Table. 5.3.19 - 162. Information displayed by the function.
Name
Range
Step
Description
N> LN
behaviour
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
Displays the mode of FSP block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.
N> condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays the status of the protection function.
Settings and signals
The settings of the frequent start protection are the directly stated motor data from the device's motor
module. The following table shows the other functions that also use these settings. If these settings are
edited through the frequent start protection function's setting view, they change in all other mentioned
functions at the same time.
Table. 5.3.19 - 163. Motor data settings.
Name
Range
Step Default Protection
functions
Description
Hot
condition
theta
limit
0.0…100.0% 0.1% 70%
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor
start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 50M)
Setting the motor's thermal limit in a hot or a cold situation. When
this setting value is not exceed while a locked rotor situation
occurs, the function uses a cold stall curve adjusted with the
actually used thermal capacity. The function uses a hot stall curve
when this setting value is exceeded. This setting also applies
to starts when the hot/cold selection is in use. Please note that
using this setting requires that the Machine thermal overload
protection (Tm>) function is activated and in use.
Safe stall
time cold 0.1…600.0s
0.1s
20.0s
- Motor
status
monitoring
- Frequent
start
protection
(N>; 48)
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor
start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 50M)
The safe stall time when the motor is cold. Unless this value is
specified, it is set to be equal to the hot stall time. Most probably
this leads to overprotection with the cold motor stall (best case
scenario). This setting value is used for the cold thermal stall
curve selection in automatic control. This parameter is also used
in the motor start-up and the number of starts calculations.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
201