Pick-up
The
Pick-up setting PF< (lead or lag) Trip and Pick-up setting PF< (lead or lag) Alarm setting
parameters control the the pick-up of the PF< function. They define the minimum allowed power factor
before action from the function. The function constantly calculates the ratio between the pick-up
settings and the measured magnitude (power factor). The reset ratio of 103 % is built into the function
and is always relative to the pick-up setting value.
Table. 5.3.22 - 183. Pick-up settings.
Name
Description
Range
Step Default
Available modes
Enables or disables alarming.
0: Trips
1: Trips
and alarms
-
1: Trips
and
alarms
Pick-up setting PF<
(lead or lag) Trip
Pick-up setting for tripping
0.05…0.99 0.01
0.8
Pick-up setting PF<
(lead or lag) Alarm
Pick-up setting for alarming. This parameter is only available when
"Available modes" parameter has been set to "Trip and alarm".
0.05…0.99 0.01
0.9
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.22 - 184. Information displayed by the function.
Name
Range
Step
Description
PF< LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of UPF block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.
PF< condition
0: Normal
1: Start
2: Trip
3: Blocked
4: Alarm Start
5: Alarm
-
Displays status of the protection function.
Expected
alarming time
0.000...1800.000s
0.005s Displays the expected alarming time when a fault occurs.
Time remaining
to alarm
0.000...1800.000s
0.005s When the function has detected a fault and counts down time towards an
alarm, this displays how much time is left before alarm is activated.
PF
meas
/
PF
alarm
at the
moment
0.00...1250.00
0.01
The ratio between the measured power factor and the alarm pick-up
value.
Expected
operating time
0.000...1800.000s
0.005s Displays the expected operating time when a fault occurs.
Time remaining
to trip
-1800.000...1800.000s 0.005s When the function has detected a fault and counts down time towards a
trip, this displays how much time is left before tripping occurs.
PF
meas
/ PF
set
at the moment
0.00...1250.00
0.01
The ratio between the measured power factor and the pick-up value.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
217