10
Troubleshooting
Logano plus GB312 - Technical specifications are subject to change without prior notice
75
10.2.2 Fault messages
Type
1)
Display
code
Fault code Cause
Description
Testing
sequence/Cause
Action
B
2E
207
The water pressure is
< 8.7 psi (0.6 bar).
-
Is system pressure
at least 14.5 psi (1
bar)?
Adjust operating
pressure.
B
2U
565
Difference between
supply and return tem-
perature too great.
(>72 °F; >40 K)
Heat exchanger
cut-out due to
excessive tempera-
ture spread.
System configura-
tion problems.
Check system con-
figuration.
V
2U
575
Boiler sensor/ISTB
sensor.
The maximum per-
missible tempera-
ture at the ISTB has
been reached.
Check water flow.
Check water flow.
Check non-return
valve direction of
flow.
Check boiler sen-
sor/STB.
V
3C
537
No speed signal.
The SAFe is not
receiving a speed
signal even though
the fan is supposed
to be running.
Check connecting
leads between
SAFe and fan for
poor contact, breaks
and damage.
Check connectors
on SAFe and fan.
Establish good
electrical contact.
Replace lead if nec-
essary.
If fan has power
(but is not running)
replace fan.
If fan has no power,
replace the SAFe
V
3C
538
Fan speed too slow.
The actual speed
detected is slower
than the set speed.
Dirt in fan.
Fan defective.
Clean fan if neces-
sary.
Replace fan.
V
3C
540
Fan speed too fast.
The actual speed
detected is faster
than the set speed.
Check PWM signal/
SAFe connecting
lead for poor con-
tact, breaks and
damage.
Check connectors
for damage.
Establish good
electrical contact.
Replace lead if nec-
essary
Replace fan.
V
4A
520
Boiler safety tempera-
ture limiter (STB).
The flow tempera-
ture has reached
200 °F/93 °C (cut-
out temperature of
boiler temperature
limiter).
Fault can only occur
as a result of faults
in system configura-
tion (e.g. only with 2-
boiler systems).
Check system con-
figuration. Check
non-return valve is
fitted correct way
round.
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code