Name
Range
Step
Default
Description
Magnitude
of mA
output
channel
(dependent on the
measurement
category selection)
-
(dependent on
the
measurement
category
selection)
Defines the measurement magnitude used for mA output
control. The available measurements depend on the
selection of the "Magnitude selection for mA output
channel" parameter.
Input value
1
-10
7
…10
7
0.001
0
The first input point in the mA output control curve.
Scaled mA
output
value 1
0.0000…24.0000mA 0.0001mA 0mA
The mA output value when the measured value is equal
to or less than Input value 1.
Input value
2
-10
7
…10
7
0.001
1
The second input point in the mA output control curve.
Scaled mA
output
value 2
0.0000…24.0000mA 0.0001mA 0mA
The mA output value when the measured value is equal
to or greater than Input value 2.
Figure. 5.4.4 - 155. Example of the effects of mA output channel settings.
Table. 5.4.4 - 230. Hardware indications.
Name
Range
Step
Description
Hardware in mA output
channels 1...4
0: None
1: Slot A
2: Slot B
3: Slot C
4: Slot D
5: Slot E
6: Slot F
7: Slot G
8: Slot H
9: Slot I
10: Slot J
11: Slot K
12: Slot L
13: Slot M
14: Slot N
15: Too many cards
installed
-
Indicates the option card slot where the mA output card
is located.
Hardware in mA output
channels 5...8
Table. 5.4.4 - 231. Measurement values reported by mA output cards.
Name
Range
Step
Description
mA in Channel 1
0.0000…24.0000mA 0.0001mA Displays the measured mA value of the selected input
channel.
mA in Channel 2
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
310
© Arcteq Relays Ltd
IM00020
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...