See Activation options of pump outlets page 85 Maximum speed of boiler 2 pump If you need to limit the maximum speed of the loading pump of the secondary boiler for systemic reasons you can do so by adjusting this parameter Invert secondary boiler isolating valve YES I...

Страница 60: ...is not subsequently changed and ignition is not disabled the storage tank loading criterion applies daily from the specified time Storage tank f flow method The maximum flow temperature required by the system environment e g heating circuit is compared with the current storage tank temperature from the specified time The ignition Ignition time date time process starts if the top storage tank tempe...

Страница 61: ... specified values for the chosen fuel selection should be adopted Fuel selection Wet firewood If firewood is to be burnt with a water content of more than 15 this setting should be selected A prompt then appears to confirm whether the specified values for the chosen fuel selection should be adopted Parameters overview 4 Fuel Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 61 ...

Страница 62: ... 2 4 pump 4 9 2 Network pump Temperatures System menu Network pump Network return setpoint Prerequisite Network pump installed The network return setpoint is regulated to the value set here When the network return temperature reaches the specified value the network pumps starts up at minimum speed Return temperature setpoint distributor 1 Prerequisite Variant 1 and pump for distributor 1 installed...

Страница 63: ...nstalled Definition of control signal for pump type used See Activation options of pump outlets page 85 Minimum speed for distributor 1 pump Prerequisite Variant 1 and pump for distributor 1 installed Adjustment of the minimum speed to the pump type set mode of pump in accordance with pump manufacturer Maximum speed for distributor 1 pump Prerequisite Variant 1 and pump for distributor 1 installed...

Страница 64: ...ference Temperature difference between heat source and heat sink which must be reached to activate the pump of the differential controller Shutdown difference If the temperature difference between the heat source and the heat sink falls below this value the pump of the differential controller is deactivated Minimum temperature for heat source If the temperature in the heat source falls below this ...

Страница 65: ...ordance with pump manufacturer Maximum pump speed If you need to limit the maximum speed of the pump of the differential controller for systemic reasons you can do so by adjusting this parameter Sensor input of heat source sensor Sensor input to which the heat source sensor is connected Sensor input of heat sink sensor Sensor input to which the heat sink sensor is connected Sensor monitoring YES I...

Страница 66: ...ump is also activated at a signal from the flow valve YES The circulation pump is controlled according to time program and temperature at the return circulation line In conjunction with the use of a flow switch the circulation pump is also activated at a signal from the flow switch NOTICE Connect the flow sensor as the return sensor Switch off the pump at what return temperature in the circulation...

Страница 67: ...which the flow switch is connected Pump output of circulation pump Pump outlet to which the circulation pump is connected Control of circulation pump Definition of control signal for pump type used See Activation options of pump outlets page 85 Maximum speed of the circulation pump If you need to limit the maximum speed of the circulation pump for systemic reasons you can do so by adjusting this p...

Страница 68: ...boiler off on standby ON The solenoid opens and the calorific value heat exchanger is cleaned NOTICE This parameter can only be activated when the boiler is in Standby or Boiler off status 4 12 2 Manual Digital outputs System menu Manual Digital outputs The parameters displayed depend on the boiler configuration A 0 Automatic Off A 1 Automatic On 1 Manual On 0 Manual Off 4 Parameters overview Manu...

Страница 69: ...e outputs The parameters displayed depend on the boiler configuration A 0 Automatic Off A 1 100 Automatic with value ON 1 100 Manual with value ON 0 Manual Off Parameters overview 4 Manual Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 69 ...

Страница 70: ...anual Digital inputs The parameters displayed depend on the boiler configuration A 0 Automatic Off A 1 Automatic On 1 Manual On 0 Manual Off 4 Parameters overview Manual 70 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 71: ...g operating status the difference between the current flue gas temperature and the current boiler temperature must at least exceed the value set here Flue gas temperature below which boiler switches to OFF status If the flue gas temperature is below this value for the duration of the Maximum heating up time during which HEATING status must be reached the boiler switches to Off status Activating th...

Страница 72: ...cified time Storage tank min method The ignition process starts if heat is requested from the storage tank from the specified time parameter Boiler start if difference between boiler setpoint and top storage tank is larger The period applies from the specified time until 24 00 h on the specified date If the specified time is not subsequently changed and ignition is not disabled the storage tank lo...

Страница 73: ...is over 100 C the safety time starts If the control of the secondary air flap does not change within this set period of time a warning appears on the display Primary air opening at 0 activation At 0 activation of the primary air flap this will open by the specified value Primary air opening at 100 control At 100 activation of the primary air flap this will open by the specified value at most Openi...

