Name
Range
Step Default Prot.funcs.
Description
Max
locked
rotor
current
0.1…40.0xI
n
0.1xI
n
7.5xI
n
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
Maximum locked rotor current of the motor. This setting defines
the current limit which is maximum current for the motor to
draw in locked rotor situation (starting or stalled). If the
measured current exceeds this setting limit it is considered to
be overcurrent fault and corresponding measures can be
applied to disconnect the feeder and motor from the supply.
Max
locked
rotor
current
A
0.1...5
000.0A
0.1A
-
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The maximum locked rotor current in amperes.
Max
overload
current
0.1…40.0xI
n
0.1xI
n
2.0xI
n
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's maximum overload current. Exceeding this setting
stalls the motor. This setting defines when the thermal replica
switches to the short (stall) time constant. As long as the
current stays below this setting value, the motor should
run even when overloaded.
Max
overload
current
A
0.1...5
000.0A
0.1A
-
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The maximum overload current of the motor in amperes.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
211