Figure. 5.3.18 - 103. Outputs when motor starting takes too long, no speed switch.
There are many reasons why the motor starting takes too long. These include problems in the drive or
in the application. There may also be an issue with the feeding network: if the started motor is very
large and the feeding network is weak, its voltage may drop and therefore the motor cannot provide the
needed torque for normal starting, resulting in a prolonged start-up situation. This is why the I
2
t mode
is suggested as it can compensate for the voltage drop by taking the lower starting current caused by
the lower voltage into account. If definite time is preferred for the Ist> function, it may cause a situation
where the starting is well in action but the user-allowed time is spent due to the lower current and lower
torque caused by the network's low voltage. In this case the function may trip before the starting is over
eventhough the motor is not yet stressed too much and could still continue the starting.
A speed switch –if available in the application– activates when the motor shaft rotates or accelerates,
and it can be used to give the motor additional time for starting beyond the set maximum starting
duration. If the speed switch is in use while a similar situation happens (that is, that the motor starting is
taking longer than it should), the speed switch ensures that the start-up of the motor is still going
fine and the function lets the starting process continue.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
189
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...