7. –15. Scan
A similar operation to Scan 6 (checks which designations have been reserved by modules in
previous slots and numbers the new ones accordingly).
Thus far this document has only explained the installation of I/O add-on cards to the option module
slots. This is because all other module types are treated in a same way. For example, when an
additional communication port is installed into the upper port of the communication module, its
designation is Communication port 3 or higher, as Communication ports 1 and 2 already exist in the
CPU module (which is scanned, and thus designated, first). After a communication port is detected, it
is added into the device's communication space and its corresponding settings are enabled.
The partially optioned example case of AQ-X255-XXXXXXX-BBBBBCAAAA
BBBBBCAAAAJJ (the first image pair, on
the right) has a total of 43 digital input channels available: three (DI1…DI3) in the CPU module, and the
rest in Slots C…H in groups of eight. It also has a total of 10 digital output channels available:
five (DO1…DO5) in the CPU module, and five (DO6…DO10) in Slot I. Additionally, there is a double
(LC) fiber Ethernet communication option card installed in Slot N. These same principles apply to all
non-standard configurations in the AQ-X255 IED family.
8.2 CPU module
Figure. 8.2 - 193. CPU module.
Connector
Description
COM A
Communication port A, or the RJ-45 port. Used for the setting tool connection and for IEC 61850, Modbus/
TCP, IEC 104, DNP3 and station bus communications.
COM B
Communication port B, or the RS-485 port. Used for the SCADA communications for the following protocols:
Modbus/RTU, Modbus I/O, SPA, DNP3, IEC 101 and IEC 103. The pins have the following designations: Pin 1
= DATA +, Pin 2 = DATA –, Pin 3 = GND, Pins 4 & 5 = Terminator resistor enabled by shorting.
X1-1
Digital input 1, nominal threshold voltage 24 V, 110 V or 220 V.
X1-2
Digital input 2, nominal threshold voltage 24 V, 110 V or 220 V.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
386
© Arcteq Relays Ltd
IM00020
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...