Figure. 5.3.13 - 83. Earth fault in an isolated network.
Figure. 5.3.13 - 84. Close-distance short-circuit between phases 1 and 3.
Negative sequence voltage calculation
Below is the formula for symmetric component calculation (and therefore to negative sequence voltage
calculation).
In what follows are three examples of negative sequence calculation (negative sequence component
vector).
Figure. 5.3.13 - 85. Normal situation.