Fault 8Y/590 (locking)
Cause:
pressure switch in safety sequence has tripped.
Description:
cut-out in pressure switch safety sequence
during burner operation.
Fig. 70 Fault elimination sequence 8Y/590
7 747 010 719-93.3RS
check high pressure switch
(available separately)
air supply and flue pressure
switch while burner is OFF.
yes
no
Check which pressure switch cuts
out when burner is running
Is there clear
passage on all
pressure
switches?
Replace the
pressure switch
which has cut
out!
Perform reset!
Perform reset!
High pressure
switch cuts out!
Replace gas
valve!
Air supply pres-
sure monitor
cuts out!
Check air supply
pipe for blockage!
Flue pressure
monitor cuts out!
Check flue pipe for
blockage!
yes
no
Is the required gas supply
pressure available across
complete burner modulation
range (30-100%)?
Eliminate cause!
check low pressure
switch (available
separately).
Perform reset
Содержание Logano plus GB312