Figure. 5.3.22 - 112. Operating characteristics of power factor protection.
The power factor protection function uses a total of eight (8) separate setting groups which can be
selected from one common source.
The operational logic consists of the following:
• input magnitude selection
• input magnitude processing
• saturation check
• threshold comparator
• block signal check
• time delay characteristics
• output processing.
The inputs for the function are the following:
• operating mode selections
• setting parameters
• digital inputs and logic signals
• measured and pre-processed current magnitudes.