Figure. 5.3.13 - 88. Simplified function block diagram of the U1/U2>/< function.
Measured input
The function block uses analog voltage measurement values and always uses RMS values. A -20 ms
averaged value of the selected magnitude is used for pre-fault data registering.
Table. 5.3.13 - 127. Measurement inputs of the U1/U2>/< function.
Signal
Description
Time base
U
1
RMS
RMS measurement of voltage U
1
/V
5ms
U
2
RMS
RMS measurement of voltage U
2
/V
5ms
U
3
RMS
RMS measurement of voltage U
3
/V
5ms
In RMS values the pre-fault condition is presented with 20 ms averaged history value from -20 ms of
START or TRIP event.
General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.3.13 - 128. General settings of the function.
Name
Range
Default
Description
U1/2 >/< LN
mode
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
0: On
Set mode of VUB block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020