Figure. 5.3.16 - 95. Simplified function block diagram of the power protection function.
Measured input
The function block uses three-phase power values (active, reactive, or apparent). A -20 ms averaged
value is used for pre-fault data registering. The used power measurement value depends on user input.
If the protection relay has more than one CT module, the
Measured side parameter determines which
current measurement is used for power measurement.
Table. 5.3.16 - 147. Measurement inputs of the power protection function.
Signal
Description
Time base
3PH active power (P)
Total three-phase active power
5ms
3PH reactive power (Q)
Total three-phase reactive power
5ms
3PH apparent power
Total three-phase apparent power
5ms
General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.3.16 - 148. General settings of the function.
Name
Range
Step Default
Description
PQS>/< LN
mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
0: On
Set mode of PWR block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.
Pick-up
The PQS>/< setting parameter controls the pick-up of the power protection function. This defines the
maximum or minimum allowed measured three-phase power (active, reactive, or apparent) before
action from the function. The function constantly calculates the ratio between the PQS>/< and the
measured power magnitude. The reset ratios of 97 % (pick-up mode "Over") and 103 % (pick-up mode
"Under") are built into the function and is always relative to the pick-up value.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
173
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...