Страница 74: ... off Set Lambda probe System menu System Setting Lambda probe Residual oxygen content Display of the current residual oxygen content Lambda probe status The following status displays are possible Off Pre heating Normal operation Cooling Reheating Error Lambda probe type Setting the Lambda probe type used Bosch broadband probe item number 69001A broadband probe socket NTK broadband probe item numbe...

Страница 75: ... If the boiler switches to Boiler off or Off mode the lambda probe heating remains active for at least 1 hour up to a maximum of 24 hours If the residual oxygen content exceeds the value set here the lambda probe heating is switched off Switching type sensor Setting Lambda values Switching type sensor Residual oxygen content Display of the current residual oxygen content Lambda probe voltage measu...

Страница 76: ...nsor input Sensors 1 2 on the core module or a sensor on the hydraulic module can be used as flow temperature sensors If an invalid sensor assignment is made the value of the boiler sensor is used to calculate the quantity of heat Specific heat capacity This parameter indicates the specific heat capacity of the heat carrier The value for pure water 4180 Ws kgK is used as the default value Litres p...

Страница 77: ...eral settings See Boiler General settings page 55 MODBUS settings Setting General settings MODBUS settings See Boiler General settings MODBUS settings page 56 Parameters overview 4 System Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 77 ...

Страница 78: ...umps In the Sensors and pumps menu all sensor inputs and pump outlets available in the hydraulic system can be allocated The number of parameters depends on the configuration 4 13 4 System System selection System menu System System selection Menu for setting the configuration for systems that have not been configured with the setting wizard 4 Parameters overview System 78 Froling GesmbH A 4710 Gri...

Страница 79: ...s are pending This function can also be used to delete pending fault messages that are not visible 4 14 3 Diagnostics Error history System menu Diagnostics Error history Up to 50 fault indication entries are stored in the error history A fault can consist of up to 3 fault indication entries You can determine what type of fault message it is when the fault occurred appeared when the fault was ackno...

Страница 80: ...ear error history The entire error history can be deleted using this function From this time on the error history will be filled again with new fault messages 4 Parameters overview Diagnostics 80 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 81: ...n the set time the screensaver will activate and the screen will go dark To disable the screensaver set the delay time to 0 Module address This is where you can change the module address if it is incorrectly set Module address 0 Boiler console Module address 1 7 respective room console 3200 with touchscreen NOTICE Once you have changed the module address you will need to restart the boiler control...

Страница 82: ...oftware update Service System menu Display settings Software update Service Touchscreen Calibrate screen See Calibrating the touchscreen page 93 Restart control Carry out update See Software update Lambdatronic 3200 page 95 Restart display Touch control unit is restarted and the data is reloaded from the core module Restore control device to factory settings restart is carried out The touch displa...

Страница 83: ...sed from touchscreen 1 7 Storage tank system Allow access to storage tank 01 04 Specifies whether storage tank 01 04 can be accessed from touchscreen 1 7 Solar panel system Allow access to solar system 01 Specifies whether solar system 01 can be accessed from touchscreen 1 7 Heating system The parameters displayed depend on the configuration Boiler Boiler values visible If this function is activat...

Страница 84: ...rcuit number with its address must be set on the room console The parameters are set to none at the factory DHW tank system Touchscreen with address 1 7 is assigned to the following DHW tank To assign a DHW tank to a specific room console the respective DHW tank number with its address must set on the room console The parameters are set to none at the factory Button display with address 1 7 is ass...

Страница 85: ...r pumps Field pump PDM valve The signal for the field pump is emitted at the PDM output If the signal exceeds 2 the 230V output is switched on If the signal is below 2 for more than 4 minutes the output is switched off again PDM sol pump valve The signal for specially marked high efficiency solar pumps is emitted at the PDM output If the signal exceeds 2 the 230V output is switched on If the signa...

Страница 86: ...riefly on a regular basis even outside the season of use At that time the pumps are activated for 15 seconds at 100 The following components are affected DHW loading pump Buffer pump Collector pump not applicable to system 12 and system 13 Difference control pump Heating circuits 15 seconds pump run subsequently the mixer starts up and shuts down again 5 FAQ Pump stall protection 86 Froling GesmbH...

Страница 87: ... menu for the automatic ignition has been reached Ignition with auto ignition The fuel is ignited with fan assistance The boiler attempts to reach the criteria for heating status within a specified time Heating The boiler controller controls combustion according to the boiler setpoints Slumber Very low power consumption When the boiler temperature setpoint is exceeded by a specified value the boil...

