Figure. 5.3.7 - 48. Simplified function block diagram of the Ih> function.
Measured input
The function block uses analog current measurement values from phase or residual currents. Each
measurement input of the function block uses RMS values and harmonic components of the selected
current input. The user can select the monitored magnitude to be equal to the per-unit RMS values of
the harmonic component, or to the harmonic component percentage content compared to the RMS
values. A -20 ms averaged value of the selected magnitude is used for pre-fault data registering.
Table. 5.3.7 - 81. Measurement inputs of the Ih> function.
Signal
Description
Time base
IL1FFT
The magnitudes (RMS) of phase L1 (A) current components:
- Fundamental
- 2
nd
harmonic
- 3
rd
harmonic
- 4
th
harmonic
- 5
th
harmonic
- 6
th
harmonic
- 7
th
harmonic
- 9
th
harmonic
- 11
th
harmonic
- 13
th
harmonic
- 15
th
harmonic
- 17
th
harmonic
- 19
th
harmonic.
5 ms
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
100
© Arcteq Relays Ltd
IM00020