Name
Range
Step
Default
Description
Continue
time
calculation
during
release
time
1: No
2: Yes
-
1: No
Time calculation characteristics selection. If activated, the operating time
counter continues until a set release time has passed even if the pick-up
element is reset.
The user can reset characteristics through the application. The default setting is a 60 ms delay; the
time calculation is held during the release time.
In the release delay option the operating time counter calculates the operating time during the release.
When using this option the function does not trip if the input signal is not re-activated while the release
time count is on-going.
Events and registers
The sequence voltage function (abbreviated "VUB" in event block names) generates events and
registers from the status changes in START, TRIP and BLOCKED. The user can select which event
messages are stored in the main event buffer: ON, OFF, or both. The function offers four (4)
independent stages; the events are segregated for each stage operation.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.13 - 133. Event messages.
Event block name
Event names
VUB1
Start ON
VUB1
Start OFF
VUB1
Trip ON
VUB1
Trip OFF
VUB1
Block ON
VUB1
Block OFF
VUB2
Start ON
VUB2
Start OFF
VUB2
Trip ON
VUB2
Trip OFF
VUB2
Block ON
VUB2
Block OFF
VUB3
Start ON
VUB3
Start OFF
VUB3
Trip ON
VUB3
Trip OFF
VUB3
Block ON
VUB3
Block OFF
VUB4
Start ON
VUB4
Start OFF
VUB4
Trip ON
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
159