Settings
Table. 5.3.24 - 200. General settings of the function.
Name
Range
Default
Description
RTD LN mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
0: On
Set mode of RTD block.
This parameter is visible only when
Allow setting of individual LN mode is enabled
in
General menu.
RTD LN
behaviour
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
Displays the mode of RTD block.
This parameter is visible only when
Allow setting of individual LN mode is enabled
in
General menu.
Table. 5.3.24 - 201. Function settings for Channel x (Sx).
Name
Range
Step
Default
Description
S1...S16 enable
0: No
1: Yes
-
0: No
Enables/disables the selecion of sensor
measurements and alarms.
S1...S16 module
0: InternalRTD1
1: InternalRTD2
2: ExtModuleA
3: ExtModuleB
4: ExtModuleC
-
0:
InternalRTD1
Selects the measurement module. Internal RTD
modules are option cards installed to the relay.
External modules are Modbus based external
devices.
S1...S16 channel
0: Channel 0
1: Channel 1
3: Channel 2
4: Channel 3
5: Channel 4
6: Channel 5
7: Channel 6
8: Channel 7
-
0: Channel 0 Selects the measurement channel in the selected
module.
S1...S16 Deg C/Dec F
0: Deg C
1: Deg F
-
0: Deg C
Selects the measurement temperature scale (Celsius
or Fahrenheit).
S1...S16 Measurement -
-
-
Displays the measurement value in the selected
temperature scale.
S1...S16 Sensor
0: Ok
1: Invalid
-
-
Displays the measured sensor's data validity. If the
sensor reading has any problems, the sensor data is
set to "Invalid" and the alarms are not activated.
S1...S16 Enable alarm
1
0: Disable
1: Enable
-
0: Disable
Enables/disables the selection of Alarm 1 for the
measurement channel x.
S1...S16 Alarm1 >/<
0: >
1: <
-
0: >
Selects whether the alarm activates when
measurement is above or below the pick-up setting
value.
S1...S16 Alarm1
-101.0…2000.0deg 0.1deg 0.0deg
Sets the pick-up value for Alarm 1. The alarm is
activated if the measurement goes above or below
this setting mode (depends on the selected mode in
"Sx Alarm1 >/<").
S1...S16 sensor
0: Ok
1: Invalid
-
-
Displays the measured sensor's data validity. If the
sensor reading has any problems, the sensor data is
set to "Invalid" and the alarms are not activated.
S1...S16 Enable alarm
2
0: Disable
1: Enable
-
0: Disable
Enables/disables the selection of Alarm 2 for the
measurement channel x.
S1...S16 Alarm2 >/<
0: >
1: <
-
0: >
Selects whether the measurement is above or
below the setting value.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
254
© Arcteq Relays Ltd
IM00020
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...