6.1.7 DNP3
DNP3 is a protocol standard which is controlled by the DNP Users Group (www.dnp.org). The
implementation of a DNP3 slave is compliant with the DNP3 subset (level) 2, but it also contains some
functionalities of the higher levels. For detailed information please refer to the DNP3 Device Profile
document (
→
AQ-200 series
→
Resources).
Settings
The following table describes the DNP3 setting parameters.
Table. 6.1.7 - 287. Settings.
Name
Range
Step Default
Description
Enable
DNP3 TCP
0:
Disabled
1:
Enabled
-
0:
Disabled
Enables and disables the DNP3 TCP communication protocol when the
Ethernet port is used for DNP3. If a serial port is used, the DNP3 protocol can
be enabled from
Communication
→
DNP3.
IP port
0…65
535
1
20 000
Defines the IP port used by the protocol.
Slave
address
1…65
519
1
1
Defines the DNP3 slave address of the unit.
Master
address
1…65
534
1
2
Defines the address for the allowed master.
Link layer
time-out
0…60
000ms
1ms
0ms
Defines the length of the time-out for the link layer.
Link layer
retries
1…20
1
1
Defines the number of retries for the link layer.
Diagnostic -
Error counter 0…2
32
-1 1
-
Counts the total number of errors in received and sent messages.
Diagnostic -
Transmitted
messages
0…2
32
-1 1
-
Counts the total number of transmitted messages.
Diagnostic -
Received
messages
0…2
32
-1 1
-
Counts the total number of received messages.
Default variations
Table. 6.1.7 - 288. Default variations.
Name
Range
Default
Description
Group 1 variation (BI)
0: Var 1
1: Var 2
0: Var 1
Selects the variation of the binary signal.
Group 2 variation (BI change)
0: Var 1
1: Var 2
1: Var 2
Selects the variation of the binary signal change.
Group 3 variation (DBI)
0: Var 1
1: Var 2
0: Var 1
Selects the variation of the double point signal.
Group 4 variation (DBI change)
0: Var 1
1: Var 2
1: Var 2
Selects the variation of the double point signal.
Group 20 variation (CNTR)
0: Var 1
1: Var 2
2: Var 5
3: Var 6
0: Var 1
Selects the variation of the control signal.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00020
367
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...