Страница 88: ...ve Circulating pump speed controlled Line regulating valve Circulating pump speed controlled Thermal valve 3 way mixing valve 5 4 2 Functioning and configuration Software version V50 04 B05 19 at minimum is required for the heat quantity calculation to work The difference between the boiler temperature and the boiler return temperature as well as the flow of the circulating pump are used to calcul...

Страница 89: ... B Press the handle A on the line regulating valve Read and record the flow rate in l min at the underside of the floater B Activate the circulating pump in manual operation at 50 speed Press the push bar on the line regulating valve make a note of the flow on the scale FAQ 5 Determination of the quantity of heat Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 89 ...

Страница 90: ...figuring the heat quantity calculation Go to the menu System Settings Boiler heat quantity calculation Enter the recorded values for the flow of the circulating pump at the respective parameter 5 FAQ Determination of the quantity of heat 90 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 91: ... time menu and the procedure for changing the times are always the same Use the left or right arrow to navigate to the desired day of the week Tap the symbol under the day of the week The edit window will appear You can specify up to four time windows per component and day Tap the desired time window FAQ 5 Setting times Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 91 ...

Страница 92: ... window setting by tapping on the confirm icon If you want to apply the time window setting to another day in addition you can do this by activating the relevant day A set time window can be deleted by tapping on the Recycle bin symbol 5 FAQ Setting times 92 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 93: ...Software update Service menu open the Recalibrate touch control parameter Set the parameter to YES and confirm at the bottom right The touchscreen will restart and begin calibrating To calibrate the touchscreen you much press five points indicated by a crosshair in the order shown The control will restart after calibration FAQ 5 Calibrating the touchscreen Service manual Lambdatronic S 3200 for fi...

Страница 94: ...f you do not tap the indicated points accurately the control may stop working properly and a software update may be required 5 FAQ Calibrating the touchscreen 94 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 95: ...te The procedure for establishing a connection and any necessary bootloader update is described in the documentation of the Flash Update Wizard Overview of main steps during a software update Perform flash update but do not close the Wizard Lambdatronic Service 1 See Carrying out a software update on the boiler controller page 96 Perform software update of all touch controls 2 USB A USB C USB A Se...

Страница 96: ...ler There is a drop down list next to the Update to field which shows the Flash files available in the standard folder If the Flash file is located in the standard folder Select the required Flash file from the drop down list If the Flash file is not located in the standard folder Click on the Find button in the FLASH section A window is displayed where you can search for the Flash file Navigate t...

Страница 97: ...ll now start and a progress bar displays the current status When the flash update is successfully transferred to the boiler controller the following window appears NOTICE Do not close the update at this time and do not disconnect the boiler controller FAQ 5 Software update Lambdatronic 3200 Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 97 ...

Страница 98: ...stem message for restart is displayed Tap OK to carry out a restart of the touch control After the restart the update process will begin automatically Once the update is complete a message will appear that you can remove the stick Remove the USB stick The touch control restarts automatically The touch control software is up to date following the restart Perform updates to any other touch controls ...

Страница 99: ...s Clicking on Close closes the Flash Update Wizard and restarts the boiler controller After restarting the boiler controller check whether all touch controls have started up correctly NOTICE If not all touch controls connect to the boiler control a restart of the entire system main switch OFF ON is necessary FAQ 5 Software update Lambdatronic 3200 Service manual Lambdatronic S 3200 for firewood bo...

Страница 100: ... on the left outside the holding fixture Swivel the display forwards on the left side and remove diagonally to the left Push the cover together at both indentations and remove Connect USB C USB A adapter cable to the display bushing and secure cable on display housing using cable ties Re assemble the display in reverse order 5 FAQ USB data recording 100 Froling GesmbH A 4710 Grieskirchen Industrie...

Страница 101: ...tain a software update Recording starts automatically once the touch display has started Data recording is indicated in the status line by means of the USB symbol with an activity bar FAQ 5 USB data recording Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 101 ...

Страница 102: ...6 Notes 6 Notes 102 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...

Страница 103: ...Notes 6 Service manual Lambdatronic S 3200 for firewood boiler B1420922_en 103 ...

Страница 104: ...USTRIA TEL 0043 0 7248 606 0 FAX 0043 0 7248 606 600 EMAIL info froeling com INTERNET www froeling com Customer service Austria 0043 0 7248 606 7000 Germany 0049 0 89 927 926 400 Worldwide 0043 0 7248 606 0 7 1 2 Address of the installer Stamp 7 Appendix Addresses 104 Froling GesmbH A 4710 Grieskirchen Industriestraße 12 www froeling com ...