Table. 5.3.8 - 91. Pick-up settings.
Name
Range
Step
Default
Description
I
set
0.01…40.00×I
n
0.01×I
n
0.20×I
n
The pick-up threshold for the phase current measurement. This setting
limit defines the upper limit for the phase current pick-up element.
I0
set
0.005...40.000×I
n
0.001×I
n
1.200×I
n
The pick-up threshold for the residual current measurement. This setting
limit defines the upper limit for the phase current pick-up element.
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active. There is no delay between
the activation of the monitored signal and the activation of the pick-up when using binary signals.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.8 - 92. Information displayed by the function.
Name
Range
Description
CBFP LN
behaviour
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
Displays the mode of CBF block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.
CBFP condition
0: Normal
1: Start
2: ReTrip
3: CBFP On
4: Blocked
Displays status of the protection function.
Function blocking
The block signal is checked in the beginning of each program cycle. The blocking signal is received
from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when
the pick-up element activates, a START signal is generated and the function proceeds to the time
characteristics calculation.
If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and
the function does not process the situation further. If the START function has been activated before the
blocking signal, it resets and processes the release time characteristics similarly to when the pick-up
signal is reset.
The blocking of the function causes an HMI display event and a time-stamped blocking event with
information of the startup current values and its fault type to be issued.
The blocking signal can also be tested in the commissioning phase by a software switch signal when
the relay's testing mode "Enable stage forcing" is activated (
General
→
Device).
The variables the user can set are binary signals from the system. The blocking signal needs to reach
the device minimum of 5 ms before the set operating delay has passed in order for the blocking to
activate in time.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
109
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...