Table. 5.3.16 - 149. Pick-up settings.
Name
Description
Range
Step
Default
Measured
magnitude
Defines which three phase power is used: Active, reactive
or apparent power.
0: P3PH
1: Q3PH
2: S3PH
-
0: P3PH
Nominal
MVA
reference
Defines whether the used nominal power is set manually or
if transformer or generator status monitoring function
defines the nominal power automatically.
0: Set manually
1: Use Gen nom MVA
2: Use Trafo nom MVA
-
0: Set
manually
Set
nominal
MVA
Nominal MVA used by the function. This parameter is visible
only when "Nominal MVA reference" parameter is set to "Set
manually"
0.0001...1000.0000MVA 0.0001MVA 10MVA
Pick-up
mode
Defines whether the function operates in underpower or
overpower protection mode.
0: > Over
1: < Under
-
0: Over
Pick-up
Pick-up setting. Related to the nominal power set by the
user.
-500.000…500.000%
0.005%
0%
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.16 - 150. Information displayed by the function.
Name
Range
Step
Description
PQS>/< LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of PWR block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
PQS>/<
condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays the status of the protection function.
Nominal MVA
used
0.000...1800.000MVA
0.001MVA
Displays the nominal power used by the function. This parameter is
displayed if "Nominal MVA reference" parameter has been set to
"Use Gen nom MVA" or "Use Trafo nom MVA".
Pick-up
setting
-1800.000...1800.000MVA 0.001MVA Pick-up setting used at the moment by the function. Value of this
parameter can change if setting group has been changed.
Measurement
now
-1800.000...1800.000MVA 0.001MVA Measured active, reactive or apparent power at the moment.
Meas/Set at
the moment
-1250.00...1250.00p.u.
0.01p.u.
Ratio between the measured power and pick-up setting.
Meas/Nom at
the moment
-1250.00...1250.00p.u.
0.01p.u.
Ratio between the measured power and used nominal power value.
Expected
operating
time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs.
Time
remaining to
trip
-1800.000...1800.000s
0.005s
When the function has detected a fault and counts down time
towards a trip, this displays how much time is left before tripping
occurs.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
174
© Arcteq Relays Ltd
IM00020