Figure. 5.3.19 - 108. Updating the function's start counter (image not to scale with regard to time).
In the example above the motor is allowed four starts within a specific time frame (
t): the motor is
started four times and the counter is updated accordingly. The function's alarm activates after the third
start to indicate that only one more start is allowed. Once this start is used the function's restart inhibit
is activated and it stays active until the motor can be started again.
The cumulative start-up counter is updated constantly in each program cycle, and the device shows
the inhibit and alarm time as well as the number of used and available starts. The counter is updated in
every start: the counter is increased by the product of the safe stall time multiplied by the nominal start-
up current. In each start the counter is increased by this product which is then in every cycle deduct by
starts/given time divided by program cycle time. This way the start-up counter can be precisely set for
each motor.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
199