Reset
Reset ratio
103 % of the pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.010…150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
9.2.1.20 Mechanical jam protection (Im>; 51M)
Table. 9.2.1.20 - 343. Technical data for the mechanical jam function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
RMS phase currents
Pick-up
Pick-up current setting
0.10…40.00 × I
N
, setting step 0.10 × I
N
Inaccuracy:
- Current
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 0.95)
±1.0 % or ±30 ms
Instant operation time
Start time and instant operation time (trip):
- I
M
/I
SET
ratio 1.05
→
<50 ms
Reset
Reset ratio
97 % of the pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.010…150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
No
Notte!
e!
• Mechanical jam protection requires that the motor running condition has been met before
tripping is possible.
9.2.1.21 Resistance temperature detectors
Table. 9.2.1.21 - 344. Technical data of the resistance temperature detectors.
Inputs
Resistance input magnitudes
Measured temperatures measured by RTD sensors
Alarm channels
12 individual alarm channels
Settable alarms
24 alarms available (two per each alarm channel)
Pick-up
Alarm setting range
Inaccuracy
Reset ratio
101.00…2000.00 deg, setting step 0.1 deg (either < or > setting)
±3 % of the set pick-up value
97 % of the pick-up setting
Operation
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
429
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...